Installation Instructions
Cover Opening Alarm and External Alarm Input are electrically tied
together internally.
Alarm contact types, N.O or N.C are selectable by the Alarm Input Selection
Jumper and the selection types should be matched with Alarm Type in setup
menu.
When both the Cover Opening Alarm and External Alarm Input are used at the
same time, the alarm contact types must match. Otherwise, the alarm malfunctions.
When only the External Alarm Input is used with disabling Cover Opening Alarm,
remove the jumper cap of Alarm Input Selection Jumper.
Default setting for Alarm Input selection jumper is N.C. It prevents the Alarm from
generating when Junction box is OPEN during installation. The alarm Input
selection jumper should be set to N.O and Event Trigger/Action should be
denied to enable Cover opening alarm.
For Cover Opening Alarm, please go to SETUP> Event Rules> Event Processing>
Add Event Trigger should be set to “Alarm In” an Event Action should be
set from the available options.
• Cover Opening Alarm and External Alarm Input :
CAUTION
N.O : Alarm is generated when Junction box is OPEN.
N.C : Alarm is generated when Junction box is CLOSED.
[N.O]
[N.C]
Cover opening alarm switch
Alarm Input selection jumper
12
13