Troubleshooting
MCAC-UTSM-2008-04
40
Outdoor Units
ACP-12CT32AEI/I (-Q)
1. Running lamp flash at 5Hz
2. Defrosting lamp flash at 5Hz
Running lamp flash at 5Hz
Judge: Room temp. sensor is abnormal
Validate: Check whether the resistance of the
temp. sensor is correct according to Annex 1
Replace room temp. sensor
No
Replace indoor PCB
Yes
Defrosting lamp flash at 5Hz
Judge: Evaporator temp. sensor is abnormal
Validate: Check whether the resistance of the
temp. sensor is correct according to Annex 1
Replace room temp. sensor
No
Replace indoor PCB
Yes