7. ALARM AND PROTECTION
7.1. BATTERY MODE ALARM
The UPS will beep once (4 continous sound) every 30 seconds when working
at battery mode.
7.2. BATTERY LOW VOLTAGE ALARM AND SHUT DOWN
The UPS will beep once per second when battery is in low level. When the
battery is near empty, it will beep rapidly for 20 seconds and then shut down
automatically.
7.3. OVERHEAT ALARM AND PROTECTION
When the temperature of transformer winding/heat sink is exceeding the limit.
Mains Mode:
UPS will beep once per second only, the output won’t be cut off.
Battery Mode:
the output will be cut off immediately,the UPS will beep rapidly
for around 20 seconds, then shut down automatically.
7.4. SHORT CIRCUIT
Mains Mode:
the circuit breaker will cut off the input power automatically once
a short circuit happens.
Battery Mode:
UPS will cut off output immediately, and beep rapidly for around
20 seconds, then shut down automatically
.
7.5. OVERLOAD ALARM PROTECTION
Mains Mode:
UPS will beep once per second, until the overload is removed.
Battery Mode:
• when load is is >120%, the UPS will beep once every second for 30 seconds,
then shut down automatically.
• when load is >150%, the output of UPS will cut off immediately, and start to
beep rapidly for 20 seconds, then shut down automatically.