background image

 

COMMISSIONING: CO AND COMBUSTION RATIO CHECK

 

 

 

 

 

 

 

 

 

 

SET BOILER TO MAXIMUM RATE 

In accordance with, section 7.3, set boiler to operate at maximum rate (full load condition). Allow sufficient time for combustion to 
stabilise. , insert analyser probe into air inlet sampling point. 

      

 

    

 

 

 

               

 

  

 

Is O2 

20.6% 

and CO2 < 0.2%? 

Verify flue integrity 

Analyser readings indicate 

that combustion products 

and inlet air are mixing. 

Further investigation of the 

flue is therefore required. 

Check that flue components 

are correctly assembled, 

fixed and supported as per 

boiler/flue instructions. 

Check that flue and flue 
terminal are not obstructed. 

Is O2 ≥20.6%

 

and CO2 < 0.2%? 

 

CHECK CO AND 

COMBUSTION RATIO 

AT MAXIMUM RATE

With boiler still set at 
maximum rate, insert 

analyser probe into flue 
gas sampling point. 

Allow readings to 
stabilise before 

di

 

 

Is CO less than 

350ppm AND 

CO/CO

ratio less 

than 0.004? 

YES 

N

YES 

NO 

Check all seals 

around the appliance 
burner, internal flue 
seals, door and case 

seals. Rectify where 
necessary. 

Is CO less 

than 350ppm 

AND 

CO/CO

ratio 

less than 
0.004? 

CHECK CO AND COMBUSTION 

RATIO AT MINIMUM RATE 

With boiler set at minimum rate, 

insert analyser probe into flue 

gas sampling point. Allow 

readings  to stabilise before 

recording. 

 

NO 

Turn off appliance and 

call Vokera’s technical 

helpline for advice. 

The appliance must not 

be commissioned until 

problems are identified 

and resolved. 

Turn off appliance and call 

Vokera’s technical helpline 

for advice. 

The appliance must not be 

commissioned until 

problems are identified and 

resolved. If commissioning 

cannot be fully completed, 

the appliance must be 

disconnected from the gas 

supply in accordance with 

the GSIUR. 

NOTE: Check and record CO and 
combustion ratio at both 
maximum AND minimum rate 
before contacting the Vokera 

   

SET BOILER TO 

MINIMUM RATE

In accordance with 

section 7.3, set 
boiler to operate at 
minimum rate (to 

minimum load 
condition).  Allow 

sufficient time for 
combustion to 
stabilise. 
 

YES 

Is CO < 350ppm 

and CO/CO

ratio 

less

 

than 0.004 ?

 

NO 

Boiler is operating satisfactorily

No further actions required.

Ensure test points are capped, boiler case is correctly replaced and all other commissioning procedures are completed. 
Complete Benchmark Checklist, recording CO and combustion ratio readings as required. 

NOTE 

The air/gas ratio valve is factory-set and must not be 
adjusted during commissioning unless this action is 
recommended, following contact with the Vokera 
technical help line. If any such adjustment is 
recommended and further checking of the boiler is 
required, the engineer must be competent to carry out 
this work and to use the flue gas analyser accordingly. 
If the boiler requires conversion to operate with a 
different gas family (e.g., conversion from natural gas 
to LPG) separate guidance will be provided by the 
Vokera technical help line and must be followed. 

NO 

BEFORE CO AND COMBUSTION RATIO CHECK

The installation instructions should have been followed, gas 

type verified and gas supply pressure/rate checked as required 

prior to commissioning. 
As part of the installation process, 

ESPECIALLY WHERE A 

FLUE HAS BEEN FITTED BY PERSONS OTHER THAN THE 
BOILER INSTALLER
, visually check the integrity of the whole 

flue system to confirm that all components are correctly 
assembled, fixed and supported. Check that the maximum flue 

lengths have not been exceeded and all guidance has been 
followed (e.g. Technical Bulletin 008).

 

The flue gas analyser should be of the correct type, as specified 
by BS 7967. 

Before use, the flue gas analyser should have been maintained 
and calibrated as specified by the manufacturer. The installer 

must have the relevant competence for use of the analyser. 
Check and zero the analyser 

IN FRESH AIR, as per analyser 

manufacturer’s instructions. 

YES 

YES 

Summary of Contents for Easi-Heat Plus 25C

Page 1: ...D BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK Easi Heat Plus C High effici...

Page 2: ...WATER CIRCULATION 12 3A 7 ELECTRICAL SUPPLY 12 3A 8 MOUNTING ON A COMBUSTIBLE SURFACE 12 3A 9 TIMBER FRAMED BUILDINGS 12 3A 10 INHIBITORS 12 3A 11 SHOWERS 12 3A 12 DECLARATION OF CONFORMITY 12 SECTIO...

Page 3: ...has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please therefore take some time to rea...

Page 4: ...ounter clockwise to reduce the temperature range 40 C 80 C for standard central heating The automatic temperature control function SARA is factory disabled To enable this function please contact the V...

Page 5: ...ntly hot enough it may be necessary to reduce the flow of water at the hot water outlet tap NOTE If the appliance fails to ignite during the ignition sequence it will enter a lockout condition Should...

Page 6: ...position To select OFF mode move the selector switch in the upper position APPLIANCE STATUS LED AND FAULT CODES Fig 3 4 WHAT IF 5 SETTING THE VOK RA Advice for homeowners Please contact Vok ra Custome...

Page 7: ...tained from Vok ra customer services When the product reaches the end of its life it should not be disposed of as solid urban waste but should be brought to a separated waste collection facility Easi...

Page 8: ...n and the boiler will perform a three minute anti cycle timer delay When the request for heat has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat withi...

Page 9: ...ght mm 792 Width mm 405 Depth mm 253 Dry weight kg 27 30 2 6 Clearances Easi Heat Plus 25C Easi Heat Plus 29C Sides 12mm Top 150mm from casing or 25mm above flue elbow whichever is applicable Bottom 1...

Page 10: ...rature boilers 37 C and for other heaters 50 C return temperature at heater inlet Seasonal space heating energy efficiency class A Water heating energy efficiency class A Parameter Symbol Value Unit P...

Page 11: ...lcony level 300 mm J From a surface or boundary facing the terminal 600 mm K From a terminal facing a terminal 1200 mm L From an opening in the car port into the building 1200 mm M Vertically from a t...

Page 12: ...c directly from the mains supply must be provided see fig 8 This method of filling complies with the current Water Supply Water Fittings Regulations 1999 and Water Bylaws 2000 Scotland If an alternati...

Page 13: ...s to be fitted on a wall of combustible material There is no requirement to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefittedi...

Page 14: ...LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a position at least 1 metre above the highest point in the system...

Page 15: ...talsobemadetothemaximumlength see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum flue length for each bend 45 bend 1 0 metre 60 100 1 0 metre 80 12...

Page 16: ...flue length see table below Reduction for bends Bend Reduction in maximum flue length for each bend 45 bend 1 0 metre 60 100 1 0 metre 80 125 90 bend 1 0 metre 60 100 1 0 metre 80 125 Vertical flue te...

Page 17: ...no less than 20mm diameter to the outlet pipe and ensure it discharges in accord ance with building regulations or other rules in force 4 7 ELECTRICAL CONNECTIONS The boiler is supplied with a 2 metre...

Page 18: ...to remove any installation debris from the boiler prior to lighting Refill the boiler and heating system as described in 5 3 5 5 PRE OPERATION CHECKS Before attempting the initial lighting of the appl...

Page 19: ...this appliance including these instructions and explain the importance of keeping them in a safe place Explain to the user how to isolate the appliance from the gas water and electricity supplies and...

Page 20: ...nd remove the pump outlet pipe A from the pump assembly combustion chamber connection Remove the expansion pipe locking pin B from the top of the pump assembly and withdraw the flexible pipe Locate an...

Page 21: ...the reverse order Check and adjust burner pressure settings WARNING A GAS TIGHTNESS CHECK MUST BE CAR RIED OUT 6 13 ELECTRODES fig 27 Carry out component removal procedure as described in 6 4 Remove t...

Page 22: ...e carefully withdraw the by pass cartridge S1 and or DHW non return cartridge T1 Ensure all seals are in good condition taking care to ensure they are replaced correctly Replace in the reverse order e...

Page 23: ...anger DisconnectthewiringtotheDHWflowswitch Slacken and unscrew the inlet connection Unscrew the nut E2 Lift the DHW flow switch housing from its seating If necessary remove the locking pin F2 from th...

Page 24: ...e gas rate to 75 for a period of 15 minutes The speed of the fan and therefore the output of the boiler is determined by the temperature of the water sensed by the flow temperature sensor consequently...

Page 25: ...tion analysis check can easily be carried out on the appliance via the test points located on the top of the applian ce see 7 3 Operate the boiler in combustion analysis mode see 7 3 1 Insert the flue...

Page 26: ...o proceed to next stage If not see 7 7 4 connect test leads between the Neutral Earth connec tions at the appliance terminal strip The meter should read approximately 0 15Vac If so polarity is correct...

Page 27: ...particular control Further guidance on the recom mended practice for the installation of external controls can be found in CHeSS HC5 HC6 www energyefficiency gov uk 8 4 VOK RA LOWER COVER MECHANICAL...

Page 28: ...ic hot water temperature WPS Water pressure switch S E Spark electrode TSC2 Ignition transformer 3W 3 way motor F O H T Flow over heat thermostat FS Flue sensor FT Flow thermistor NTC RS Return thermi...

Page 29: ...37 0 mbar 37 0 mbar Heating maximum gas rate kg hr 1 55 1 94 DHW maximum gas rate kg hr 1 94 2 25 Minimum gas rate kg hr 0 39 0 47 Injector size 3 8 mm 3 9 Silencer flange 27 mm 29 mm CO2 maximum outp...

Page 30: ...TO MINIMUM RATE In accordance with section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES Is CO 350ppm and CO CO2 ratio less...

Page 31: ...ommissioning checklist completed in full To instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation To maintain the boiler guarantee...

Page 32: ...terlock Provided ALL SYSTEMS The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer s instructions Yes What system cleaner was used What inhibitor was used Quantity...

Page 33: ...gister No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Gas safe register No Record At max rate C...

Page 34: ......

Page 35: ......

Page 36: ...1HG enquiries vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited...

Reviews: