Battery Capacity Level Charging Current
20AH to 50AH L Low (3A~5A)
60AH to 100AH M Medium (7A~9A)
100AH to 200AH H High (10A~15A)
Wrong selection of the charging current may lead to the damage of
battery in charging process!
5.3. CHARGING CURRENT SELECTOR
I
t’s recommended to select the charging current as below:
9
5.4. MUTE BUZZER BEEPING
•
Temporary Mute Button
At battery mode, press and hold the
TEMPORARY MUTE BUTTON
for 1~2
seconds, the UPS will be muted. When mains power restore, the UPS will work
at mains mode, if mains power is failure again, the
MUTE FUNCTION
will be
disabled, the UPS will beep till press this button again.
•
Permanent Mute Button
Press up the
, the UPS won’t give beeping at
PERMANENT MUTE BUTTON
any cases. Press it down to cancel the “mute mode”.
5.5. WORK AS AVR (AUTOMATIC VOLTAGE REGULATOR)
At mains mode, the UPS works as an AVR, offering regulated output and surge
protection to the connected appliances.
6. MAINTENANCE OF BATTERY
With correct using and maintenance, the life of the battery can last for three to
six years, depending on the times of discharging and temperature. So regular
check and maintenance are very necessary.
• Charge the battery every three months if you don’t use the UPS for a long
time. The charging time should be at least 12 hours.
• If the UPS works continuously in mains mode for more than fours months,
please discharge the battery with 50% of rated load, so as to keep the battery
be active.
• For more details, please refer to the specification of the battery