background image

General Information

56

 

5

Section 2

General Information

Figure 1 System Components

Item

Description

Part 

Number

UV Systems

1

Temperature management valve 
(optional)

440179

Optional

2

Flow restrictor 

Optional

Used on all systems

3

O-ring

410867

Used on all systems

4

Open-ended, GE 214 fused quartz 
sleeve with fire polished ends

QS-001

VH200

QSO-410

VH410, VH410M

QSO-600

VP600, VP600M

QSO-950

VP950, VP950M

5

Hard glass, coated Sterilume

®

-HO UV 

lamps for long, consistent life (9000 
hours)

S200RL-HO

VH200

S410RL-HO

VH410, VH410M

S600RL-HO

VP600, VP600M

S950RL-HO

VP950, VP950M

6

Retaining Nut

RN-001

Used on all systems

7

Controller (for 100-240V/50-60HZ 
models only)

BA-ICE-CL

VH200, VH410

BA-ICE-C

VP600, VP950

BA-ICE-CM

VH410M, VP600M, VP950M

8

IEC replacement power cords for 
controller (sold separately)

260010

VH200, VH410, VH410M, VP600, VP600M, VP950, VP950M (N. America)

602637

VH200/2, VH410/2, VH410M/2, VP600/2, VP600M/2, VP950/2, VP950M/2 (EU CEE)

260012

VH200/2B, VH410/2B, VH410M/2B, VP600/2B, VP600M/2B, VP950/2B, VP950M/2B 
(UK)

260013

VH200/2A, VH410/2A, VH410M/2A, VP600/2A, VP600M/2A, VP950/2A, VP950M/2A 
(Australia, NZ)

260019

NO CONNECTOR, 3-WIRE, BARE LEADS

9

Mounting Brackets/Clamp Assembly

410076

Used on all systems

10

UV Sensor

254NM-C1

VH410M, VP600M, VP950M

2

7

8

9

10

1

3

4

5

6

Solución de problemas

Procedimiento:

Sección 6

Solución de problemas

Síntoma

Causas probables

Soluciones

Pérdida de presión

El pre-filtro de sedimento está atascado

Reemplazar el cartucho del filtro por un cartucho adecuado de 5 micrones.

Nota: Verificar el suministro de agua de origen, ya que se pueden producir fluctuaciones en la 
presión de origen.

Regulador de flujo

El regulador de flujo provoca una pérdida de presión al acercarse al flujo total.

Altas 
concentraciones 
de
bacterias

Vaina tubular de cuarzo manchada 

o sucia

Limpiar la vaina tubular con un eliminador de sarro y eliminar la fuente del problema de mancha 

(por ejemplo, ablandar el agua dura), consultar la 

Sección 4.2

.

Cambio en la calidad del agua de 
entrada

Analizar el agua de suministro para asegurarse de que la calidad del agua se encuentra dentro de los 
límites permitidos para este sistema.

Contaminación en las líneas de agua 
después del sistema UV

Es fundamental que el flujo de aguas residuales se llene de cloro (lejía) antes de que el agua salga del 
sistema UV. Para funcionar de manera eficaz, el sistema de desinfección debe tener un sistema de 
distribución libre de bacterias. Consultar la 

Sección 3.2

Posible entrada de sedimentos a través 
del pre-filtro

Analice el agua de suministro para descartar la turbiedad: es posible que necesite un filtrado escalonado 
para recoger todos los sedimentos que entren en el sistema de agua (filtro de 20 micras seguido por uno 
de 5 micras, seguido a su vez por el sistema UV).

Agua procesada 
calentada

Problema común causado por un uso 
infrecuente del agua

Deje correr el agua hasta que vuelva a la temperatura ambiente.

El agua tiene un 
aspecto 
blanquecino

Provocado por el aire en las líneas 

de agua

Deje correr el agua hasta purgar todo el aire.

Unidad con fugas 
de agua

Problema con las juntas tóricas (en la 
tuerca de retención o el sensor UV)

Asegúrese de que la junta tórica esté en su sitio, compruebe si hay cortes o abrasiones, límpiela, 
humedézcala con agua o lubricante y vuelva a instalarla o sustitúyala si es necesario (410867).

Condensación en la cámara provocada 
por humedad excesiva y agua fría

Verificar la ubicación del sistema de desinfección y controlar la humedad.

Conexiones de puerto de entrada/salida 
inadecuadas

Comprobar las conexiones de rosca, volver a sellar con cinta Teflon

®

 y volver a apretar.

El sistema se 
apaga
de manera 
intermitente

Controlador interrumpido

  •

Asegurarse de que el sistema se ha instalado en un circuito propio, ya que es posible que 
otros equipos estén consumiendo la alimentación del UV (por ejemplo, bomba o nevera).

  •

El sistema UV no debería instalarse en un circuito incorporado a un interruptor de luz.

Alarma de fallo de 
lámpara activada: 
nueva lámpara

Conexión suelta entre la lámpara 

y el conector

Desconecte la lámpara del conector y vuelva a conectarla, asegurándose de apretarla bien

La humedad que se acumula en el 
conector puede impedir que la lámpara 
y el conector hagan contacto 
correctamente

Eliminar toda posibilidad de que la humedad entre en contacto con las clavijas del conector o la lámpara

1

•   

Desconecte el cable de 

sensor anterior del 
controlador.

2

1

2

•   

Conecte el cable en "Y" al 

controlador.

3

•   

Conecte el extremo "macho" 

del cable de sensor extraído 
al extremo "hembra" del 
nuevo cable en "Y".

•   

Conecte correctamente el 

cable de 4-20 mA al equipo 
correspondiente y garantice 
que todas las conexiones 
estén apretadas a mano. 

Summary of Contents for VH200

Page 1: ...f 1 519 763 5069 Courriel info viqua com www viqua com 425 Clair Rd W Guelph Ontario Canadá N1L 1R1 t 1 519 763 1032 f 1 800 265 7246 solo EE UU y Canadá t 31 73 747 0144 solo Europa f 1 519 763 5069 correo electrónico info viqua com www viqua com 425 Clair Rd W Guelph Ontario Canada N1L 1R1 t 1 519 763 1032 f 1 800 265 7246 US and Canada only t 31 73 747 0144 Europe only f 1 519 763 5069 e mail i...

Page 2: ...reclamación bajo garantía necesitará su factura original o bien deberá haber completado y enviado su tarjeta de registro de producto por correo postal o en línea Cobertura específica de la garantía La cobertura de la garantía es específica de la gama de productos de VIQUA La cobertura de la garantía está sujeta a las condiciones y limitaciones establecidas en la sección Condiciones y limitaciones ...

Page 3: ...l if you are in doubt as to whether the outlet is properly grounded DO NOT modify the plug provided with this system if it does not fit in the outlet have a proper outlet installed by a qualified electrician DO NOT use any type of adapter with this system GROUND FAULT CIRCUIT INTERRUPTER PROTECTION To comply with the National Electrical Code NFPA 70 and to provide additional protection from the ri...

Page 4: ...r yank cord to pull plug from outlet Always grasp the plug and pull to disconnect SYSTEM PROTECTION To protect your Controller a UL1449 certified or equivalent transient voltage surge suppressor is strongly recommended The UV lamp in this system conforms to the applicable provisions of the Code of Federal Regulations CFR requirements including Title 21 Chapter 1 Subchapter J Radiological Health Re...

Page 5: ...uales se llene de cloro lejía antes de que el agua salga del sistema UV Para funcionar de manera eficaz el sistema de desinfección debe tener un sistema de distribución libre de bacterias Consultar la Sección 3 2 Posible entrada de sedimentos a través del pre filtro Analice el agua de suministro para descartar la turbiedad es posible que necesite un filtrado escalonado para recoger todos los sedim...

Page 6: ...fection System Note UV system should be the final piece of treatment equipment Optional flow restrictor Note Mandatory for NSF credited systems Optional water softener To drain Optional by pass assembly Optional by pass assembly Optional by pass assembly Optional solenoid valve Hot water pipes Cold water pipes Customer supplied GFCI circuit to match voltage Water meter Main water shut off 5 Micron...

Page 7: ...2 segundos durante las condiciones de bajo nivel de UV Nota Niveles de UV de APLAZAMIENTO para aplazar temporalmente la alarma acústica y reactivar la válvula de solenoide si se ha instalado durante una alarma de nivel bajo de UV mantenga pulsado el botón de reinicio del temporizador durante cinco segundos Con esto se silenciará la condición de alarma acústica y se activará la salida de solenoide ...

Page 8: ... que sustituir la lámpara de 365 días a 1 día Al llegar a 0 días el controlador mostrará y emitirá un chirrido intermitente 1 segundo encendido 5 segundos apagado para indicar la necesidad de cambiar la lámpara 5 1 2 Interpretación del código A3 APLAZAMIENTO cuando aparece en la pantalla LED el mensaje de fin de la vida útil de la lámpara o A3 la alarma acústica se puede aplazar hasta 4 veces sepa...

Page 9: ...are present Replace the UV lamp annually or biennially if seasonal home use to ensure maximum disinfection Always drain the chamber when closing a seasonal home or leaving the unit in an area subject to freezing temperatures N O T I C E Reset lamp life timer after lamp replacement Refer to Section 5 1 3 Refer to www lamprecycle org for lamp disposal Do not use water during replacement of UV lamp 5...

Page 10: ...ED display will read once again 10 51 Maintenance Procedimiento Nota Tras reemplazar la lámpara UV o la vaina tubular de cuarzo realice el procedimiento de desinfección y consulte la Sección 3 2 1 Drene la cámara usando el puerto de drenaje 2 1 2 3 Quite la tuerca de retención el muelle flotante y la junta tórica de la parte inferior 3 1 2 Quite la tuerca de retención y la junta tórica de la parte...

Page 11: ... la vaina tubular de la lámpara Esta capa debe retirarse porque reduce la cantidad de luz UV que llega al agua reduciendo de este modo el rendimiento de la desinfección Si la vaina tubular no puede limpiarse deberá reemplazarse por otra Requisitos previos Cortar el suministro de agua y drenar todas las líneas Quitar la lámpara UV Consulte Sección 4 1 1 Corte la línea de agua de la cámara y libere ...

Page 12: ...or de intensidad UV de 254 nm tenga en cuenta que la introducción de la solución de lejía requerida para efectuar la desinfección provocará una condición temporal de bajo nivel de UV Esto se debe a que la lejía enturbia físicamente el agua no potable Una vez que la lejía circule por el sistema la condición de alarma volverá al estado normal Durante el proceso de desinfección la condición de alarma...

Page 13: ...optimum protection against microbiological contamination in water DO NOT disregard the warning signals The best way to ensure optimum UV performance is to have the water microbiologically tested by a recognized testing agency on a regular basis Instalación 5 Instale la lámpara UV Consulte Sección 4 1 6 Cuando se hayan realizado todas las conexiones de tuberías conecte el suministro de agua lentame...

Page 14: ...tes the UV level is still within a safe level however cleaning or lamp sleeve replacement may soon be required to Indicates the UV level is nearing the point of unsafe UV intensity UV system should be immediately serviced Indicates the UV level has now reached a level that is unsafe At this level the water should not be consumed The system water supply should be examined to determine the reason fo...

Page 15: ...oque un peligro de incendio Es muy recomendable usar bucles de goteo en los cables conectados al controlador Consulte Figura 5 El sistema de agua completo incluidos los depósitos de presión o agua caliente se deben esterilizar antes de la puesta en marcha Para ello enjuague con cloro lejía doméstica para destruir toda contaminación residual Consulte Sección 3 2 El sistema de desinfección está dise...

Page 16: ...tem should not be installed on a circuit which is incorporated into a light switch Lamp Failure Alarm on New Lamp Loose connection between lamp and connector Disconnect lamp from connector and reconnect ensuring that a tight fit is accomplished Moisture build up in connector may keep lamp and connector from making a solid connection Eliminate chance of any moisture getting to the connector and or ...

Page 17: ...l debido la exposición a rayos UV es recomendable usar accesorios metálicos y canalización de cobre de al menos 25 4 cm en la salida de la cámara UV AVISO La lámpara UV en el interior del sistema de desinfección tiene una clasificación nominal con una vida eficaz de aproximadamente 9000 horas Para garantizar una protección continua reemplace la lámpara UV una vez al año Los niños no deben usar el ...

Page 18: ...surización segura Este símbolo indica que se requiere el uso de botas de seguridad Este símbolo indica que el sistema está bajo presión Este símbolo indica que el operador debe leer toda la documentación disponible para realizar los procedimientos requeridos Este símbolo indica que existe peligro de exposición a rayos UV Se debe usar protección adecuada Este símbolo indica que el fontanero debe us...

Page 19: ...rcionarle años de funcionamiento sin problemas con un mínimo mantenimiento para proteger su agua potable contra contaminantes microbiológicos Para garantizar la continua desinfección del agua las lámparas UV se deben reemplazar cada año por repuestos VIQUA de fábrica Las lámparas VIQUA son fruto de un extenso desarrollo que ha resultado en una plataforma de desinfección altamente eficaz con un ren...

Page 20: ...e date of purchase During this time VIQUA will repair or replace at its option any defective parts covered by the warranty Please return the defective part to your dealer who will process your claim One Year Limited Warranty for UV lamps Sleeves and UV Sensors VIQUA warrants UV lamps sleeves and UV sensors to be free from defects in material and workmanship for a period of one 1 year from the date...

Page 21: ...This page intentionally left blank ...

Page 22: ...This page intentionally left blank ...

Page 23: ...This page intentionally left blank ...

Page 24: ...f 1 519 763 5069 Courriel info viqua com www viqua com 425 Clair Rd W Guelph Ontario Canadá N1L 1R1 t 1 519 763 1032 f 1 800 265 7246 solo EE UU y Canadá t 31 73 747 0144 solo Europa f 1 519 763 5069 correo electrónico info viqua com www viqua com 425 Clair Rd W Guelph Ontario Canada N1L 1R1 t 1 519 763 1032 f 1 800 265 7246 US and Canada only t 31 73 747 0144 Europe only f 1 519 763 5069 e mail i...