Initiated by the following:
1. Open the SVI switch.
2. Set the “Clean” button to the “On” position.
3. Set the “Ice” button to the “On” position.
4. Push both the “Harvest” and “Start” buttons simultaneously.
At this point, the machine “fault” can be identified and necessary corrections or adjustments can be
made for returning the machine to good working order. A “fault” will be identified by illumination of
specific numbered PLC output indicator lights on the PLC. See “Fault Identity”, TABLE 6-2.
To exit the troubleshoot mode, follow this sequence:
1. Set the “Clean” button to the “Off” position.
2. Set the “Ice” button to the “Off” position.
3. Close the SVI switch.
4. This will return the machine to the “Start-Up” mode.
Output Light
Fault #
Fault Description
ll¬l¬l
#10
High or low pressure cutout during freeze cycle
ll¬l¬¬
#11
High or low pressure cutout during harvest cycle
ll¬¬ll
#12
High or low pressure cutout during partial pumpdown
ll¬¬l¬
#13
High or low pressure cutout during total pumpdown
ll¬¬¬l
#14
Short Cycle Fault:
Three Harvests Within A Specified Time As Noted:
HEC-10 --- 10 Minutes
HEC-20 --- 10 Minutes
HEC-30 --- 5 Minutes
HEC-40 --- 5 Minutes
ll¬¬¬¬
#15
Long Freeze Cycle Fault:
One Freeze Cycle Longer Than A Specified Time As Noted:
HEC-10 --- 120 Minutes
HEC-20 --- 120 Minutes
HEC-30 --- 80 Minutes
HEC-40 --- 60 Minutes
l¬llll
#16
Power failure/compressor O/L
Note:
¬
indicates light is “On”
TABLE 6-2
Fault Identity
Summary of Contents for HEC-10
Page 1: ...HEC SERVICE MANUAL ...
Page 95: ...HEC Series Service Manual SERVICE OPERATIONS 10 21 01 9 13 FIGURE 9 9 Cutter Water Tank Parts ...
Page 96: ...HEC Series Service Manual SERVICE OPERATIONS 10 21 01 9 14 FIGURE 9 10 Cutter Drive Parts ...
Page 97: ...HEC Series Service Manual SERVICE OPERATIONS 10 21 01 9 15 FIGURE 9 11 Cutter Parts ...
Page 106: ...HEC Series Service Manual MODEL NUMBER STRUCTURE 10 21 01 10 1 10 Model Number Structure ...