HEAT MODE
If the air conditioner is off and then turned on while set at COOL ,HEAT or DRY mode, it will
take approximately 3 minutes for the compressor to start.
The ST at heat mode is adjustable within16 -31
.
When RT ST, the compressor stops; when RT<ST-1
, the compressor starts.
Once turning on the unit while set at heat mode, if all the conditions meet with the
requirement of compressor operation, the four-way valve gets charged and 8 seconds later,
the compressor and outdoor fan start running.
Heat overload protection:
Deice control:
Conditions for activating deice:
a. The working hours of compressor accumulates to be 40 minutes.
b. When OT -4
for 1 minute.
Conditions for terminating deice:
a. When OT 15
for 1 minute.
b. Over 10 minutes of deicing operation.
CONTROL SPECIFICATION
Electric-heat control:
Conditions for initiating electric-heat function:
a. RT 23
; b. RT+3
ST; c. The indoor fan runs;
d. Turn on the electric-heat key; e. PT<50
Conditions for terminating electric-heat function:
a. PT
50
; b. RT
26
; c. The indoor fan stops running;
d. Turn off the electric-heat key; e. Mode change.
Conditions for terminating electric-heat function:
a. PT
50
; b. RT
26
; c. The indoor fan stops running;
d. Turn off the electric-heat key; e. Mode change.
OT
15
-4
COMP
ON
OFF
OFAN
ON
OFF
ON
OFF
4-way
valve
TIME
30S
15S
30S
15S
10 minutes at most
18
For 7000
, when PT 47
, the outdoor fan stops; when PT
42
, the outdoor
fan starts; when PT
60
, the compressor stops.
BTU/h Model
For 9000
, when PT 50
, the outdoor fan stops; when PT
47
, the outdoor
fan starts; when PT
63
, the compressor stops.
BTU/h Model
For
9000
, when PT 55
, the outdoor fan stops; when Pt
50
, the outdoor
fan starts; when PT
63
, the compressor stops.
BTU/h Model
Strong-wing prevention :
A.PT<27,the indoor fan stops running, the swing louver cannot be controlled by the remote
controller.
B.34>PT
27,the indoor fan runs at low speed, the sweep louver erects.
C.PT
34,the indoor fan and the swing louver can be controlled normally.
Summary of Contents for ACP-09CH25ZNM
Page 1: ...ACP 09CH25ZNM ACP 12CH35ZNM RoHS Service manual ENG ...
Page 2: ......
Page 29: ...Outdoor unit Exploded Views and Parts List 27 AUS 07C53R010Lx ACP 09CH25ZNM ...
Page 31: ...Outdoor unit Exploded Views and Parts List 29 AUS 07C53R010Lx ACP 09CH25ZNM ...
Page 33: ...Outdoor unit Exploded Views and Parts List 31 ACP 12CH35ZNM ...
Page 35: ...Outdoor unit Exploded Views and Parts List 33 ACP 12CH35ZNM ...
Page 37: ...Outdoor unit Exploded Views and Parts List 35 AUS 12C53R130Lx ...
Page 39: ...Exploded Views and Parts List Outdoor unit 37 AUS 12H53R130Lx ...
Page 43: ...Wiring Diagrams Indoor unit ACP 12CH35ZNM Outdoor unit 41 ACP 12CH35ZNM IFAN ...
Page 44: ......
Page 45: ......
Page 46: ......