16
SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL
5KW
Input Voltage Waveform
Sinusoidal (utility or generator)
Nominal Input Voltage
220Vac
Low Loss Voltage
170Vac± 3V
Low Loss Return Voltage
180Vac± 3V
High Loss Voltage
255Vac± 3V
High Loss Return Voltage
245Vac± 3V
Max AC Input Voltage
300Vac
Nominal Input Frequency
50Hz / 60Hz (Auto detection)
Low Loss Frequency
47.5± 1Hz
Low Loss Return Frequency
48± 1Hz
High Loss Frequency
52.5± 1Hz
High Loss Return Frequency
52± 1Hz
Output Short Circuit Protection
Line mode: Circuit Breaker; Battery mode: Electronic Circuits
Efficiency (Line Mode)
>97% ( Rated R load, battery full charged )
Transfer Time
*
10ms typical
*Transfer time may be longer than specified figure when the unit is operating in parallel system.
Table 2 Inverter Mode Specifications
INVERTER MODEL
5KW
Rated Output Power
5KVA/5KW
Output Voltage Waveform
Pure Sine Wave
Output Voltage Regulation
220Vac± 5%
Output Frequency
60Hz or 50Hz
Peak Efficiency
90%
Overload Protection
5s@≥150% load; 10s@110%~150% load
Surge Capacity
2* rated power for 5 seconds
Nominal DC Input Voltage
48Vdc
Cold Start Voltage
46.0Vdc
Low DC Warning Voltage
@ load < 20%
44.0Vdc
@ 20% ≤ load < 50%
42.8Vdc
@ load ≥ 50%
40.4Vdc
Low DC Warning Return Voltage
@ load < 20%
46.0Vdc
@ 20% ≤ load < 50%
44.8Vdc
@ load ≥ 50%
42.4Vdc
Low DC Cut-off Voltage
@ load < 20%
42.0Vdc
@ 20% ≤ load < 50%
40.8Vdc
@ load ≥ 50%
38.4Vdc
High DC Recovery Voltage
58Vdc
High DC Cut-off Voltage
60Vdc
No Load Power Consumption
<50W
Saving Mode Power Consumption
<15W