2. Mount Smoke Detector Backplate

NOTE:

The alarm device should only be installed by a competent engineer or technician. The

device should not be used with a guard.

Once a suitable location is found, mount the detector backplate. Install the mounting base on
the ceiling or on the wall (if local ordinances permit) using screw locations as required. Use the
two screws and anchors provided. Maneuver the base so the screws are at the elbow of the
screw slots and secure.

100 mm (4 in.) minimum

100 mm (4 in.)

 minimum

3. Mounting

Fit the detector inside the base by aligning it over the base. The detector's alignment notch
should be slightly offset from the mounting base tamper release tab. Then turn the detector
clockwise until it clicks into place.

4. Test Unit

NOTE:

The central monitoring station if used, should be notified prior to the test being gen-

erated. This prevents a false alarm and an unnecessary response from the central mon-
itoring station.

Initiate test by pressing the test button for 5 seconds minimum. Alarm activation is indicated by
the flashing LED, the sounder, and transmission of the alarm signal to the control panel. The
detector restores to normal when the test button is released.

NOTE:

Allow a minimum of 20 seconds after power up and , after test, alarm or tamper restore

activations. Do not use the test button when smoke is present.

NOTE:

If the detector is in one of the following states when a test is initiated; it will not enter an

alarm state:

l

Tamper, detector not installed on mounting plate

l

Compensation Trouble

l

Other internal faults that could prevent a smoke or heat alarm

5. Device Enrollment

The 7-digit serial number located on the back of the smoke detector housing must be enrolled
on the alarm systems control panel. See the Receiver Installation Manual and follow the enroll-
ment procedure. For placement tests remove the detector from its backplate for one second
(tamper) and then reattach. Wait at least 30 seconds for the test result before activating again.
A general description of the procedure is provided in the following flow chart:

Summary of Contents for SMD-429 PG2 Series

Page 1: ...Reset button to silence the local annunciation of the alarm and transmit an alarm restore event to the control panel The LED flashes every 8 seconds for up to 10 minutes to indicate the alarm has bee...

Page 2: ...indicator the red LED blinks once per minute You can clear the alarm restore indicator only from the control panel l Tamper Tamper Restore tamper switch activated 10 second maximum delay on restore b...

Page 3: ...eyond those required for minimum protection be installed Additional areas that should be protected include the basement bedrooms especially where smokers sleep dining rooms furnace and utility rooms a...

Page 4: ...station Initiate test by pressing the test button for 5 seconds minimum Alarm activation is indicated by the flashing LED the sounder and transmission of the alarm signal to the control panel The dete...

Page 5: ...led clean and in good working order If in doubt have a professional evaluation Family Escape Planning There is often very little time between the detection of a fire and the time it becomes deadly Bec...

Page 6: ...eleased the following sequence of events occur l Red LED lights for 0 5 s off for 0 5 s l Yellow LED lights for 0 5 s off for 0 5 s This is followed by 3 loud alarm beeps and at the same time the red...

Page 7: ...ms Not Covered by Warranty In addition to the items which void the Warranty the following items shall not be covered by Warranty i freight cost to the repair centre ii customs fees taxes or VAT that m...

Page 8: ...ts the media and printed materials any upgrades and this EULA iii if you do not retain any copies of any portion of the Software iv if the recipient agrees to the terms of this EULA and v if the Softw...

Page 9: ...anual of the alarm control panel All the instructions specified within that manual must be observed FCC and IC Compliance Statement CAUTION Changes or modifications not expressly approved by Visonic c...

Reviews: