Vinopro BU-22 Service Manual Download Page 9

 

15

 

 

    Evaporator Ice-Up                                                   

 

Problem

 

Possible Cause

 

Solutions 

1.Ice is built-up on 
evaporator 

1.Door is damaged or left open too long, too 
much warmer/cooler air rushes into inner 
cabinet from outside; 

1.If Door is damaged, replace it with new 
one; 

2.Always close door tightly immediately 
after opened; 

 

1.Gasket is damaged or distorted a little, too 
much warmer/cooler air rushes into inner 
cabinet from outside; 

1.If Gasket is damaged, replace it with 
new one; 
2. If Gasket is just a little distorted, Pls. 
use a Hair dryer to heat distorted area up 
gently until all gaps disappeared.

 (Fig.18)

 

2. Fan will be blocked, 
even broken if Ice too 
much. 

Ice too much inside. 

Replace Fan with new one 

(Fig.13), (Fig.14) 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

  Temperature Unstable                                                      

 

Problem

 

Possible Cause

 

Solutions 

Temperature Unstable 

Cooling Fan does not work, it is damaged or 
broken 

Replace Fan with new one 

(Figure.14), (Figure.14-1) 

 
 
 
 
 

Gasket

Hair Dryer

 

16

 

 

   

Control System Faults                                                             

 Temp. Sensor Fault 

● 

After plugged, pls. check if temperature displayed is same as actual temperature detected in inner cabinet, if not, 

pls. disassemble Sensor 

(Figure 5 & Figure 9

) and check if Sensor Connector is loose, If not, that indicate Sensor 

is broken, pls. replace it with new one. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

T1

(

Temp.Sensor)

Power PCB

Cooling Fan

Control PCB

PCB Bracket

PCB Box

T1

(

Temp.Sensor)

Discharge Tube

(Lower Pressure)

Solder Joint

Capillary

Solder Joint

Summary of Contents for BU-22

Page 1: ...Machine 3 Gas Meter 4 Temp Meter CONTENTS Cooling System Fault Troubleshooting P1 How to re charge Refrigerant P2 Test After Repairing P2 Baffle Board and Control Box Disassembly P3 Solder Joints Pos...

Page 2: ...rge Refrigerant No YES Yes Check Rubber Foot Mounting Screw and Capillary Tube YES No Disassemble and Replace faulty part as below mentioned How to re charge Refrigerant R600a Step 1 Extract vacuum fr...

Page 3: ...Screw Screw Screw Screw A A B B D C D C AScrew C Screw B Screw Step 4 Pull Control Box out about 70mm away in Horizontal direction and unplug terminals of Power PCB carefully Take Control Box out Fig...

Page 4: ...ssure Solder Joint Evaporator Stopper Shelf Step 2 Unscrew the 5 screws No 1 5 on Separator Board Cover one by one Figure 8 Step 3 Pull Baffle Board out Caution Unplug Fan Connector carefully before p...

Page 5: ...as following figure and loose the 2 screws No 3 4 a little about 2mm away Figure 10 1 B A Screw at back of PCB Box D C Screw Phillips Screw Driver Step 5 Pull Control Box put Figure 10 2 Caution Unplu...

Page 6: ...ndenser Solder Joint I Suction Tube Low Pressure Tube Solder Joint J Discharge Tube High Pressure Tube Solder Joint K Connection Tube 3 Solder Joint 2 For BU 58 Figure 13 A Evaporator Solder Joint B C...

Page 7: ...appened caused by following reasons a Fan Shaft is broken b Fan running unstable due to part abased badly over time Solutions Replace faulty Fan as following steps Evaporator Cooling Fan replace Figur...

Page 8: ...Evaporator too far 1 Re Insert Capillary Tube into Evaporator with depth less than 15mm Re solder it and wrap it with Shock absorbing Clay 2 Re do vacuum extraction and re charge Refrigerant Page 2 2...

Page 9: ...ared Fig 18 2 Fan will be blocked even broken if Ice too much Ice too much inside Replace Fan with new one Fig 13 Fig 14 Temperature Unstable Problem Possible Cause Solutions Temperature Unstable Cool...

Page 10: ...es Figure 1 Figure 7 Step 2 Remove Baffle Board and Control Box Figure 5 Figure 9 Step3 Unplug all Terminal of Fan and Temp Senor Figure 5 Figure 9 Step 3 Unscrew Screws of Temp Senor Remove Temp Seno...

Page 11: ...ep 4 Remove Control PCB and Replace it with new one Figure 21 Terminals Screws 2pcs Control PCB Bracket Control PCB Phillips Screwdriver Terminals Control PCB Bracket Control PCB Snaps Control PCB Pow...

Page 12: ...minals For 7 Bottles Screws 2pcs Washer Hex Nut Transformer Terminals For 19 Bottles Screws 2pcs Washer Hex Nut Transformer Connector Position Control PCB Figure 24 Connector Position Power PCB Figure...

Page 13: ...k Absorbing Rubber Foot Bushing Hex Nut Spring Washer Flat Washer Compressor Bracket Clip Spring Terminal Cover Start Relay Overload Protector Compressor For 7 Bottles LED Light Replace Warning Unplug...

Reviews: