Burr

Oblique

Copper pipe

90

Roughness

Reamer

Burr

 Outer diameter           

A(mm)

2.0--2.5

3.0--3.5

3.5--4.0

6.35mm ( 1/4

)

9.52mm ( 3/8

)

12.7mm ( 1/2

)

15.88mm(5/8

)

4.0--4.5

Air exhausting

4

Installation of the drain joint(only for heat pump type)

Bottom

Double-channel 
drain joint

Drain hose

Joint of the connecting pipe

Put some seal oil to cover the joint and the flare.

Align the centre of joint in line with that of flare and tighten the nut of connecting pipe
with wrench. ( Adjust the torque by the same method of connecting pipe for indoor unit.)

   

 Insert the outdoor double-channel drain joint in one of the  
 bottom holes of the suitable size then connect drain hose 
 and joint together. 

2

3

gas shut-off  
valve

liquid shut-off valve

service port

gas connecting
pipe

liquid connecting pipe

valve nuts

service port cap

allen wrench 

Screw down the cap of both gas shut-off valve and 
liquid shut-off valve as well as the nut of service port.

Use Allen wrench to turn the  valve cork of liquid side
at 90  counter-clockwise, and close it after 10 seconds.
Use soapy water to check the  gas leakage especially
at all joint. If there is no gas leakage, please turn the 
valve cork of liquid side at 90  counter-clockwise again.

Press the cork of service port at gas shut-off valve, 10 
seconds later, when you see foggy gas discharged, that 
means inner air is exhausted out.

Use Allen wrench to turn the  valve cork of  both liquid 
shut-off valve and gas shut-off valve counter-clockwise
until they are completely open and then replace the 
valve caps and tighten them.

Process of flared tube

5

Use the pipe cutter to cut off the broken part of flare.

Remove burrs at the cut of the flare.

Insert a nut into the connecting pipe and do flaring 
with specified flaring tools, reamers for example.

Check the quality of flaring technique.

Remove burrs at the cut of the flare.

9

INSTALLATION

Summary of Contents for ACP-09CH25ZNM

Page 1: ...ACP 09CH25ZNM ACP 12CH35ZNM RoHS Service manual ENG ...

Page 2: ......

Page 3: ...y precautions Installation 11 11 Block diagram 12 12 Trouble shooting 13 13 Fault diagnosis by symptom 17 17 Control specification 21 21 To disassemble mechanical parts 25 25 Exploded views and parts list Wiring diagrams 2 2 39 39 ...

Page 4: ...unding area 1 2 Location of indoor unit A place solid enough to bear the weight of the unit and not cause any shake Good ventilation less dust far from direct rain and sunshine Avoid places close to inflammable gas leakage Keep the air inlet and outlet at a far distance from the blockage Keep the height distance between the indoor and outdoor unit at most 5m Mount on the wall solid enough to bear ...

Page 5: ...he pipeline on the thin armor plate or on the wall of metal mesh you should use the wooden board to clamp between the wall and the pipeline or wrap up the pipeline with 7 8 layers of insulating plastic tape left 100mm above 300mm above 500mm above 300mm above 500mm above 500mm INSTALLATION Installation diagram of indoor unit and outdoor unit Confirm the installation position by the mark of the ind...

Page 6: ...l NOTICE Fasten string at the central hole 105mm or more from sidewall 455mm or more at least 250mm from sidewall Tapping screw ST4 25 5 mounting plate plumb 40mm at least 24mm plumb fasten string at the central hole 105mm 45mm Center of hole 65mm plumb NOTICE The holes at solid arrow position must be secured to avoid the shake of mounting plate When the expansion bolts are used two holes 11 20 or...

Page 7: ... of the indoor unit cut part 2 of the unit If pipe comes out of the left side of the indoor unit cut part 3 of the unit Installation of the drain hose 3 Drain hose gaspipe Liquid pipe felt Adiabatic underlay drain hose If pipe comes out of the left side of the indoor unit the drain hose must be refitted otherwise water leakage may occur Refit methods Interchange the position of drain hose and drai...

Page 8: ...sition of the pipe in the indoor unit should not exceed 10 The number of bent position of the pipe in the indoor unit and the outdoor unit should not exceed 15 The radius of bent position should be more than 10cm Evaporator craft tube Do not exhaust the inside air just by loosing the nut since there is the air of certain pressure inside the tube of indoor unit Please do not make extra effort for f...

Page 9: ...Piping cover Ejecting hole Right wiring Back wiring Sponge Piping cover 2 Loosen the self tapping screws 2 pcs on the fixing clip to loosen the fixing clip 5 Install the maintenance board After the pipes and cable wire are installed please seal the sponge block as per drawing indication 3 Loosen the fixing screw of the wire terminal board pass the power wire and signal wire through the fixing clip...

Page 10: ...sition otherwise fire or electrical shock may occur because of dust or moisture The connecting cables must be clipped together Please take the electric circuit diagram attached to the indoor outdoor units as major reference while installing The power wire and signal wire between the indoor outdoor units must be connected one by one as per corresponding number on the wiring terminal board All the m...

Page 11: ...the cap of both gas shut off valve and liquid shut off valve as well as the nut of service port Use Allen wrench to turn the valve cork of liquid side at 90 counter clockwise and close it after 10 seconds Use soapy water to check the gas leakage especially at all joint If there is no gas leakage please turn the valve cork of liquid side at 90 counter clockwise again Press the cork of service port ...

Page 12: ...rant L the length of connecting pipe 6 7 0 0 8 15 50 9 30 100 10 45 150 The length of connecting pipe m Cool only type added amount g Heat pump type added amount g Set the unit to cool operation mode Stop operation of the air conditioner Relocation of the air conditioner Refer to this procedure when the unit is relocated 1 Carry out the pump down procedure 2 Remove the power cord 3 Disconnect the ...

Page 13: ... the power Check switch source and then the operation test is activated If the indicator lamps light up at first and then go out in succession or the LED window of the indoor unit illuminates at first and then goes out the system is under normal operation If one of the indicator lamps is flashing at all times or failure codes are displayed on the LED window of the indoor unit the system has someth...

Page 14: ... operation is automatically controlled in DRY mode depending on the room temperature and humidity Compressor of the outdoor unit is operating although it is turned off in HEAT mode When the unit is turned off while de ice is activated the compressor continues operation for up to 10 minutes maximum until the deice is completed Timer indicator lamp lights up and the air conditioner does not operate ...

Page 15: ...ning burden is not adequate for the room The capillary pipeline are blocked or the valve is not open or the connecting tube is folded flat The doors and windows are not closed well too weak of input cooling power or too many heat resources in the room Some leakage in the valve No cooling The four way valve error Blockage in the system The valve isnot completely open the capillary or Pipeline is ha...

Page 16: ...s too dirty Air conditioning burden is not adequate for the room Accumulated lampblack or dust is attached to the vane The capillary pipeline are blocked or the valve is not open or the connecting tube is folded flat The doors and windows are not closed well too weak of input cooling heating power Some leakage in the valve No heating The four way valve or solenoid valve faults The four way valve d...

Page 17: ...ieces deform due to expansion when hot and shrink when cold Or some spare parts may not match very well Noise from Outdoor unit Collision sound of the machine Collision of the pipeline fixing screws loose or deform caused by rubbing Inappropriate installation method the unit does not match with the installation kit very well or the compressor quivers acutely The whole unit resonates thedoor and wi...

Page 18: ...ch jumps to turn off Is the voltage of power supply lower than 15 of rated voltage 220V Yes The voltage islow please add manostat Short circuit somewhere Partially short circuit in some components Fuse capacity is adequate or not Yes No No Replace with adequate fuse Check as the above mentioned method Short circuit in the electric wire or connection wire Without any response Check whether the rece...

Page 19: ...mpressor start running If not either the outdoor fan or compressor could start The four way valve keeps being off all the time at cool mode If the horizontal air flow louver is set at low angle on COOL mode after a while it will auto swing to its maximum angel for system protection 3 minutes later the horizontal air flow louver will resume to its original position Condensate dew prevention Anti ic...

Page 20: ...he indoor fan runs d Turn on the electric heat key e PT 50 Conditions for terminating electric heat function a PT 50 b RT 26 c The indoor fan stops running d Turn off the electric heat key e Mode change Conditions for terminating electric heat function a PT 50 b RT 26 c The indoor fan stops running d Turn off the electric heat key e Mode change OT 15 4 COMP ON OFF OFAN ON OFF ON OFF 4 way valve TI...

Page 21: ...speed can not be controlled by remote controller CONTROL SPECIFICATION AUTO MODE Mode Mode 24 26 RT 2 RT 2 Cool Cool Dry RT 2 RT 2 Dry Heat 24 21 Room Temperature RT RT 26 25 RT 23 RT 23 26 RT 25 Heat pump type Cool only type Initial Setting Temperature Initial Setting Temperature In this mode the air conditioner can automatically adjust the room temperature to decide the most suitable temperature...

Page 22: ... of operation the set temperature will increase by 1 One hour later the set temperature will increase by 1 once more The unit will then continue operating at 2 above the set temperature B After one hour of operation the set temperature will decrease by 2 One hour later the set temperature will decrease by 2 once more The unit will then continue operating at 4 below the set temperature Sleep mode i...

Page 23: ... 2 Contract the second finger to the left and right handle and pull to open the inlet grille 3 Draw away signal line 6 Put hands at the two ruts of the body then pull the front panel out 5 Loosen two fixing screw of front grille 4 Take the left and right filter out TO DISASSEMBLE MECHANICAL PARTS 21 The following pictures taking L1 series as an example are presented just for the purpose of illustr...

Page 24: ...oftly the indoor pipe temperature sensor out from the pipe casing tepping motor line and p No Parts Procedure Remark 3 Push the hook outside to take the electrical box out easily 2 Electrical parts 3 Ass y tray drain 1 Push the left and right hooks to make the ass y pulled out 22 TO DISASSEMBLE MECHANICAL PARTS ...

Page 25: ...tray drain from the body 1 Push the left hook and separate the left part out of evaporator 1 Separate the fan motor from the fan No Parts Procedure Remark 2 Push the right hook and separate the right part out of evaporator 5 Fan motor and cross fan 23 TO DISASSEMBLE MECHANICAL PARTS ...

Page 26: ...e nut flange Turn to the right to remove as it a left turned screw 1 Loosen the fixing screw of the base electrical control 2 Fan motor propeller fan 3 3 Loosen the fixed screw of fan motor separate the fan motor from outdoor unit No Parts Procedure Remark Ass y control out 2 separate the connector 3 Separate the ass y control out from the outdoor unit 24 TO DISASSEMBLE MECHANICAL PARTS ...

Page 27: ...Indoor unit Exploded Views and Parts List 25 AUS 07C H 53R010Lx AUS 12C H 53R130Lx ACP 12CH35ZNM ACP 09CH25ZNM ...

Page 28: ...ndoor unit terminal block 1 16 Transformer 1 17 Mounting plate 1 18 Main control board 1 19 Power supply cord 1 20 Room temperature sensor 1 21 Pipe temperature sensor 1 22 Pipe fixing plate 1 23 fan motor 1 24 Electrical holder 1 25 Stepping motor 1 29 2 L1 L3 L16 L18 without L15 decorate tape L17 decorate board 1 Decorate ring L1 L17 display piece L15 transparency piece L15without Indoor display...

Page 29: ...Outdoor unit Exploded Views and Parts List 27 AUS 07C53R010Lx ACP 09CH25ZNM ...

Page 30: ...1 10 Electrical install board supporter 1 11 Left back side plate 1 12 Back cover 1 13 right back side plate 1 14 Electrical install board 1 15 Capacitor fixing clip 1 16 Outdoor unit terminal block 1 17 power supply cord clip 1 18 capacitor for Compressor 1 19 Fan motor capacitor 1 20 Capillary assembly 1 21 High pressure valve 1 22 Low pressure valve 1 23 valve board 1 24 Compressor screw 3 25 C...

Page 31: ...Outdoor unit Exploded Views and Parts List 29 AUS 07C53R010Lx ACP 09CH25ZNM ...

Page 32: ... Partition 1 10 Four way valve 1 11 Electrical install board supporter 1 12 Left back side plate 1 13 Back cover 1 14 Right back side plate 1 15 Electrical install board 1 16 Capacitor fixing clip 1 17 Outdoor unit terminal block 1 18 Power supply cord clip 1 19 Capacitor for Compressor 1 20 Fan motor capacitor 1 21 Capillary assembly 1 22 High pressure valve 1 23 Low pressure valve 1 24 Valve boa...

Page 33: ...Outdoor unit Exploded Views and Parts List 31 ACP 12CH35ZNM ...

Page 34: ...er supply cord fixing 1 8 Power supply cord clip 1 9 Capacitor for compressor 1 10 Electrical install board 1 11 Right side board 1 12 Top cover 1 13 Fan motor capacitor 1 14 Outdoor unit terminal block 1 15 High pressure valve 1 16 Capillary assembly 1 17 Low pressure valve 1 18 Compressor 1 19 Bottom board 1 20 Condenser 1 21 Uphold board 1 22 Capacitor fixing clip 1 23 Fan motor out door 1 24 F...

Page 35: ...Outdoor unit Exploded Views and Parts List 33 ACP 12CH35ZNM ...

Page 36: ...ply cord clip 1 9 Capacitor for compressor 1 10 Electrical install board 1 11 Right side board 1 12 Top cover 1 13 fan motor capacitor 1 14 Outdoor unit terminal block 1 15 High pressure valve 1 16 Capillary assembly 1 17 Low pressure valve 1 18 Four way valve 1 19 Compressor 1 20 Bottom board 1 21 Condenser 1 22 Uphold board 1 23 Capacitor fixing clip 1 24 Fan screw nut M6 1 25 Fan screw nut M8 3...

Page 37: ...Outdoor unit Exploded Views and Parts List 35 AUS 12C53R130Lx ...

Page 38: ... side board 1 8 Condenser 1 9 Back cover 1 10 Fixed board 1 11 Top cover 1 12 Fan motor capacitor 1 13 Capacitor for Compressor 1 14 Electrical install board 1 15 Capacitor fixing clip 1 16 Outdoor unit terminal block 1 17 Power supply cord clip 1 18 Right handle 1 19 Right back side board 1 20 Capillary assembly 1 21 High pressure valve 1 22 Low pressure valve 1 23 Valve board 1 24 Compressor 1 2...

Page 39: ...Exploded Views and Parts List Outdoor unit 37 AUS 12H53R130Lx ...

Page 40: ... plate 1 8 Condenser 1 9 Right back side plate 1 10 Right handle 1 11 Fan motor capacitor 1 12 Capacitor for Compressor 1 13 Electrical install board 1 14 Outdoor unit terminal block 1 15 Power supply cord clip 1 16 Outdoor fan motor supporter 1 17 Outdoor fan motor 1 18 Four way valve 1 19 Capillary assembly 1 20 High pressure valve 1 21 Valve board 1 22 Low pressure valve 1 23 Compressor 1 24 Ba...

Page 41: ...Wiring Diagrams Indoor unit Outdoor unit 39 AUS 07C53R010Lx ACP 09CH25ZNM ACP 12CH35ZNM AUS 12C53R130Lx AUS 07C53R010Lx ACP 09CH25ZNM ACP 12CH35ZNM AUS 12C53R130Lx IFAN ...

Page 42: ...Wiring Diagrams Indoor unit AUS 07H53R010Lx Outdoor unit 40 AUS 12H53R130Lx ACP 09CH25ZNM AUS 07H53R010Lx AUS 12H53R130Lx ACP 09CH25ZNM IFAN ...

Page 43: ...Wiring Diagrams Indoor unit ACP 12CH35ZNM Outdoor unit 41 ACP 12CH35ZNM IFAN ...

Page 44: ......

Page 45: ......

Page 46: ......

Reviews: