Installation and Operating Manual
I/H Converter DSG-B03212
DSG-B07212
2019 / 02
J.M. Voith SE & Co.
KG │ Division Digital Ventures
Page: 16 / 22
918 3626018861 en
D – 74564 Crailsheim
Version: 4.1
6.2.1
Potentiometer effect
Set X1 at setpoint w = 20 mA before setting X0.
Fig. 3: Adjusting range PA of I/H converter
I/H converter type
DSG-B03212
DSG-B07212
Pressure adjusting range
P
A
[
bar
]
0..3
1..7
Adjusting range approx.
P
A
max
[
bar
]
at setpoint w = 20 mA
1..
3
5..7
Adjusting range approx.
P
A
min
[
bar
]
at setpoint w = 4 mA
0..0.8
0..2
1..3
1.5..5
The bold data for PAmin refer to the maximum set pressure PAmax.
6.2.2
Factory setting
The adjusting range of PA is assigned to the setpoint range 0/4...20mA according to the
order data.
X
0
Potentiometer X
0
is used to adjust the minimum output pressure PAmin at a
setpoint w of 0 mA or 4 mA. The output pressure increases by turning the
potentiometer clockwise.
X
1
Potentiometer X
1
is used to adjust the maximum output pressure PAmax at a
setpoint w of 20 mA. The output pressure increases by turning the potentiometer
clockwise.