background image

them out from the “+” end and correctly re-inserting them.

BATTERY COMPARTMENT

+ + +

4. Re-install the detector on its mounting base by turning the detector clockwise until the mat-

ing marks align.

5. After the power-up sequence, the green LED should blink once every 12 seconds to indic-

ate normal operation. If the batteries are not installed correctly, the detector will not oper-
ate and the batteries may be damaged. If the detector does not power up, check that the
batteries are installed correctly and fully charged.

6. Test the detector as described later.

CONSTANT EXPOSURES TO HIGH OR LOW TEMPERATURES OR HIGH HUMIDITY MAY
REDUCE BATTERY LIFE.

Installation Instructions

The SMD-429 PG2 Series wireless smoke detector shall be installed and used within an envir-
onment that provides the pollution degree max 2 and over voltages category II in non- haz-
ardous locations, indoor only. The equipment is designed to be installed by SERVICE
PERSONS only; (SERVICE PERSON is defined as a person having the appropriate technical
training and experience necessary to be aware of hazards to which that person may be
exposed in performing a task and of measures to minimize the risks to that person or other per-
sons).

1. Smoke Detector Placement

Research has shown that all hostile fires in homes generate smoke to a greater or lesser extent.
Experiments with typical fires in homes indicate that detectable quantities of smoke precede
detectable levels of heat in most cases. For these reasons, smoke alarms should be installed
outside of each sleeping area and on each storey of the home.

The following information is for general guidance only and it is recommended that local fire
codes and regulations be consulted when locating and installing smoke alarms. It is recom-
mended that additional smoke alarms beyond those required for minimum protection be
installed. Additional areas that should be protected include: the basement; bedrooms, especially
where smokers sleep; dining rooms; furnace and utility rooms; and any hallways not protected
by the required units. On smooth ceilings, detectors may be spaced 9.1 m (30 ft) apart as a
guide. Other spacing may be required depending on ceiling height, air movement, the presence
of joists, uninsulated ceilings, etc. Consult National Fire Alarm Code NFPA 72, CAN/ULC- S553
or other appropriate national standards for installation recommendations.

l

Do not locate smoke detectors at the top of peaked or gabled ceilings; the dead air space
in these locations may prevent the unit from detecting smoke.

l

Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air move-
ment around the detector may prevent smoke from entering the unit.

l

Do not locate detectors in areas of high humidity.

l

Do not locate detectors in areas where the temperature rises above 38 ºC (100 ºF) or falls
below 5 ºC (41 ºF).

l

Smoke detectors must always be installed in USA in accordance with Chapter 29 of NFPA
72, the National Fire Alarm Code: 29.5.1.1.

Where required by applicable laws, codes, or standards for a specific type of occupancy,
approved
single and multiple-station smoke alarms shall be installed as follows:

1. In all sleeping rooms and guest rooms.
2. Outside of each separate dwelling unit sleeping area, within 6.4 m (21 ft) of any door to a

sleeping room, the distance measured along a path of travel.

3. On every level of a dwelling unit, including basements.
4. On every level of a residential board and care occupancy (small facility), including base-

ments and excluding crawl spaces and unfinished attics.

5. In the living areas of a guest suite.
6. In the living areas of a residential board and care occupancy (small facility).

NOTE

: In Australia the device shall not be installed in locations where the normal ambient

temperature is lower than 5 ºC or higher than 45 ºC.

Summary of Contents for SMD-429 PG2 Series

Page 1: ...Reset button to silence the local annunciation of the alarm and transmit an alarm restore event to the control panel The LED flashes every 8 seconds for up to 10 minutes to indicate the alarm has bee...

Page 2: ...indicator the red LED blinks once per minute You can clear the alarm restore indicator only from the control panel l Tamper Tamper Restore tamper switch activated 10 second maximum delay on restore b...

Page 3: ...eyond those required for minimum protection be installed Additional areas that should be protected include the basement bedrooms especially where smokers sleep dining rooms furnace and utility rooms a...

Page 4: ...station Initiate test by pressing the test button for 5 seconds minimum Alarm activation is indicated by the flashing LED the sounder and transmission of the alarm signal to the control panel The dete...

Page 5: ...led clean and in good working order If in doubt have a professional evaluation Family Escape Planning There is often very little time between the detection of a fire and the time it becomes deadly Bec...

Page 6: ...eleased the following sequence of events occur l Red LED lights for 0 5 s off for 0 5 s l Yellow LED lights for 0 5 s off for 0 5 s This is followed by 3 loud alarm beeps and at the same time the red...

Page 7: ...ms Not Covered by Warranty In addition to the items which void the Warranty the following items shall not be covered by Warranty i freight cost to the repair centre ii customs fees taxes or VAT that m...

Page 8: ...ts the media and printed materials any upgrades and this EULA iii if you do not retain any copies of any portion of the Software iv if the recipient agrees to the terms of this EULA and v if the Softw...

Page 9: ...anual of the alarm control panel All the instructions specified within that manual must be observed FCC and IC Compliance Statement CAUTION Changes or modifications not expressly approved by Visonic c...

Reviews: