SPIRIT G XL 1-3KVA PF.09 - UPS www.visionups.com
46
1000/1500/2000/3000 VA
0.9/1.35/1.8/2.7 kW
Frequency
50 or 60 Hz, autosensing
Output Overload
(Normal Mode)
108%±5%–150%±5%: Load transfers to Fault mode after
30 seconds.
150%±5%–200%±5%: Load transfers to Fault mode after
300 ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
Output Overload
(Bypass Mode)
100%±5%–130%±5%: Load transfers to Fault mode after
20 minutes.
130%±5%–150%±5%: Load transfers to Fault mode after
2 minutes.
150%±5%–200%±5%: Load transfers to Fault mode after
15 seconds.
>200%±5%: Load transfers to Fault mode after 140 ms.
Output Overload
(Battery Mode)
108%±5%–150%±5%: Load transfers to Fault mode after
30 seconds.
150%±5%–200%±5%: Load transfers to Fault mode after
300 ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
Voltage Waveform
Sine wave
Harmonic
Distortion
<3% THD on linear load; <5% THD on non-linear load
Transfer Time
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of
utility)
Power Factor
0.9
Load Crest Factor
3 to 1
Table 18.
Electrical Output Connections (
All
Models)
Model
Output Connections
Output Cables
1K-
RT
(IEC C13-10A)*6
IEC320 C14-10A
1.5K-
RT
(IEC C13-10A)*6
IEC320 C14-10A
2K-
RT
(IEC C13-10A)*6
IEC320 C14-10A