background image

16

The following information are shown pushing sub-
sequently the   button:

Info 1

N/A

Info 2

water pressure (fig. 18)

Info 3

CH temperature set (fig. 19)

Info 4

N/A.

5.9.3

INFORMATION MODE SERVICE

Push and hold for 10 seconds the Info button ( )
to enter the info menu service (

INF2 is shown on

the display

). The following information are shown

pushing subsequently the   button:

5.9.4

ADJUSTING APPLIANCE PARAMETERS

The appliance is delivered with pre-set param-
eters. Some parameters can be changed or ad-
justed if required. For further details, please refer
to section 7.

5.10

SETTING THE SYSTEM DESIGN PRESSURE

The design pressure should be a minimum of 0.5
BAR and a maximum of 1.5 BAR.
The actual reading should ideally be 1 BAR plus
the equivalent height in metres (0.1 BAR = 1
metre) to the highest point in the system above the
base of the appliance (up to the maximum of 1.5
BAR total).

N.B.

 The safety valve is set to lift at 3 BAR/30

metres/45 psig.

To lower the system pressure to the required
value, drain off some water from the appliance
drain valve until the required figure registers on the
pressure gauge (see fig. 1).

5.11

REGULATING THE CENTRAL HEATING SYS-
TEM

Fully open all radiator and circuit valves and run
the appliance for both heating and hot water until
heated water is circulating. If conditions are warm
remove any thermostatic head. Adjust radiator
return valves and any branch circuit return valves
until the individual return temperatures are correct
and are approximately equal.

5.12

FINAL CHECKS

ENSURE ALL TEST NIPPLES ON THE APPLI-
ANCE GAS VALVE ARE TIGHT AND CHECKED
FOR SOUNDNESS.

ENSURE THE APPLIANCE FLUE SYSTEM IS
FITTED CORRECTLY AND IS PROPERLY
SECURED.

ENSURE ALL PIPE WORK IS RE-CHECKED
FOR SOUNDNESS.

RE-FIT APPLIANCE CASING.

COMPLETE BENCHMARK CHECKLIST.

FOR UK ONLY

Complete details of the boiler, controls, installa-
tion and commissioning in the Benchmark check-
list at the back of this book. It is important that the
Benchmark checklist is correctly completed and
handed to the user. Failure to install and commis-
sion the appliance to the manufacturers instruc-
tions may invalidate the warranty.

5.13

INSTRUCTING THE USER

Hand over all documentation supplied with this
appliance - including these instructions - and
explain the importance of keeping them in a safe
place.
Explain to the user how to isolate the appliance
from the gas, water and electricity supplies, and
the locations of all drain points. Show the user how
to operate the appliance and any associated
controls correctly.
Show the user the location of the filling valve and
how to top-up the system pressure correctly and
show the location of all manual air release points.
Explain to the user how to turn off the appliance for
both long and short periods and advise on the
necessary precautions to prevent frost damage.
Explain to the user that for continued safe and
efficient operation, the appliance must be serv-
iced annually by a competent person.

IMPORTANT

To validate the appliance warranty, it’s necessary
to register the appliance details with us.
The warranty can be registered in several ways:

by completing the warranty registration card and
posting to us using the pre-paid envelope supplied

online at: vokera.co.uk

for UK residents by calling: 0870 607 0281

for ROI residents by calling: 1850 221121.

Step number

Information displayed

01

Temperature at flow sensor °C

02

Temperature at return sensor °C

03

Unused

04

Unused

05

Unused

06

Unused

07

Unused

FAN

Fan speed RPM/100

09

Unused

10

Unused

Fig. 18

Fig. 19

Summary of Contents for MYNUTE 35HE

Page 1: ...Installation Servicing Instructions THESEINSTRUCTIONS TO BE RETAINED BY USER 0694 0694BQ0479...

Page 2: ...on analysis 15 5 8 Final flushing of the heating system 15 5 9 Setting the boiler operating temperature 15 5 10 Setting the system design pressure 16 5 11 Regulating the central heating system 16 5 12...

Page 3: ...ansion ves sel safety valve pressure gauge and automatic by pass The35HEisproducedasaroomsealed categoryII2H3P appliance suitableforinternalwallmountingapplications only It is provided with a fan powe...

Page 4: ...try to ensure flame stability at the burner Once suc cessful ignition has been achieved the electronic circuitryincreasesthegasrateto75 foraperiod of 15 minutes Thereafter the boiler s output will eit...

Page 5: ...ions Height 845 mm Width 453 mm Depth 359 mm Dry weight Kg 43 0 2 5 Clearances Sides 12 mm Top 150 mm from casing or 25 mm above flue elbow whichever is applicable Bottom 150 mm Front 600 mm 2 6 Conne...

Page 6: ...tc 500 mm D Below gutter drain pipe etc 75 mm E Below eaves 200 mm F Below balcony car port roof etc 1200 mm G To the side of a soil drain pipe etc 150 mm H From internal external corner or boundary 3...

Page 7: ...entrally over the terminal Refer to BS 5440 Part 1 when the terminal is 0 5 metres or less below plastic guttering or 1 metre or less below painted eaves BS5440 PART 1 FLUES BS5440 PART 2 FLUES VENTIL...

Page 8: ...fuse The method of connection to the mains electricity supply must allow for com plete isolation from the supply The preferred method is by using a double pole switch with a contact separation of at...

Page 9: ...hosenfortheappliancemustpermit the provision of a safe and satisfactory flue and termination The location must also permit an adequateairsupplyforcombustionpurposesand anadequatespaceforservicingandai...

Page 10: ...he system has an unusually high water content it may be necessary to provide additional expansion capacity see 6 19 3A 6 6 FILLING POINT Amethodforinitialfillingofthesystemandreplacing water lost duri...

Page 11: ...te supplied carefully mark the position of the wall mounting bracket see fig 6 and flue hole if applicable 4 5 FITTING THE FLUE The top flue outlet permits both horizontal and verticalflueapplications...

Page 12: ...to ensurethatthecorrectsealismadewhenassem blingthefluesystem Connecttherequirednumber of flue extensions or bends up to the maximum equivalentfluelength totheflueterminal seefig 7 8 The flue system...

Page 13: ...the dedi cated concentric flue kit for termination It is essential that the installation of the twin flue system be carried out in strict accordance with these instructions GUIDANCE NOTES ONTWIN FLUE...

Page 14: ...in flue pipes must be pushed 50mm onto the male spigots of the concentric to twin converter NOTE Seal the flue terminal assembly to the wall using cement or a suitable alternative that will provide sa...

Page 15: ...nlet of the valve and tighten both nuts NOTE Itwillbenecessarytocalculatethediameterofthe gas supply pipe to ensure the appliance has an adequate supply of gas 4 6 2 FLOW RETURN fig 6 The appliance is...

Page 16: ...B cover C Fig 15 Optional devices 24V terminal block Mains 230V terminal block 4 7 2 APPLIANCETERMINALBLOCK Theapplianceterminalblockislocatedontherear of the control fascia Remove the casing as descr...

Page 17: ...ensure the proper electrical checks have been carried out see 7 8 particularly continuity polarity and resistance to earth ensure the 3 AMP fuse supplied with the appliance has been fitted ensure the...

Page 18: ...LY SECURED ENSURE ALL PIPE WORK IS RE CHECKED FORSOUNDNESS RE FIT APPLIANCE CASING COMPLETEBENCHMARKCHECKLIST FOR UK ONLY Complete details of the boiler controls installa tionandcommissioningintheBenc...

Page 19: ...ugh it is anticipated that this appliance will give years of reliable trouble free service the life spanofcomponentswillbedeterminedbyfactors such as operating conditions and usage Should the applianc...

Page 20: ...rolfasciaupwardandrotate it Locateandremovethescrews A whichsecure the PCBcover pushtheclips B andremovecover after carefullytakingnoteofallwiringconnections discon nect all wiring from the PCB locate...

Page 21: ...re it is replaced correctly Replace in the reverse order 6 16 MAIN HEAT EXCHANGER fig 29 30 Carry out component removal procedure as de scribed in 6 4 Unclip and remove the three air chambercovers fro...

Page 22: ...tandleft side covers Disconnect the fan transformer wiring Locateandremovethe2screws D thatsecurethefan transformer to the air box plate cut the two cable ties previewedonheat shrinkableinsulatorsthat...

Page 23: ...of the primary thermistor reaches 30 C There after the pump fan will over run for 30 sec onds Pump anti block cycle when there has been noheatingorHWrequestfor24 hours theanti block cycle is activate...

Page 24: ...ee fig 36 Push MODE button and selecttheadjustparameterspasswordbyturning the RH right hand encoder and confirm it by pushingMODEbutton Thefollowingfunctionsare available in this mode 7 4 1 GAS TYPE S...

Page 25: ...liance however you must check that the CO2 values are set correctly see 7 4 Insert the flue gas analyser probe into the flue gas test point see fig 35 Operate the boiler in HH LL and compare the value...

Page 26: ...ition 13 check the wiring harness 23 check the wiring harness 25 high limit flow temperature probe 27 high limit return temperature probe 31 internal fault 35 fan error 36 internal fault 41 low water...

Page 27: ...odes 6x appear if a problem exists with the secondary DHW thermistor Check thermistor Check wiring continuity FAULT CODES 5x Fault codes 5x appear if a problem with the main board exists Check paramet...

Page 28: ...3600 1 25 Differential heating positive C 2 10 1 6 26 Differential heating negative C 2 10 1 6 28 CH timer force burner 75 after CH start Min 0 20 1 15 29 CH timer blocking time CH Min 0 20 1 5 30 CH...

Page 29: ...win channel programmers figs 40 41 The appliance can be used in conjunction with typi cal S Plan Y Plansystems see8 4 1 8 4 2 please contact Vokera technical should you requirefurtherdetailedinstructi...

Page 30: ...28 8 4 1 Y PLANWITH EXTERNALTWIN CHANNEL PROGRAMMER fig 40 8 4 2 S PLANWITH EXTERNALTWIN CHANNEL PROGRAMMER fig 41 Fig 40 Fig 41...

Page 31: ...S Outside sensor WPS Water pressure sensor FS Flow termoster RS Return termoster AE01A P1 Master board AE01A P2 Ausiliary board controll M0T2B Motor control board AC0X Display board K9 Pump relay K13...

Page 32: ...cover assembly 10025842 26 Instrumental panel 10027949 31 Case 10026241 38 Driver PCB 10027200 90 Fuse 3478 226 Edge clip 5128 300 Wiring harness 10026341 301 Wiring harness 10027953 302 Wiring harnes...

Page 33: ...ctions cover 10027685 63 Pipe 10026228 105 Pressure transductor 10027132 201 Washer 5026 265 Washer 5236 266 Washer 5237 288 Washer 6898 290 Clip 2165 351 Nut 1823 353 Nut 1824 432 Clip 10024958 435 C...

Page 34: ...6338 6 Pipe 10026264 7 Pipe 10027317 9 Pipe 10027318 10 Pipe 10027146 17 Air vent bottle 10026275 25 Siphon 10027190 26 Flexible pipe 10027191 27 Flexible pipe 10027192 48 Pipe 10027321 66 Flexible pi...

Page 35: ...veyor 10026309 39 Gas pipe 10027196 46 Gas diaphragm 10027162 46 Gas diaphragm 2111 67 Washer 10026322 69 Tryton 10027089 72 Mixer 10024295 200 Washer 5023 479 Transformer 10026237 480 Transformer 100...

Page 36: ...r assembly 01005369 7 Conveyor assembly 10026310 12 Flue drain connection 10026311 27 Fumes testing connection screw 10020625 475 Washer 10026323 482 Washer 10026366 487 Washer 10026345 509 Limit ther...

Page 37: ...themaximumpower the CO2 readingshouldbeasshowninthetableabove If the CO2 reading is correct press the MODE button to exit the maximum setting If the CO2 reading is incorrect the maximum gas pressure m...

Page 38: ...OW RATE lts min FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH THE MANUFACTURER S INSTRUCTIONS YES FOR ALL INSTALLATIONS CONFIRM THE FOLLO...

Page 39: ...CARD SERIAL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No...

Page 40: ...0 333 0520 Fax 01442 281403 After Sales Service Tel 0870 333 0220 Vok ra Ireland West Court Callan Co Kilkenny Tel 05677 55057 Fax 05677 55060 Vok ra Ltd reserve the right to change the specifications...

Reviews: