Switching on the air conditioner
The current leakage switch
jumps to turn off
Junction wire looses and collides with the outer
cover.
Degraded capability of wire insulation.
Insulation capability of
some components has
lowered.
Check the resistance
of every component
by multimeter
Water comes into the plug or electric components.
The fuse is blown
or air limit switch
jumps to turn off
Is the voltage
of power supply lower
than 15% of rated voltage
(220V)?
Yes The voltage is low,
please add manostat.
Short circuit
somewhere.
Partially short circuit in
some components.
Fuse capacity
is adequate or not?
Yes
No
No
Replace with adequate
fuse.
Check as the above
-mentioned method.
Short circuit in the
electric wire or
connection wire.
Without any
response
Check whether
the receptacle has
power or not.
Power supply error
Strong circuit breaks
the circulation.
The transformer faults.
The main control board
faults.
FAULT DIAGNOSIS BY SYMPTOM
16
Summary of Contents for ACP-09CH25ZNM
Page 1: ...ACP 09CH25ZNM ACP 12CH35ZNM RoHS Service manual ENG ...
Page 2: ......
Page 29: ...Outdoor unit Exploded Views and Parts List 27 AUS 07C53R010Lx ACP 09CH25ZNM ...
Page 31: ...Outdoor unit Exploded Views and Parts List 29 AUS 07C53R010Lx ACP 09CH25ZNM ...
Page 33: ...Outdoor unit Exploded Views and Parts List 31 ACP 12CH35ZNM ...
Page 35: ...Outdoor unit Exploded Views and Parts List 33 ACP 12CH35ZNM ...
Page 37: ...Outdoor unit Exploded Views and Parts List 35 AUS 12C53R130Lx ...
Page 39: ...Exploded Views and Parts List Outdoor unit 37 AUS 12H53R130Lx ...
Page 43: ...Wiring Diagrams Indoor unit ACP 12CH35ZNM Outdoor unit 41 ACP 12CH35ZNM IFAN ...
Page 44: ......
Page 45: ......
Page 46: ......