11
LCD Setting
After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press “SELECT”
button to select setting programs. And then, press “ENTER” button to confirm the selection or ESC button to
exit.
Setting Programs:
Program
Description
Selectable option
00
Exit setting mode
Escape
02
Output voltage
220V (default)
230V
240V
03
Output frequency
50Hz (default)
60Hz
04
Maximum utility charging
current
2A
10A (default)
20A
30A
40A
50A
60A
05
Bulk charging voltage
(C.V voltage)
Default setting: 56.4V
This program can be set up. Setting range is from 48.0V to
58.4V for 48V model. Each click increment 0.1V.
06
Floating charging voltage
Default setting: 54V
This program can be set up. Setting range is from 48.0V to
58.4V for 48V model. Each click increment 0.1V.
07
Low DC cut-off voltage
Default setting: 42V
This program can be set up. Setting range is from 40.0V to
48.0V for 48V model. Each click increment 0.1V. Low DC
cut-off voltage will be fixed to setting value no matter what
percentage of load is connected.
09
Power saving mode
enable/disable
Saving mode disable
(default)
If disabled, no matter connected load
is low or high, the output (on/off
status) of inverter will not be affected.
Saving mode enable
If enabled, the output of inverter will
be off when connected load is pretty
low or not detected.