Title: Instruction manual PROFINET interface
Date: Sept. 2020
Ver: 04AD_Red-y_V2.1
By: WES/HAE
Page 21
/
30
Description: LUT Select
Data type: UINT16
Specifies, which gas data set is to be used. Up to 10 different calibration data sets can be saved in the
instrument. They have to be created by the manufacturer.
Description: Gas Temperature
Data type: FLOAT32
Measured value temperature [°C].
Note:
Due to self-heating this temperature may be slightly higher range than the effective gas temperature at
the device inlet.
Description: Valve Power
Data type: FLOAT32
Contains the actual control value for the valve whether the control value is generated from the controller
(automatic mode) or manually set via ModBus. If the register control mode (Output PDO: Device Setup) is
defined as mode 10, the control value is immediately loaded into the register. In any other modes the
value is stored in a buffer and becomes active when control mode 10 has been activated. It is possible to
adjust directly the position of the control valve [0...100%].
Description: Serial Number
Data type: UINT32
Clear and unique serial number of the electronic part of the measuring instrument (PCB).
Description: Flow Limit
Data type: FLOAT32
Maximum allowed flow
Description: Flow Unit
Data type: STRING
Name of the selected flow unit
Description: Gas Name
Data type: STRING
Name of the selected gas
Description: Pressure Units
Data type: STRING
Pressure units
Description: Pressure
Data type: FLOAT32
Actual pressure (in Device Setup )