![Vivax ACP-24CH70AEB Service Manual Download Page 26](http://html.mh-extra.com/html/vivax/acp-24ch70aeb/acp-24ch70aeb_service-manual_1038075026.webp)
Service manual
21
8.9 Gas
charging
Procedure:
1. Connect the charge hose to the charging cylinder.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the
cylinder.
2. Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air
(be careful of the liquid refrigerant).
3. Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
If the system cannot be charge with the specified amount of refrigerant, if can be charged with a little at a
time (approximately 150g each time0 while operating the air conditioner in the cooling cycle; however, one
time is not sufficient, wait approximately 1 minute and then repeat the procedure.(pumping down-pin).
4. Immediately disconnect the charge hose from the 3-way valve’s service port.
Stopping partway will allow the refrigerant to be discharged.
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air
conditioner before disconnecting the hose.
5. Mounted the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
Summary of Contents for ACP-24CH70AEB
Page 1: ...ACP 24CH70AEB RoHS Service manual ENG ...
Page 2: ......
Page 5: ......
Page 14: ...Service manual 9 5 Refrigerant cycle diagram Cooling only Heat pump mode ...
Page 18: ...Service manual 13 7 2 Wiring diagram MSE 21CRN2 MSE 24CRN2 MSE 28CRN2 ...
Page 19: ...Service manual 14 MSE 21HRN2 ACP 24CH70AEB MSE 28HRN2 ...
Page 48: ......
Page 49: ......
Page 50: ......