background image

23

fig. 37

7.3.1 CO

2

 FUNCTION SETTINGS

Locate the CO

 

button (see 7.3)

Select the main selector switch in position 

.

CO

2

 FUNCTIONS

ACTION ON THE BUTTON

LED STATUS

combustion analysis mode

press once = burner running at maximum heating

yellow led blinking

gas valve maximun setting 

press twice = burner running at maximum DHW

yellow led bl red led fixed

gas valve minimum setting

press three time = burner running at minimum

yellow led bl green led fixed

NOTE

1 - Any additional pressing of CO

 

button after the third time the burner switched between maximum DHW and minimum.

2 - To restart the CO

 

function it is necessary to pass throught the 

 position with the main selector switch.

Minimum 

screw

Inlet gas pressure

connection

Compensation pipe 

connection

Maximum 

screw

7.3.2  GAS VALVE MAXIMUM SETTING

Set the CO

2

 button at maximum (see 7.3.1), once the maximum 

is obtained check that it corresponds with the appropriate CO

2

 

value (Maximum) for the respective appliance (see 2.11). If 

the CO

2

 reading is correct, proceed to gas valve minimum 

setting (7.3.3).

However, if the CO

2

 reading is incorrect, the maximum gas 

pressure must be adjusted as follows:

•  using a 2.5mm Allen key, very slowly turn the maximum ad-

justment screw (see fig. 37) – clockwise to decrease, counter 

clockwise to increase – until the correct value is displayed on 

the CO

2

 analyser (allow time for the analyser to stabilise).

7.3.3  GAS VALVE MINIMUM SETTING

Set the CO

2

 button at minimum (see 7.3.1), once the minimum 

is obtained check that it corresponds with the appropriate CO

2

 

value (Minimum) for the respective appliance (see 2.11). If the 

CO

2

 reading is correct, proceed to completion (7.3.4).

However, if the CO

2

 reading is incorrect, the minimum gas 

pressure must be adjusted as follows:

•  locate the minimum adjustment screw (fig. 37), using a suit-

able screwdriver remove the protection plug 

•  using a 4mm Allen key, very slowly turn the minimum adjust-

ment  screw  (see  fig.  37)  -  clockwise  to  increase,  counter 

clockwise to decrease - until the correct value is displayed 

on the CO

2

 analyser (allow time for the analyser to stabilise).

7.3.4 COMPLETION

On completion of the combustion analysis check and/or any 

gas valve adjustment, refit the plug (fig. 36 - 

L2) 

and move the 

mode selector throught 

 position. Remove the test probe 

from the test point and refit the sealing screw/s and/or cap. 

IMPORTANT

A GAS TIGHTNESS CHECK MUST BE CARRIED OUT IF ANY 

GAS CARRYING COMPONENTS HAVE BEEN REMOVED, 

REPLACED OR DISTURBED.

7.4  COMBUSTION ANALYSIS TEST

A combustion analysis check can easily be carried out on the 

appliance via the test points located on the top of the applian-

ce (see 7.3).

•  Operate the boiler in combustion analysis mode (see 7.3.1)

•  Insert the flue gas analyser probe into the flue gas test point 

(see fig. 33) and compare the values with those shown in 

section 2 (Nat. Gas) or section 9 (LPG). If different adjust 

the gas valve according to 7.3.1, 7.3.2, & 7.3.3.

The appliance will operate in CO

2

 mode for approximately 

15minutes.

Note

: If a measured CO/CO

2

 ratio of 0.004/1 or less AND a 

CO reading of less than 350ppm cannot be achieved, please 

contact Vokera technical for advice.

Note: 

When checking the air inlet test point, insert the probe 

no more than 25mm into the test point.

7.5  CHECKING THE EXPANSION VESSEL

Carry out the component removal procedure as described in 

6.4. You must ensure that the boiler is completely drained of 

water. Using a suitable pressure gauge, remove dust cap on 

expansion vessel and check the charge pressure. The correct 

charge pressure should be 1.0 bar ± 0.1 bar. If the charge 

pressure is less, use a suitable pump to increase the charge.

NOTE

You must ensure the drain valve is in the open position whilst 

re-charging takes place. Replace the dust cap and carry out 

the relevant commissioning procedure (section 5).

7.6  EXTERNAL FAULTS

Before carrying out any faultfinding or component replacement, 

ensure the fault is not attributable to any aspect of the installation.

7.6.1  INSTALLATION FAULTS

Symptom

Possible cause

No ignition

Check wiring/check electrical 

supply

No hot water

Check pipe-work

No heating

Check external controls

 

Fault

Possible cause

Red led fixed

Check gas supply, check flue 

system, check polarity

7.7  ELECTRICAL CHECKS

Any electrical checks must be carried out by a suitably quali-

fied person.

7.7.1  EARTH CONTINUITY TEST

Isolate the appliance from the electrical supply, and using a 

suitable multi-meter carry out a resistance test. Connect test 

leads between an appliance earth point and the earth wire of 

the appliance supply cable. The resistance should be less than 

1 OHM. If the resistance is greater than 1 OHM check all earth 

wires and connectors for continuity and integrity.

7.7.2  SHORT CIRCUIT CHECK

Isolate the appliance from the electrical supply, and using a 

suitable multi-meter, carry out a short circuit test between the 

Live & Neutral connections at the appliance terminal strip. 

Repeat above test on the Live & Earth connections at the ap-

pliance terminal strip.

NOTE

Should it be found that the fuse has failed but no fault is indi-

cated, a detailed continuity check will be required to trace the 

fault. A visual inspection of components may also assist in 

locating the fault.

Summary of Contents for Easi-Heat Plus 25C

Page 1: ...D BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK Easi Heat Plus C High effici...

Page 2: ...WATER CIRCULATION 12 3A 7 ELECTRICAL SUPPLY 12 3A 8 MOUNTING ON A COMBUSTIBLE SURFACE 12 3A 9 TIMBER FRAMED BUILDINGS 12 3A 10 INHIBITORS 12 3A 11 SHOWERS 12 3A 12 DECLARATION OF CONFORMITY 12 SECTIO...

Page 3: ...has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please therefore take some time to rea...

Page 4: ...ounter clockwise to reduce the temperature range 40 C 80 C for standard central heating The automatic temperature control function SARA is factory disabled To enable this function please contact the V...

Page 5: ...ntly hot enough it may be necessary to reduce the flow of water at the hot water outlet tap NOTE If the appliance fails to ignite during the ignition sequence it will enter a lockout condition Should...

Page 6: ...position To select OFF mode move the selector switch in the upper position APPLIANCE STATUS LED AND FAULT CODES Fig 3 4 WHAT IF 5 SETTING THE VOK RA Advice for homeowners Please contact Vok ra Custome...

Page 7: ...tained from Vok ra customer services When the product reaches the end of its life it should not be disposed of as solid urban waste but should be brought to a separated waste collection facility Easi...

Page 8: ...n and the boiler will perform a three minute anti cycle timer delay When the request for heat has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat withi...

Page 9: ...ght mm 792 Width mm 405 Depth mm 253 Dry weight kg 27 30 2 6 Clearances Easi Heat Plus 25C Easi Heat Plus 29C Sides 12mm Top 150mm from casing or 25mm above flue elbow whichever is applicable Bottom 1...

Page 10: ...rature boilers 37 C and for other heaters 50 C return temperature at heater inlet Seasonal space heating energy efficiency class A Water heating energy efficiency class A Parameter Symbol Value Unit P...

Page 11: ...lcony level 300 mm J From a surface or boundary facing the terminal 600 mm K From a terminal facing a terminal 1200 mm L From an opening in the car port into the building 1200 mm M Vertically from a t...

Page 12: ...c directly from the mains supply must be provided see fig 8 This method of filling complies with the current Water Supply Water Fittings Regulations 1999 and Water Bylaws 2000 Scotland If an alternati...

Page 13: ...s to be fitted on a wall of combustible material There is no requirement to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefittedi...

Page 14: ...LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a position at least 1 metre above the highest point in the system...

Page 15: ...talsobemadetothemaximumlength see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum flue length for each bend 45 bend 1 0 metre 60 100 1 0 metre 80 12...

Page 16: ...flue length see table below Reduction for bends Bend Reduction in maximum flue length for each bend 45 bend 1 0 metre 60 100 1 0 metre 80 125 90 bend 1 0 metre 60 100 1 0 metre 80 125 Vertical flue te...

Page 17: ...no less than 20mm diameter to the outlet pipe and ensure it discharges in accord ance with building regulations or other rules in force 4 7 ELECTRICAL CONNECTIONS The boiler is supplied with a 2 metre...

Page 18: ...to remove any installation debris from the boiler prior to lighting Refill the boiler and heating system as described in 5 3 5 5 PRE OPERATION CHECKS Before attempting the initial lighting of the appl...

Page 19: ...this appliance including these instructions and explain the importance of keeping them in a safe place Explain to the user how to isolate the appliance from the gas water and electricity supplies and...

Page 20: ...nd remove the pump outlet pipe A from the pump assembly combustion chamber connection Remove the expansion pipe locking pin B from the top of the pump assembly and withdraw the flexible pipe Locate an...

Page 21: ...the reverse order Check and adjust burner pressure settings WARNING A GAS TIGHTNESS CHECK MUST BE CAR RIED OUT 6 13 ELECTRODES fig 27 Carry out component removal procedure as described in 6 4 Remove t...

Page 22: ...e carefully withdraw the by pass cartridge S1 and or DHW non return cartridge T1 Ensure all seals are in good condition taking care to ensure they are replaced correctly Replace in the reverse order e...

Page 23: ...anger DisconnectthewiringtotheDHWflowswitch Slacken and unscrew the inlet connection Unscrew the nut E2 Lift the DHW flow switch housing from its seating If necessary remove the locking pin F2 from th...

Page 24: ...e gas rate to 75 for a period of 15 minutes The speed of the fan and therefore the output of the boiler is determined by the temperature of the water sensed by the flow temperature sensor consequently...

Page 25: ...tion analysis check can easily be carried out on the appliance via the test points located on the top of the applian ce see 7 3 Operate the boiler in combustion analysis mode see 7 3 1 Insert the flue...

Page 26: ...o proceed to next stage If not see 7 7 4 connect test leads between the Neutral Earth connec tions at the appliance terminal strip The meter should read approximately 0 15Vac If so polarity is correct...

Page 27: ...particular control Further guidance on the recom mended practice for the installation of external controls can be found in CHeSS HC5 HC6 www energyefficiency gov uk 8 4 VOK RA LOWER COVER MECHANICAL...

Page 28: ...ic hot water temperature WPS Water pressure switch S E Spark electrode TSC2 Ignition transformer 3W 3 way motor F O H T Flow over heat thermostat FS Flue sensor FT Flow thermistor NTC RS Return thermi...

Page 29: ...37 0 mbar 37 0 mbar Heating maximum gas rate kg hr 1 55 1 94 DHW maximum gas rate kg hr 1 94 2 25 Minimum gas rate kg hr 0 39 0 47 Injector size 3 8 mm 3 9 Silencer flange 27 mm 29 mm CO2 maximum outp...

Page 30: ...TO MINIMUM RATE In accordance with section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES Is CO 350ppm and CO CO2 ratio less...

Page 31: ...ommissioning checklist completed in full To instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation To maintain the boiler guarantee...

Page 32: ...terlock Provided ALL SYSTEMS The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer s instructions Yes What system cleaner was used What inhibitor was used Quantity...

Page 33: ...gister No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Gas safe register No Record At max rate C...

Page 34: ......

Page 35: ......

Page 36: ...1HG enquiries vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited...

Reviews: