background image

22

NOTES

When the request for heating and/or hot water has
been satisfied, the appliance pump and fan may
continue to circulate to dissipate any residual heat
within the appliance

.

7.3

SERVICE MODE & PARAMETERS

To check or adjust the service parameters you
must first access the service mode. This mode is
only accessible in OFF mode. To access the
service mode: push INFO and MODE buttons at
the same time for 10 seconds to enter the adjust-
ing menu. The display shows “CodE” (see fig. 36).
Push MODE button and select the service param-
eters code by turning the RH (right-hand) encoder
and confirm it by pushing MODE button

.

7.3.1

PARAMETERS SETTING

Turn the RH (right-hand) encoder to display all
parameters and their values (see fig. 37). When
the required parameter is displayed, push the
MODE button, the current (parameter) value will
flash. To change the parameter value, rotate the
RH (right-hand) encoder until the required value is
displayed, push the MODE button to store the new
value. To exit the service mode push INFO button.

7.4

ADJUSTING MODE & ADJUSTING THE GAS
VALVE

THE GAS VALVE MUST BE SET-UP OR AD-
JUSTED WITH THE AID OF A PROPERLY CALI-
BRATED FLUE GAS ANALYSER.

Fig. 37

Parameter value

Parameter number

Par.

Action

01

set gas type

HP

max fan speed

LP

min fan speed

SP

start-up fan speed

HH

force burner to max power

LL

force burner to min power

MM

force burner to medium power

Isolate the appliance from the electrical supply
and remove the appliance casing as described in
4.7.1. Set the flue gas analyser to read CO

2

 and

insert the probe into the flue analysis test point (

A,

fig. 35). Restore the electrical supply to the

boiler and switch on the boiler. To adjust the gas
valve you must first access the adjusting mode.
This mode is only accessible in STANDBY mode.
To access the adjusting mode: push INFO and
MODE buttons at the same time for 10 seconds to
enter the adjusting menu. The display shows
“CodE” (see fig. 36). Push MODE button and
select the adjust parameters password by turning
the RH (right-hand) encoder and confirm it by
pushing MODE button. The following functions are
available in this mode.

7.4.1

GAS TYPE SETTING - 1

Select the parameter 1 by turning the RH (right-
hand) encoder; push MODE button, it is possible
to set gas type: 1(natural gas) - 2 (LPG), by turn-
ing the RH (right-hand) encoder. Push MODE but-
ton to store the gas type selected.

ATTENTION

Gas type and boiler output 

must be 

according to

the boiler design specification. Vokera accepts no
responsibility if the gas type and boiler output are
set not according to the appliance specification.

7.4.3

ABSOLUTE MAX FAN SPEED - HP

Select the parameter HP by turning the RH (right-
hand) encoder; push MODE button, it is possible
to set the absolute max fan speed that is related
to gas type and boiler output. Modify this param-
eter only if strictly necessary. The value is shown
on the display as rpm/100 (i.e. 3600/100 = 36). The
set value automatically modifies the max value of
parameter 23.

7.4.4

ABSOLUTE MIN FAN SPEED - LP

Select the parameter LP by turning the RH (right-
hand) encoder; push MODE button, it is possible
to set the absolute min fan speed that is related to
gas type and boiler output. Modify this parameter
only if strictly necessary. The value is shown on
the display as rpm/100 (i.e. 3600/100 = 36). The
set value automatically modifies the min value of
parameter 24.

7.4.5

START-UP FAN SPEED - SP

Select the parameter SP by turning the RH (right-
hand) encoder; push MODE button, it is possible
to set the start-up fan speed. Modify this param-
eter only if strictly necessary. The value is shown
on the display as rpm/100 (i.e. 3600/100 = 36).

7.4.6

GAS VALVE MAXIMUM SETTING - HH

Select the HH parameter by turning the RH (right-
hand) encoder; the boiler starts at the maximum
power, the CO

2

 reading should be as shown in the

table below (for LPG see 9.2).

If the CO

2

 reading is correct, pass to gas valve

minimum setting (7.4.7). If the CO

2

 reading is

incorrect, the maximum gas pressure must be
adjusted as follows:

Fig. 36

MODE

INFO

Summary of Contents for MYNUTE 35HE

Page 1: ...Installation Servicing Instructions THESEINSTRUCTIONS TO BE RETAINED BY USER 0694 0694BQ0479...

Page 2: ...on analysis 15 5 8 Final flushing of the heating system 15 5 9 Setting the boiler operating temperature 15 5 10 Setting the system design pressure 16 5 11 Regulating the central heating system 16 5 12...

Page 3: ...ansion ves sel safety valve pressure gauge and automatic by pass The35HEisproducedasaroomsealed categoryII2H3P appliance suitableforinternalwallmountingapplications only It is provided with a fan powe...

Page 4: ...try to ensure flame stability at the burner Once suc cessful ignition has been achieved the electronic circuitryincreasesthegasrateto75 foraperiod of 15 minutes Thereafter the boiler s output will eit...

Page 5: ...ions Height 845 mm Width 453 mm Depth 359 mm Dry weight Kg 43 0 2 5 Clearances Sides 12 mm Top 150 mm from casing or 25 mm above flue elbow whichever is applicable Bottom 150 mm Front 600 mm 2 6 Conne...

Page 6: ...tc 500 mm D Below gutter drain pipe etc 75 mm E Below eaves 200 mm F Below balcony car port roof etc 1200 mm G To the side of a soil drain pipe etc 150 mm H From internal external corner or boundary 3...

Page 7: ...entrally over the terminal Refer to BS 5440 Part 1 when the terminal is 0 5 metres or less below plastic guttering or 1 metre or less below painted eaves BS5440 PART 1 FLUES BS5440 PART 2 FLUES VENTIL...

Page 8: ...fuse The method of connection to the mains electricity supply must allow for com plete isolation from the supply The preferred method is by using a double pole switch with a contact separation of at...

Page 9: ...hosenfortheappliancemustpermit the provision of a safe and satisfactory flue and termination The location must also permit an adequateairsupplyforcombustionpurposesand anadequatespaceforservicingandai...

Page 10: ...he system has an unusually high water content it may be necessary to provide additional expansion capacity see 6 19 3A 6 6 FILLING POINT Amethodforinitialfillingofthesystemandreplacing water lost duri...

Page 11: ...te supplied carefully mark the position of the wall mounting bracket see fig 6 and flue hole if applicable 4 5 FITTING THE FLUE The top flue outlet permits both horizontal and verticalflueapplications...

Page 12: ...to ensurethatthecorrectsealismadewhenassem blingthefluesystem Connecttherequirednumber of flue extensions or bends up to the maximum equivalentfluelength totheflueterminal seefig 7 8 The flue system...

Page 13: ...the dedi cated concentric flue kit for termination It is essential that the installation of the twin flue system be carried out in strict accordance with these instructions GUIDANCE NOTES ONTWIN FLUE...

Page 14: ...in flue pipes must be pushed 50mm onto the male spigots of the concentric to twin converter NOTE Seal the flue terminal assembly to the wall using cement or a suitable alternative that will provide sa...

Page 15: ...nlet of the valve and tighten both nuts NOTE Itwillbenecessarytocalculatethediameterofthe gas supply pipe to ensure the appliance has an adequate supply of gas 4 6 2 FLOW RETURN fig 6 The appliance is...

Page 16: ...B cover C Fig 15 Optional devices 24V terminal block Mains 230V terminal block 4 7 2 APPLIANCETERMINALBLOCK Theapplianceterminalblockislocatedontherear of the control fascia Remove the casing as descr...

Page 17: ...ensure the proper electrical checks have been carried out see 7 8 particularly continuity polarity and resistance to earth ensure the 3 AMP fuse supplied with the appliance has been fitted ensure the...

Page 18: ...LY SECURED ENSURE ALL PIPE WORK IS RE CHECKED FORSOUNDNESS RE FIT APPLIANCE CASING COMPLETEBENCHMARKCHECKLIST FOR UK ONLY Complete details of the boiler controls installa tionandcommissioningintheBenc...

Page 19: ...ugh it is anticipated that this appliance will give years of reliable trouble free service the life spanofcomponentswillbedeterminedbyfactors such as operating conditions and usage Should the applianc...

Page 20: ...rolfasciaupwardandrotate it Locateandremovethescrews A whichsecure the PCBcover pushtheclips B andremovecover after carefullytakingnoteofallwiringconnections discon nect all wiring from the PCB locate...

Page 21: ...re it is replaced correctly Replace in the reverse order 6 16 MAIN HEAT EXCHANGER fig 29 30 Carry out component removal procedure as de scribed in 6 4 Unclip and remove the three air chambercovers fro...

Page 22: ...tandleft side covers Disconnect the fan transformer wiring Locateandremovethe2screws D thatsecurethefan transformer to the air box plate cut the two cable ties previewedonheat shrinkableinsulatorsthat...

Page 23: ...of the primary thermistor reaches 30 C There after the pump fan will over run for 30 sec onds Pump anti block cycle when there has been noheatingorHWrequestfor24 hours theanti block cycle is activate...

Page 24: ...ee fig 36 Push MODE button and selecttheadjustparameterspasswordbyturning the RH right hand encoder and confirm it by pushingMODEbutton Thefollowingfunctionsare available in this mode 7 4 1 GAS TYPE S...

Page 25: ...liance however you must check that the CO2 values are set correctly see 7 4 Insert the flue gas analyser probe into the flue gas test point see fig 35 Operate the boiler in HH LL and compare the value...

Page 26: ...ition 13 check the wiring harness 23 check the wiring harness 25 high limit flow temperature probe 27 high limit return temperature probe 31 internal fault 35 fan error 36 internal fault 41 low water...

Page 27: ...odes 6x appear if a problem exists with the secondary DHW thermistor Check thermistor Check wiring continuity FAULT CODES 5x Fault codes 5x appear if a problem with the main board exists Check paramet...

Page 28: ...3600 1 25 Differential heating positive C 2 10 1 6 26 Differential heating negative C 2 10 1 6 28 CH timer force burner 75 after CH start Min 0 20 1 15 29 CH timer blocking time CH Min 0 20 1 5 30 CH...

Page 29: ...win channel programmers figs 40 41 The appliance can be used in conjunction with typi cal S Plan Y Plansystems see8 4 1 8 4 2 please contact Vokera technical should you requirefurtherdetailedinstructi...

Page 30: ...28 8 4 1 Y PLANWITH EXTERNALTWIN CHANNEL PROGRAMMER fig 40 8 4 2 S PLANWITH EXTERNALTWIN CHANNEL PROGRAMMER fig 41 Fig 40 Fig 41...

Page 31: ...S Outside sensor WPS Water pressure sensor FS Flow termoster RS Return termoster AE01A P1 Master board AE01A P2 Ausiliary board controll M0T2B Motor control board AC0X Display board K9 Pump relay K13...

Page 32: ...cover assembly 10025842 26 Instrumental panel 10027949 31 Case 10026241 38 Driver PCB 10027200 90 Fuse 3478 226 Edge clip 5128 300 Wiring harness 10026341 301 Wiring harness 10027953 302 Wiring harnes...

Page 33: ...ctions cover 10027685 63 Pipe 10026228 105 Pressure transductor 10027132 201 Washer 5026 265 Washer 5236 266 Washer 5237 288 Washer 6898 290 Clip 2165 351 Nut 1823 353 Nut 1824 432 Clip 10024958 435 C...

Page 34: ...6338 6 Pipe 10026264 7 Pipe 10027317 9 Pipe 10027318 10 Pipe 10027146 17 Air vent bottle 10026275 25 Siphon 10027190 26 Flexible pipe 10027191 27 Flexible pipe 10027192 48 Pipe 10027321 66 Flexible pi...

Page 35: ...veyor 10026309 39 Gas pipe 10027196 46 Gas diaphragm 10027162 46 Gas diaphragm 2111 67 Washer 10026322 69 Tryton 10027089 72 Mixer 10024295 200 Washer 5023 479 Transformer 10026237 480 Transformer 100...

Page 36: ...r assembly 01005369 7 Conveyor assembly 10026310 12 Flue drain connection 10026311 27 Fumes testing connection screw 10020625 475 Washer 10026323 482 Washer 10026366 487 Washer 10026345 509 Limit ther...

Page 37: ...themaximumpower the CO2 readingshouldbeasshowninthetableabove If the CO2 reading is correct press the MODE button to exit the maximum setting If the CO2 reading is incorrect the maximum gas pressure m...

Page 38: ...OW RATE lts min FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH THE MANUFACTURER S INSTRUCTIONS YES FOR ALL INSTALLATIONS CONFIRM THE FOLLO...

Page 39: ...CARD SERIAL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No...

Page 40: ...0 333 0520 Fax 01442 281403 After Sales Service Tel 0870 333 0220 Vok ra Ireland West Court Callan Co Kilkenny Tel 05677 55057 Fax 05677 55060 Vok ra Ltd reserve the right to change the specifications...

Reviews: