Green Series
99999
Failure and analysis
T h e b r e a k e r t r i p s a t o n c e w h e n i t
is set to "ON".
Measure insulation resistance to ground to see
if there is any leakage.
Trip of breaker or blow
of fuse
The breaker trips in few minutes
when it is set to "ON"
C h e c k p o w e r s u p p l y c i r c u i t .
Check if the plug is properly plugged in and
make the loose contact firm.
Change controller fuse
Check remote controller
C h a n g e b a t t e r i e s
Change controller
Adjust setting temp.
Improper setting of temperature
W i r e l o o s e o r w r o n g c o n n e c t i o n
In cool, heat mode,the
outdoor
unit and compressor
will not run.
Correctly wire according to the drawing
Power voltage is too low
R e m o t e c o n t r o l l e r m a l f u n c t i o n
R e c e i v e r i s b r o k e n
C o n t r o l l e r i s b r o k e n
Receiver loose or poor connection
N o p o w e r
Fuse of controller burnt out
Remote controller is short of power
Power plug is not well plugged in and poor con-
nection
Fasten the wiring; measure the output
v o l t a g e o f t h e t r a n s f o r m e r , i f i t i s
incorrect, change the transformer
Air conditioner can not start up
The air conditioner
does not react after
it is powered ( after
the plug is inserted,
the buzzer does
not sound and the
remote startup has
no response)
The remote controller
does not receive
signals (after it is
powered, the buzzer
will sound, unless it
has malfunction)
The circuit or the part of the air conditioner has
malfunction. They heat and break the insulation
and lead to short circuit or creepage. Measure
the insulation resistance or eliminate the malfunc-
t i o n o n e b y o n e . I f t h e b r e a k e r i t s e l f h a s
malfunction, then replace the breaker.
The transformer connection is loose or has bad
contact or the transformer has malfunction
First, press the manual switch button AUTO,
if there is no response,check based on the
above methods. If it runs normally after
pressing the button,check again whether the
installation position and the connection wire
of the reception head is correct. If it is
correct,then replace the receiver or the re-
mote controller.
heck the voltage. If it is lower than 10£¥ of the rated voltage, check the
cause, improve the power supply condition and add the stabilized voltage
power supply.
C o n t r o l l e r m a l f u n c t i o n ( I C 2 0 0 3 b r o k e n ,
creepage of parallel capacitor of relay loop,
relay is broken etc.)
Note: When replacing thecontroller, make sure insert the wire jumper into the new controller, otherwise, the
running indicator off 3s, blink 15 times, (the dual eight will display C5) but cannot turn on the unit.
Summary of Contents for ACP-09CH25GEH
Page 1: ...ACP 09CH25GEH ACP 12CH35GEH ACP 18CH50GEH RoHS Service manual ENG ...
Page 2: ......
Page 13: ...913 378 680 550 342 ACP 18CH50GEH O Bolt Nut Wrench Unit mm ...
Page 14: ...GWHN24DCNK3A1A O 7PKV OO QNV 0WV 9TGPEJ ...
Page 17: ......
Page 54: ...Exploded View of Components and Parts of Indoor unit ᑇ ޚ ...
Page 56: ... 18 24 Exploded View of Components and Parts of Indoor unit ...
Page 58: ... 09 Exploded View of Components and Parts of outdoor unit ...
Page 60: ... 12 Exploded View of Components and Parts of outdoor unit ...
Page 62: ... 18 Exploded View of Components and Parts of outdoor unit ...
Page 64: ... 24 Exploded View of Components and Parts of outdoor unit ...
Page 66: ... 09X2 Exploded View of Components and Parts of outdoor unit ...
Page 68: ... 09 12 Exploded View of Components and Parts of outdoor unit ...
Page 70: ... 12X2 Exploded View of Components and Parts of outdoor unit ...
Page 77: ......
Page 78: ......
Page 79: ......