Installation

6

 

55

Section 3

Installation

3.1 UV Disinfection System

The disinfection system is designed to be mounted either horizontally or vertically at the point-of-use or point-of-entry 
depending on the specific flow rate of the unit. 

Note: The ideal installation is vertical with the lamp connector on top. This is to prevent water damage from occurring on the 
lamp pins and lamp connector.

The controller should be mounted either above or beside the chamber. Always mount controller horizontally to prevent 
moisture from running down cordage and causing a potential fire hazard. Drip loops in all cordage connected to 
controller is highly recommended. Refer to 

Figure 5

.

The complete water system, including any pressure or hot water tanks, must be sterilized before start up by flushing with 
chlorine (household bleach) to destroy any residual contamination. Refer to 

Section 3.2

.

The disinfection system is intended for indoor use only, do not install disinfection system where it may be exposed to the 
weather.

Install the disinfection system on cold water line only, before any branched lines. 

A 5 micron sediment filter must precede the disinfection system. Ideally, the disinfection system should be the last 
treatment the water receives before it reaches the faucet.

Procedure:

1.

Figure 2

 shows the installation of a typical disinfection system and the related components that may be used for the 

installation. The use of a by-pass assembly is recommended in case the system requires “off-line” maintenance. In this 
case, note the system requires a supplementary disinfection for the distribution system if any water is used during 
by-pass condition. In addition, during by-pass, the water will NOT be disinfected and a “DO NOT CONSUME THE 
WATER” tag should be physically installed on the by-pass assembly until such time as the system is sanitized and 
returned to service. For more information, refer to 

Section 3.2

. If the water is to be consumed while the system is off-line, 

the water must be boiled for twenty minutes prior to consumption.

C A U T I O N

Electronic controller must be connected to a Ground Fault Protected Circuit (GFCI) receptacle and the lamp connector ground wire connected to the 
stainless steel chamber.

Figure 2 

Figure 2 Disinfection System

Note:

 UV system should

be the final piece of
treatment equipment

 

Optional flow restrictor

Note:

 Mandatory for

NSF credited systems

Optional water

softener

To

drain

Optional by-pass

assembly

Optional by-pass

assembly

Optional
by-pass
assembly

Optional
solenoid

valve

Hot water pipes
Cold water pipes

Customer supplied

GFCI circuit to

match voltage

Water

meter

Main

water

shut-off

5 Micron

sediment

filter

Optional

carbon

filter

Optional
by-pass
assembly

Optional

drain

cock

Funcionamiento

5.2.3 Número total de días de funcionamiento

 Para obtener esta lectura, pulse dos veces seguidas el botón de reinicio del temporizador y siga los pasos que se 

describen en la 

Sección 5.1.3

, en relación al uso de esta función.

5.2.4 Fallo de lámpara (pantalla en blanco)

 Consulte la 

Sección 5.1.5

 para ver una explicación de esta función. 

Nota: En los sistemas VIQUA, el tono audible correspondiente al fallo de lámpara es una alarma continua, no la condición 
intermitente (1 segundo encendida, 1 segundo apagada) de los sistemas VIQUA básicos.

5.2.5 Salida de solenoide

El controlador VIQUA, en combinación con el monitor de intensidad UV, proporciona un conector de salida de solenoide 
IEC activado (voltaje de línea). (Nota: no es un contacto seco) Esta salida de solenoide está protegida por un fusible 
aislado de 2 amperios sustituible. La conexión de esta salida al solenoide se puede realizar con el cable de alimentación 
de solenoide IEC PN 260135. Cuando el monitor de intensidad UV detecta que el agua no se está tratando de la forma 
adecuada e indica una intensidad de UV del 49 % o inferior, el relé interno se abre, impidiendo así que la alimentación de 
CA llegue hasta la válvula de solenoide, normalmente cerrada. La válvula permanecerá cerrada (sin alimentación) hasta 
que el nivel de UV suba por encima del 49 %, momento en el que el solenoide se abrirá, permitiendo así el paso del agua. 
(Para activar temporalmente el funcionamiento de esta salida de solenoide hasta las 12 horas, consulte las instrucciones 
de la 

Sección 5.2.1

).

Nota: Durante la derivación, no consuma el agua hasta que el sistema haya vuelto a un estado seguro.

5.2.6 Salida de 4-20 mA (opcional)

Para poder transmitir los datos de intensidad UV a una ubicación remota mediante una señal de 4-20 mA, adquiera un 
cable en "Y" (PN 260134) de su distribuidor. El cable en "Y" incluye 20 metros (65') de cable para la señal de 4-20 mA. 

Figura 6 Instalación del solenoide

Válvula de 

solenoide opcional

Summary of Contents for VH200

Page 1: ...f 1 519 763 5069 Courriel info viqua com www viqua com 425 Clair Rd W Guelph Ontario Canadá N1L 1R1 t 1 519 763 1032 f 1 800 265 7246 solo EE UU y Canadá t 31 73 747 0144 solo Europa f 1 519 763 5069 correo electrónico info viqua com www viqua com 425 Clair Rd W Guelph Ontario Canada N1L 1R1 t 1 519 763 1032 f 1 800 265 7246 US and Canada only t 31 73 747 0144 Europe only f 1 519 763 5069 e mail i...

Page 2: ...reclamación bajo garantía necesitará su factura original o bien deberá haber completado y enviado su tarjeta de registro de producto por correo postal o en línea Cobertura específica de la garantía La cobertura de la garantía es específica de la gama de productos de VIQUA La cobertura de la garantía está sujeta a las condiciones y limitaciones establecidas en la sección Condiciones y limitaciones ...

Page 3: ...l if you are in doubt as to whether the outlet is properly grounded DO NOT modify the plug provided with this system if it does not fit in the outlet have a proper outlet installed by a qualified electrician DO NOT use any type of adapter with this system GROUND FAULT CIRCUIT INTERRUPTER PROTECTION To comply with the National Electrical Code NFPA 70 and to provide additional protection from the ri...

Page 4: ...r yank cord to pull plug from outlet Always grasp the plug and pull to disconnect SYSTEM PROTECTION To protect your Controller a UL1449 certified or equivalent transient voltage surge suppressor is strongly recommended The UV lamp in this system conforms to the applicable provisions of the Code of Federal Regulations CFR requirements including Title 21 Chapter 1 Subchapter J Radiological Health Re...

Page 5: ...uales se llene de cloro lejía antes de que el agua salga del sistema UV Para funcionar de manera eficaz el sistema de desinfección debe tener un sistema de distribución libre de bacterias Consultar la Sección 3 2 Posible entrada de sedimentos a través del pre filtro Analice el agua de suministro para descartar la turbiedad es posible que necesite un filtrado escalonado para recoger todos los sedim...

Page 6: ...fection System Note UV system should be the final piece of treatment equipment Optional flow restrictor Note Mandatory for NSF credited systems Optional water softener To drain Optional by pass assembly Optional by pass assembly Optional by pass assembly Optional solenoid valve Hot water pipes Cold water pipes Customer supplied GFCI circuit to match voltage Water meter Main water shut off 5 Micron...

Page 7: ...2 segundos durante las condiciones de bajo nivel de UV Nota Niveles de UV de APLAZAMIENTO para aplazar temporalmente la alarma acústica y reactivar la válvula de solenoide si se ha instalado durante una alarma de nivel bajo de UV mantenga pulsado el botón de reinicio del temporizador durante cinco segundos Con esto se silenciará la condición de alarma acústica y se activará la salida de solenoide ...

Page 8: ... que sustituir la lámpara de 365 días a 1 día Al llegar a 0 días el controlador mostrará y emitirá un chirrido intermitente 1 segundo encendido 5 segundos apagado para indicar la necesidad de cambiar la lámpara 5 1 2 Interpretación del código A3 APLAZAMIENTO cuando aparece en la pantalla LED el mensaje de fin de la vida útil de la lámpara o A3 la alarma acústica se puede aplazar hasta 4 veces sepa...

Page 9: ...are present Replace the UV lamp annually or biennially if seasonal home use to ensure maximum disinfection Always drain the chamber when closing a seasonal home or leaving the unit in an area subject to freezing temperatures N O T I C E Reset lamp life timer after lamp replacement Refer to Section 5 1 3 Refer to www lamprecycle org for lamp disposal Do not use water during replacement of UV lamp 5...

Page 10: ...ED display will read once again 10 51 Maintenance Procedimiento Nota Tras reemplazar la lámpara UV o la vaina tubular de cuarzo realice el procedimiento de desinfección y consulte la Sección 3 2 1 Drene la cámara usando el puerto de drenaje 2 1 2 3 Quite la tuerca de retención el muelle flotante y la junta tórica de la parte inferior 3 1 2 Quite la tuerca de retención y la junta tórica de la parte...

Page 11: ... la vaina tubular de la lámpara Esta capa debe retirarse porque reduce la cantidad de luz UV que llega al agua reduciendo de este modo el rendimiento de la desinfección Si la vaina tubular no puede limpiarse deberá reemplazarse por otra Requisitos previos Cortar el suministro de agua y drenar todas las líneas Quitar la lámpara UV Consulte Sección 4 1 1 Corte la línea de agua de la cámara y libere ...

Page 12: ...or de intensidad UV de 254 nm tenga en cuenta que la introducción de la solución de lejía requerida para efectuar la desinfección provocará una condición temporal de bajo nivel de UV Esto se debe a que la lejía enturbia físicamente el agua no potable Una vez que la lejía circule por el sistema la condición de alarma volverá al estado normal Durante el proceso de desinfección la condición de alarma...

Page 13: ...optimum protection against microbiological contamination in water DO NOT disregard the warning signals The best way to ensure optimum UV performance is to have the water microbiologically tested by a recognized testing agency on a regular basis Instalación 5 Instale la lámpara UV Consulte Sección 4 1 6 Cuando se hayan realizado todas las conexiones de tuberías conecte el suministro de agua lentame...

Page 14: ...tes the UV level is still within a safe level however cleaning or lamp sleeve replacement may soon be required to Indicates the UV level is nearing the point of unsafe UV intensity UV system should be immediately serviced Indicates the UV level has now reached a level that is unsafe At this level the water should not be consumed The system water supply should be examined to determine the reason fo...

Page 15: ...oque un peligro de incendio Es muy recomendable usar bucles de goteo en los cables conectados al controlador Consulte Figura 5 El sistema de agua completo incluidos los depósitos de presión o agua caliente se deben esterilizar antes de la puesta en marcha Para ello enjuague con cloro lejía doméstica para destruir toda contaminación residual Consulte Sección 3 2 El sistema de desinfección está dise...

Page 16: ...tem should not be installed on a circuit which is incorporated into a light switch Lamp Failure Alarm on New Lamp Loose connection between lamp and connector Disconnect lamp from connector and reconnect ensuring that a tight fit is accomplished Moisture build up in connector may keep lamp and connector from making a solid connection Eliminate chance of any moisture getting to the connector and or ...

Page 17: ...l debido la exposición a rayos UV es recomendable usar accesorios metálicos y canalización de cobre de al menos 25 4 cm en la salida de la cámara UV AVISO La lámpara UV en el interior del sistema de desinfección tiene una clasificación nominal con una vida eficaz de aproximadamente 9000 horas Para garantizar una protección continua reemplace la lámpara UV una vez al año Los niños no deben usar el ...

Page 18: ...surización segura Este símbolo indica que se requiere el uso de botas de seguridad Este símbolo indica que el sistema está bajo presión Este símbolo indica que el operador debe leer toda la documentación disponible para realizar los procedimientos requeridos Este símbolo indica que existe peligro de exposición a rayos UV Se debe usar protección adecuada Este símbolo indica que el fontanero debe us...

Page 19: ...rcionarle años de funcionamiento sin problemas con un mínimo mantenimiento para proteger su agua potable contra contaminantes microbiológicos Para garantizar la continua desinfección del agua las lámparas UV se deben reemplazar cada año por repuestos VIQUA de fábrica Las lámparas VIQUA son fruto de un extenso desarrollo que ha resultado en una plataforma de desinfección altamente eficaz con un ren...

Page 20: ...e date of purchase During this time VIQUA will repair or replace at its option any defective parts covered by the warranty Please return the defective part to your dealer who will process your claim One Year Limited Warranty for UV lamps Sleeves and UV Sensors VIQUA warrants UV lamps sleeves and UV sensors to be free from defects in material and workmanship for a period of one 1 year from the date...

Page 21: ...This page intentionally left blank ...

Page 22: ...This page intentionally left blank ...

Page 23: ...This page intentionally left blank ...

Page 24: ...f 1 519 763 5069 Courriel info viqua com www viqua com 425 Clair Rd W Guelph Ontario Canadá N1L 1R1 t 1 519 763 1032 f 1 800 265 7246 solo EE UU y Canadá t 31 73 747 0144 solo Europa f 1 519 763 5069 correo electrónico info viqua com www viqua com 425 Clair Rd W Guelph Ontario Canada N1L 1R1 t 1 519 763 1032 f 1 800 265 7246 US and Canada only t 31 73 747 0144 Europe only f 1 519 763 5069 e mail i...

Reviews: