Fig. 10 Water Regulating Valve 

 

 

2) 

Checking pressure control settings 

 

Suction pressure setting: Cut out=5 psig; Cut in=25 psig; Differential=20 psig 
Head pressure setting: Cut out=230 psig; Cut in=150 psig; Differential=80 psig It 
is necessary to adjust the setting in the field to reach the correct cycle time. 

 

Fig. 11 Adjustable Pressure Control 

 

 

3) 

A  fan  speed  control  may  be  used  to  adjust  the  air  flow  to  achieve  the 
specified CFM. The fan will run from the minimum speed to full speed with 
the control  knob  at  the  lowest  and  highest  speed  position.  To  adjust  the 
minimum speed, turn control knob to the lowest speed position, then rotate 
the setting (located on the side or front) clockwise to decrease the minimum 
speed or counter-clockwise to increase the minimum speed. The minimum 
speed should be adjusted until it supplies the required CFM

Summary of Contents for WINE-MATE WM-2500SSWWC

Page 1: ...tem Operation Care Installation Manual WM 2500SSWWC WM 4500SSWWC www vinotemp com Read and save these instructions Vinotemp International Corp 732 South Racetrack Road Henderson NV 89015 Tel 800 777 V...

Page 2: ...cle installed by a qualified electrician DO NOT UNDER ANY CIRCUMSTANCES REMOVE THE POWER CORD GROUNDING PRONG A separate adequately fused and grounded circuit should be available for this appliance Do...

Page 3: ...2 Table of Contents Cellar Construction Guide 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 25 Warranty 26...

Page 4: ...temperature surrounding the cellar shall not exceed the temperature of the cellar by more than 25 F No cellar walls shall receive direct sun or strong wind Lighting shall be of low wattage with a tim...

Page 5: ...e installed inside a wine rack or between two wall studs making them an idea choice for wine cabinets or small wine roomsas built in installation SSWWC cooling systems consist of a remote condensing u...

Page 6: ...F condensing unit ambient temperature with R13 interior and R19 exterior insulations Higher ambient temperatures or lower insulations will cause reducing capacity and the cellar temperature may not b...

Page 7: ...ock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys pr...

Page 8: ...nstrument 2 Temperature Setting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of...

Page 9: ...e regulation differential 4 AC anti short cycle delay min 10 hidden Con compress on with probe faulty min 15 CoF compress off with probe faulty min 30 CF temperature unit F C F Fahrenheit rES display...

Page 10: ...lative humidity Use a separate hygrometer to monitor the humidity 10 How to set alarm call 1 Speech notice will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the s...

Page 11: ...aning To clear any sediment that may accumulate the water regulating valve maybe manually flushed Insert screwdrivers under both sides of the valve spring guide and lift upwardsto flush 2 Condensate R...

Page 12: ...the cooling unit turns on at 59 F of air temperature It may be higher than 59 F if it is in anti short cycle or defrost and turns off at 55 F of air temperature The average air temperature is 57 F and...

Page 13: ...otector compressor c Call service 11 Temperature low a Low temperature setting b Low ambient temperature c Air probe fault d Temperature controller fault a Raise the setting b Move to another location...

Page 14: ...ion b Use dehumidifier c Increase air flow or raise temperature setting 17 Circuit tripping a Incorrect fuse or breaker b Incorrect wirings c Failed components a Check for proper fuse or breaker b Che...

Page 15: ...efrigeration technician has properly installed the system Proper installation is critical Vinotemp can only warrant the quality of the components The installation and proper operation of the system mu...

Page 16: ...earances for electrical wiring and refrigeration piping Model No Evap Unit W x D x H x H1 Cond Unit L x W x H Electrical Rating Evap Unit Cond Unit Min Circuit Ampacity Weight lb Evap Unit Cond Unit W...

Page 17: ...16 Fig 4 WM 25 45SFCW Evaporator Unit Fig 5 WM 250 450SCUR WC Condensing Unit...

Page 18: ...side and air return on the bottom side It can be installed inside the wine racks 2 Air supply shall be unobstructed minimum 12 air return shall be unobstructed minimum 6 3 A grille can be used to cov...

Page 19: ...alve must be used to reduce water pressure 4 Service valve operation 5 Refrigeration Piping and Leak Testing NOTE The line connector sizes of liquid filter and indicator the valve connector sizes of c...

Page 20: ...oil returning to the compressor 5 Complete pipe brazing check solenoid valve and expansion valve restrictions and perform leak testing 6 Hook up the drain line and check if water drains 6 Water Piping...

Page 21: ...ld high or low pressure hose to the discharge or suctionvalve and connect it to a vacuum pump 3 Open the manifold high and low pressure valves to evacuate the system 4 Close the manifold high and low...

Page 22: ...stable Pressure Control 3 A fan speed control may be used to adjust the air flow to achieve the specified CFM The fan will run from the minimum speed to full speed with thecontrol knob at the lowest a...

Page 23: ...8 Again you must verify if the superheat at the evaporator unit is 9 18 F at55 F 65 F wine cellar temperatures 9 If the superheat is high check the subcooling first to see if the refrigerant charge is...

Page 24: ...Low suction pressure and low head pressure Normal to high superheat and low subcooling 16 Low suction pressure and low head pressure Low superheat and low subcooling 17 Low suction pressure and low to...

Page 25: ...e and high head pressure High superheat and high subcooling 14 low to normal suction pressure and high head pressure Normal to high superheat and high subcooling and suction lines connected wrong 15 L...

Page 26: ...components 4 Low pressure switch shutting downthe system 5 high pressure switch shutting downthe system 1 Check for proper voltage 2 Check all wirings and connections 3 Check start relay start capaci...

Page 27: ...e field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the condensi...

Page 28: ...lied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products shall void this war...

Page 29: ...G BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidelines VINOTEMP cannot warrant its units to prop...