Contact current (direct measurement method)
Measurement range
Resolution
Accuracy
0.1 mA - 1.99 mA
0.01 mA
±(5% + 2)
Rated voltage: 230 V ±10% (as for mains supply)
Rated current: 16 A
Max. breaking capacity: 3000 VA
Max. lamp load: 1000 W
Max. measurement time: 30 seconds
Pre-set limit value 0.5 mA (protection class 2)
Protected against external voltages: Max. 276 V
For non-sinusoidal power supply, an additional error must be taken into account:
Crest factor of >1.4 to 2.0, additional error +3.1%
.
Testing of extension cables and cable drums
Measurement of the protective conductor resistance (for data, see above)
Measurement of the insulation resistance (for data, see above)
Lead break test of the external conductor (L) and the neutral conductor (N)
Short-circuit test of external conductor (L) and neutral conductor (N)
Tripping time of RCCB/RCD
Measurement range
Resolution
Accuracy
10 ms - 500 ms
1 ms
±(5% + 2)
Testing of current/polarity: 30 mA sinusoidal/0° and 180°, 150 mA sinusoidal /0° and 180°
Pre-set limit value 200 ms (30 mA), 40 ms (150 mA)
Protective conductor current (direct measurement method with optional measurement adapters)
Measurement range
Resolution
Accuracy
0.25 mA - 9.99 mA
0.01 mA
±(5% + 2)
Rated voltage: 3x 400 V ±10% (as for mains supply)
Rated current: 16 A
Pre-set limit value 3.5 mA
Summary of Contents for 2238757
Page 9: ...9 6 Einzelteilbezeichnung IPE IB 250 V 500 V RCD Phase 3 12 8 ...
Page 44: ...44 6 Overview of parts IPE IB 250 V 500 V RCD Phase 3 12 8 ...
Page 79: ...79 6 Désignation des pièces détachées IPE IB 250 V 500 V RCD Phase 3 12 8 ...
Page 115: ...115 6 Overzicht van de onderdelen IPE IB 250 V 500 V RCD Phase 3 12 8 ...
Page 143: ...143 ...