Way Valve WSR-D16214
2005 / 03 aie
Voith Turbo GmbH & Co. KG
Page: 16 / 24
9183626018945 en
D – 74564 Crailsheim
Version: 2.0
Potentiometer: Parameter
description:
FM
Setting of hydraulic center of control piston
X0
Setting of position s at setpoint w = 4 mA
X1
Setting of position s at setpoint w = 20 mA
KP
Setting of proportional gain of positioner
SF
Setting of switching frequency of magnetic
force
controller
X0 must be adjusted before adjusting X1.
For position of potentiometer, see Chapter 10.
6.2.1
Setting the hydraulic center of control piston
To avoid a deviation between the setpoint and the actual position remote indication, a
magnetic force offset is set with potentiometer FM. This offset is selected so that the
control deviation is zero at setpoint w = 12 mA and the control piston is in the hydraulic
center.
For setpoints of w
≠
12 mA, minor deviations to the actual value remote indication may
occur.
•
Run the way valve until it has reached operating temperature and check the feed
pressure.
•
Predefine setpoint w = 12.00 mA with a power source.
•
Measure the actual value remote indication and set to 12 +/- 0.05 mA
with potentiometer FM.
Effective direction of FM:
The magnetic force or actual position remote indication increases by turning the
potentiometer clockwise.
Stroke setting
Fig. 3
Stroke setting
0
4
20
100
X1
Mech. stop
in the cylinder
Mech. stop
in the cylinder
Stroke setting
Setpoint
[
mA
]
Stroke
[
%
]
X0