background image

 L     N     L     N                    

INPUT

OUTPUT

BATTERY

+ -

For models: 3000VA/5000VA:

C. Make sure the appliances are turned o 

before connect

ion

.

D. Connect the mains to the 

“INPUT” terminal

, the load to the 

“OUTPUT”

terminal. Make sure connections are tighten, not loose.  

А. 

Make sure use connection cables in correct diameter.

B. Make connection as shown in below chart. 

I

nput & Ou

tput Cable

PSU-816-5000VA  

48VDC, 3000W)

PSU-816-

3

000VA

 

48

VDC, 18

0

0W)

Model No.

12AWG

 

/

 

3.332mm

²

14AWG

 

/

 

2.075mm

²

If there are two or more appliances are connected, make sure the total 
maximum capacity of connected appliances does not exceed the rated 
capacity of UPS.

8

5. OPERATION OF THE UPS

5.1. TURN ON THE UPS

Press and hold the

 till the UPS give one 

 

INVERTER ON/OFF SWITCH

beeping sound, the UPS is switched on and delivers output.

Then switch on the connected appliances one by one. If there are two or many
appliances connected, please turn on the biggest one at the first, the smallest 
one at the last, according to their rated power.

5.2. TURN OFF THE UPS

Turn off the appliances on by one, then press 

 

INVERTER ON/OFF SWITCH

till the UPS give one beeping sound again, the output is turned off.

Even if the output of UPS is turned off, the UPS is still working to 
charge the battery, the UPS is not totally switched off. To switch 
it off completely,

 

unplug the UPS from the mains power.

[email protected]

 (58) 341-05-06 | [email protected] (58) 341-38-80 | [email protected] (22) 100-42-99 

Summary of Contents for PSU-816-1000VA

Page 1: ...HARGER INVERTER SINUS PROTECT 900 VOLT POLSKA Sp z o o ul Grunwaldzka 76 81 771 Sopot www voltpolska pl sales voltpolska pl 58 341 05 06 przemek voltpolska pl 58 341 38 80 bartek voltpolska pl 22 100...

Page 2: ...ncludes important safety instructions for operation and correct installation of the UPS PLEASE READ AND KEEP THIS MANUAL This symbol gives information warnings and other suggestions This symbol gives...

Page 3: ...TURN OFF THE UPS 5 3 CHARGING CURRENT SELECTOR 5 4 MUTE BUZZER BEEPING 5 5 WORK AS AVR AUTOMATIC VOLTAGE REGULATOR 6 MAINTENANCE OF BATTERY 7 ALARM AND PROTECTION 7 1 BATTERY MODE ALARM 7 2 BATTERY L...

Page 4: ...rding to the current capacity All units earth connections which are connected to UPS should be done with earth cable Without earth connection or unproved earth connected units are dangerous for user s...

Page 5: ...accurate output and protection AVR automatic voltage regulator function at mains mode Best for places where the mains voltage is extremely unstable Heavy duty transformer and circuit With the high e c...

Page 6: ...de 80 max Mains mode 95 max Pure sine wave 4ms 3 stages selectable by user Low 3A 5A Medium 7A 9A High 10A 15A Yes CE EMC LVD IEC62040 56dB at 1m distance with full load 10 C 40 C 10 90 non condensing...

Page 7: ...ep away from windows dust moisture and cold places Keep away from fire heat sources Keep away from corrosive gas or fluid Operating temperature 10 C 40 C Operating humidity 10 90 non condensing Operat...

Page 8: ...N OFF Switch 1 2 3 Overload Error Battery Mode Mains Mode A Front Side of the UPS Battery Capacity Output Voltage Intput Voltage Load Rate Battery Capacity Load Rate 20 40 60 80 100 sales voltpolska p...

Page 9: ...NG CURRENT OUTPUT AC INPUT CHARGING CURRENT COOLING FAN CIRCUIT BREAKER COOLING FAN 2 3 INPUT OUTPUT BATTERY 1 Cooling Fan 2 Battery Terminal 3 Battery Terminal 4 Input Circuit Breaker 5 Output Socket...

Page 10: ...d be damaged easily Diameter Battery Cable PSU 816 500VA 12VDC 300W PSU 816 300VA 12VDC 180W PSU 816 800VA 12VDC 480W PSU 816 1500VA 24VDC 900W PSU 816 2000VA 24VDC 1200W PSU 816 900VA 12VDC 600W Mode...

Page 11: ...ERATION OF THE UPS 5 1 TURN ON THE UPS Press and hold the till the UPS give one INVERTER ON OFF SWITCH beeping sound the UPS is switched on and delivers output Then switch on the connected appliances...

Page 12: ...NT MUTE BUTTON any cases Press it down to cancel the mute mode 5 5 WORK AS AVR AUTOMATIC VOLTAGE REGULATOR At mains mode the UPS works as an AVR o ering regulated output and surge protection to the co...

Page 13: ...diately the UPS will beep rapidly for around 20 seconds then shut down automatically 7 4 SHORT CIRCUIT Mains Mode the circuit breaker will cut o the input power automatically once a short circuit happ...

Page 14: ...to clean the body and ventilation holes 8 2 EXTRAORDINARY INSPECTION When malfunction occurs or the UPS is abnormal please measure and check the parameters refer to the authorized dealer if needed In...

Page 15: ...Wait till the input voltage or input requency is normal Press and hold the power switch till the UPS give a beeping sound Others Others UPS is overloaded UPS is overheating Ventilation holes are bloc...

Page 16: ...pay the cost of inverter repair due to expiration of the warranty period warranty void Before proceeding with the repair service will inform by phone about the exact costs of the repair Please attach...

Reviews: