background image

                                                       

 

                       

 

13 

fan running 
but 
condensing 
unit not 
running

 

b.  Failed components 
 
c.  Low refrigerant 
 

 

 

b.  Check  start  relay,  start  capacitor, 

overload protector, compressor. 

c.  Call service 
 

13.Temperature 

low 

a.  Low temperature setting 
b.  Low ambient temperature 
c.  Air probe fault 
 
d.  Temperature controller fault 
 

a.  Raise the setting 
b.  Move to another location 
c.  Check probe connections or change 

a new one 

d.  Change a new one 
 

14.Evaporator 

freezing up

 

a.  Evaporator air flow restriction 
b.  Condenser air flow restriction 
c.  Not stopping due to air leak, high 

ambient  temperature  or  low 
temperature setting 

d.  Defective controller or probe 
e.  Low ambient temperature 
f.  Initially  working  then  stopping, 

moisture in the system 

g.  Refrigerant low or leaking 
h.  Expansion valve blockage 

a.  Check for fans and CFM 
b.  Check for fans and CFM 
c.  Check  for  seal,  door  opening, 

ambient 

temperature 

and 

temperature setting 

d.  Check for controller and probe 
e.  Change defrost cycle 
f.  Call service 
 
g.  Call service 
h.  Call service  

15.Water leak

 

a.  Air leak in the wine cellar causing 

excessive condensate 

b.  High  humidity  causing  excessive 

condensate 

c.  Evaporator air flow restriction 
d.  Drain  restricted  or  unit  not  level, 

and water overflowing 

e.  Drip tray leak (No water overflow 

but leak)  

a.  Check for air leak 
 
b.  Use drain line 

 

c.  Check supply air flow or air TD 
d.  Clean the drip tray and drain line 
 
e.  Seal the leak using silicone sealant 
 

16.Excessive 

condensate 
in wine 
cellar

 

a.  Air leak in the wine cellar causing 

excessive condensate 

b.  High  humidity  causing  excessive 

condensate 

c.  Drain restricted 

 

a.  Check for any air leak 
 
b.  Use drain line 
 
c.  Clean the drip tray and drain line 

17.Condensate 

inside ducts 

a.  Drain line restricted  
b.  Continually running not stopping 
  
c.  Too cold supply air  
 

a.  Check for drain 
b.  raise 

temperature 

setting 

or 

increase defrost cycle 

c.  Increase 

air 

flow 

or 

raise 

temperature setting 

18.Condensate 

outside  
ducts 

a.  Duct not insulated  
b.  High humidity  
c.  Too cold supply air 
 

a.  Check for insulation 
b.  Use dehumidifier 
c.  Increase 

air 

flow 

or 

raise 

temperature setting   

19.Circuit 

tripping

 

a.  Incorrect fuse or breaker 
b.  Incorrect wirings 
c.  Failed components 

a.  Check for proper fuse or breaker 
b.  Check for wirings and connections 
c.  Call service  

20.Noisy 

operation

 

a.  Mounting area not firm 
b.  Loose parts 
 
 
c.  Compressor  overloaded  due  to 

a.  Add support to improve installation 
b.  Check 

fan 

blades, 

bearings, 

washers,  tubing  contact  and  loose 
screws. 

c.  Check for airflow 

Summary of Contents for WINE-MATE WM-2520SSH

Page 1: ...www winemate com www winemate com Duct Split Cooling System Installation Operation Care Manual WM 2520SSH WM 4520SSH WM 6520SSH WM 8520SSH www vinotemp com www vinotemp com...

Page 2: ...d and save these instructions these instructions Important Safety Information WARNING Do not use a ground fault interrupter GFI A dedicated 10 AMP circuit for WM 2520 4520SSH and 15 AMP for WM 6520 85...

Page 3: ...le of Contents Cellar Construction 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 15 Electrical Wirings 26 Customer Support 30 Warran...

Page 4: ...rature surrounding the enclosure shall not exceed the temperature of the cellar by more than 25 F No cellar wall shall receive direct sun or strong wind Lighting shall be of low wattage with a timer t...

Page 5: ...d away from the evaporator unit 50 ft so that noise and compressor vibration are isolated SSH evaporator units are designed to provide chilled air to wine a cellar through ducts and can be located up...

Page 6: ...2520SSH WM 252SFCH 22 5x15 875 x14 375 11 WM 252SCU 18x14x12 2100 180 230 R134a 220V 50Hz 0 5A 220V 50Hz 3A 35 40 WM 4520SSH WM 452SFCH 25 125x22 875 x16 375 18 WM 452SCU 18x14x12 3700 320 900 R134a 2...

Page 7: ...lock unlock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock th...

Page 8: ...e temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of bottles temperature setting and surrou...

Page 9: ...be faulty min 30 CF temperature unit F C F Fahrenheit rES display resolution in integer dLy temperature display delay min 1 ot probe calibration 0 LS minimum set point 50 US maximum set point 65 idF d...

Page 10: ...te hygrometer to monitor the humidity 10 How to set alarm call 1 Speech notice will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the set point Set 2 In order to t...

Page 11: ...lean the condenser coil regularly Coil may need to be cleaned at least every 6 months Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty 2 Condensate Removing...

Page 12: ...mperature is mainly controlled by the average air temperature If the set point is 55 F with the differential 4F the cooling unit turns on at 59 F of air temperature It may be higher than 59 F if it is...

Page 13: ...ide and leave minimum 1 foot clearance for the ambient air intake side c Check for excessive size d Check for installation location e Clean condenser f Check for fan and air short circulation 8 Conden...

Page 14: ...flow restriction d Drain restricted or unit not level and water overflowing e Drip tray leak No water overflow but leak a Check for air leak b Use drain line c Check supply air flow or air TD d Clean...

Page 15: ...14 high ambient temperatures or airflow restriction d Defective components d Call service for checking internal loose inadequate lubrication and incorrect wirings...

Page 16: ...and electrical codes The condensing unit and evaporator unit are connected by a liquid line and an insulated suction line that are supplied by the installer These lines must be properly sized for the...

Page 17: ...16 CAUTION Liquid and suction line locations may differ from what are shown here please check on the units for proper installation Fig 3 WM 252 852SFCH Evaporator Unit...

Page 18: ...17 Fig 4 WM 252 452SCU Condensing Unit Fig 5 WM 652 852SCU Condensing Unit...

Page 19: ...ditional wires are needed 18 gauge wires may be used to extend the air probe 4 If the air probe is installed in a return duct the evaporator fans shall be running all the time Meanwhile due to the tem...

Page 20: ...ng unit will build up and the cooling system will not operate properly 2 Condensing unit shall be elevated to avoid possible flooding and shaded from direct sun It shall not be exposed to temperatures...

Page 21: ...e control if applicable for pump down Suction pressure setting Cut out 5 psig Cut in 25 psig Differential 20 psig Head pressure setting Cut out 230 psig Cut in 150 psig Differential 80 psig It may nee...

Page 22: ...Head pressure setting Cut in 170 psig Cut out 110 psig Differential 60 psig It closes on rise of pressure It may need to adjust the setting in the field to avoid fan short cycle Fig 13 Condenser Fan...

Page 23: ...0 ft or the line set exceeds 75 ft use both inverted U trap and suction accumulator 3 If the condensing unit is located more than 10 ft above the evaporator unit use U trap to aid oil returning to the...

Page 24: ...nob to the lowest speed position then rotate the setting located on the side or front clockwise to decrease the minimum speed or counter clockwise to increase the minimum speed The minimum speed shoul...

Page 25: ...pressure Low superheat and high subcooling 4 High to normal suction pressure and high head pressure Low subcooling 5 High suction pressure and high head pressure Low superheat and low subcooling 6 Hi...

Page 26: ...2 Expansion valve restricted 13 Both evaporator and condenser restricted liquid and suction lines connected wrong 14 Liquid line restricted before receiver 15 Condenser restricted 11 Condensing Unit T...

Page 27: ...are the field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the co...

Page 28: ...27 Fig 17 WM 6520SSH Electrical Wiring Diagram Fig 18 WM 8520SSH Electrical Wiring Diagram...

Page 29: ...28 Fig 19 Low Ambient Temperature WM 2520 4520SSH LA Electrical Wiring Diagram Fig 20 Low Ambient Temperature WM 6520SSH LA Electrical Wiring Diagram...

Page 30: ...29 Fig 21 Low Ambient Temperature WM 8520SSH LA Electrical Wiring Diagram...

Page 31: ...0 Customer Support If you need further assistance please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp co...

Page 32: ...and is in lieu of all other warranties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any...

Page 33: ...NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidelines VINOTEMP cannot warrant its units to properly...

Reviews: