L N L N
INPUT
OUTPUT
BATTERY
+ -
For models: 3000VA/5000VA:
C. Make sure the appliances are turned o
ff
before connect
ion
.
D. Connect the mains to the
“INPUT” terminal
, the load to the
“OUTPUT”
terminal. Make sure connections are tighten, not loose.
А.
Make sure use connection cables in correct diameter.
B. Make connection as shown in below chart.
I
nput & Ou
tput Cable
PSU-816-5000VA
(
48VDC, 3000W)
PSU-816-
3
000VA
(
48
VDC, 18
0
0W)
Model No.
12AWG
/
3.332mm
²
14AWG
/
2.075mm
²
If there are two or more appliances are connected, make sure the total
maximum capacity of connected appliances does not exceed the rated
capacity of UPS.
8
5. OPERATION OF THE UPS
5.1. TURN ON THE UPS
Press and hold the
till the UPS give one
INVERTER ON/OFF SWITCH
beeping sound, the UPS is switched on and delivers output.
Then switch on the connected appliances one by one. If there are two or many
appliances connected, please turn on the biggest one at the first, the smallest
one at the last, according to their rated power.
5.2. TURN OFF THE UPS
Turn off the appliances on by one, then press
INVERTER ON/OFF SWITCH
till the UPS give one beeping sound again, the output is turned off.
Even if the output of UPS is turned off, the UPS is still working to
charge the battery, the UPS is not totally switched off. To switch
it off completely,
unplug the UPS from the mains power.