Installation & Start-up – HES Series
15
Ice Machine Model
HE20
HE30
HE40
Recommended Condenser
DVT005
(DVT008)
DVT008
(DVT012)
DVT012
(DVT016)
Note:
For continuous operation at ambient above 105 °F, use larger condenser shown in parenthesis
Total Heat Rejection:
BTU/hr at 60 Hz.
(15°F TD)
BTU/hr at 50 Hz.
35,700
32,800
58,800
54,100
117,500
108,100
Fans:
Number
HP, Each
Total, CFM
1
1/3
(1/2)
5,050
(6,450)
1 (2)
1/2
6,450
(12,400)
2
1/2
12,400
(12,900)
Full Load Amps:
1 ph., 208/230V, 60 Hz
3 ph., 208/230V, 60 Hz
3 ph., 460V, 60 Hz
1 ph., 200/220V, 50 Hz
3 ph., 200/220V, 50 Hz
3 ph., 400V, 50 Hz
3.4
(3.9)
N/A
1.3
(1.3)
3.4
(3.9)
N/A
1.3
(1.3)
3.9
(7.8)
N/A
1.3
(2.6)
3.9
(7.8)
N/A
1.3
(2.6)
7.8
(7.8)
N/A
2.6
(2.6)
7.8
(7.8)
N/A
2.6
(2.6)
Weight, lbs.:
Net
Shipping
Operating
(maximum flooded)
180
(260)
320
(390)
195
(285)
260
(470)
390
(520)
285
(500)
470
(530)
520
(680)
500
(560)
Condenser dimensions, inches:
A (Width)
B (Length)
C (Height)
D (Leg centerline)
E (Leg centerline)
F (Clearance below)
43”
39.75”
(49.75”)
30”
(40”)
17”-3
30”
(40”)
24.5”
43”
49.75”
(69.75”)
40”
(60”)
17” - 3
40”
(60”)
24.5”
43”
69.75”
60”
17” - 3
60”
24.5”
Recommended Line Sizes, OD:
Liquid
(All lengths and orientations)
Discharge Gas
Vertical Up, All lengths
Horizontal Or Down, < 75 ft.
Horizontal Or Down, > 75 ft.
1/2”
5/8”
5/8”
7/8”
5/8”
7/8”
7/8”
1-1/8”
7/8”
1-1/8”
1-1/8”
1-3/8”
Connections at Condenser:
Liquid (ODC)
Discharge Gas (ODC)
Connections at Machine
Liquid & Discharge Gas (ODC)
5/8”
(7/8”)
7/8”
(1 1/8”)
1-1/8”
7/8”
1 1/8”
1-1/8”
7/8”
1-1/8”
(1-3/8”)
1-1/8”
TABLE - 4
Bohn Air-Cooled Condenser Data
Summary of Contents for HE S Series
Page 2: ...Installation Start up HES Series 2 Blank Page ...
Page 12: ...Installation Start up HES Series 12 FIGURE 8 Typical Space Diagram ...
Page 26: ...Installation Start up HES Series 26 FIGURE 16 Piping Schematic Air Cooled ...
Page 27: ...Installation Start up HES Series 27 FIGURE 17 Piping Schematic Water Cooled ...