30
The displayed parameters are the following:
engine speed:
RPM
(traditional alternators)
current supplied:
A
frequency:
Hz
(traditional alternators)
hour-meter:
hourglass
load indicator:
% e bar
pre heating:
glows
(PAGURO 6000 / 9000 / 14000 / 18000
/ 6500 / 8500 / 16500 / 22 EK / 9000v /
12000v)
PAGURO STARTING AND STOPPING:
GENERATORS WITHOUT PREHEATING (PAGURO 2000 / 3 SY / 3000 / 4 SY / 4000 / 5000 /
12500):
To start push and keep pushed START button up to the generators is started.
To stop push and release STOP button.
GENERATORS WITH PREHEATING (PAGURO 6000 / 9000 / 14000 / 18000 / 6500 / 8500 / 16500
/ 22 EK / 9000v / 12000v):
To start push and keep pushed START button; the remote control panel let start the preheating
procedure and then after 10 sec., automatically let start the generator; release the START
button when the generator is started.
To stop push and release STOP button.
ALARM MANAGEMENT:
The control panel monitors several parameters to detect anomalies on the generator and turn it
off if necessary to avoid damage; the controlled parameters are the following
overtemperature / low oil pressure:
the generator stops, and the display appears the alarm and the red light is lighted.
electrical overload:
the generator does not stop and the red led is lighted. A proper circuit breaker must always be
installed on the board plant.
In the case of activation of an alarm will appear an indication relating to the alarm; to reset the
alarm, proceed as follows:
push either UP ARROW or DOWN ARROW buttons: on the display disappers the alarm. The
red light remains lighted.
push and keep pushed for 5 sec either UP ARROW or DOWN ARROW buttons: the red light
turn off.