-17-
Fig. 5 WM-Liquid Filter
Fig. 6 WM-Liquid Indicator
2. Temperature Controller and Air Probe Location
1) The air probe shall be located in the wine cellar 5 ft above the floor or the air
return area.
3. Evaporator Unit Location
1)
The WM15~45SFCW evaporator units shall be installed for wall mount with
the air supply on the top side and air return on the bottom side. It can be
installed inside the wine racks.
2)
Air supply shall be unobstructed minimum
12”; air return shall be
unobstructed
minimum 6”.
3)
A grille can be used to cover the supply and return with 0~2”
clearance. A 2-3 ft long duct can be added.
4)
There is a gravity drain system, so the unit shall be installed level or
with a slight slope downward the drain connection and the drain line
shall be installed slope down toward the drain. If rise-up is necessary,
a condensation pump must be used.