Vinopro BU-22 Service Manual Download Page 2

 

 

 

  Cooling System Fault                                                  

■ 

Troubleshooting

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

Is Compressor current same as data marked on Rated Label? 

1. Cut off Discharge Tube and Service Tube,; 
2. Charge 0.8

1MPa High-pressure Nitrogen. 

Does air flow feel? 
Note

It is not allowed to run the unit too long after 

tubes cut off, in case of humidity air absorbed by 
Compressor.

 

No 

No 

I

s Refrigerant enough, 

not less than 90% of data 

marked on Rated Label 

Compressor itself is 
broken, replace is 
necessary. 

1.Condenser Coil 
or 

Anti-dew 

Tube is 

choked. 

2. Condenser, 
Evaporator, Dry 
Filter is broken.

 

The unit is 
beyond repair, it 
should be 
scrapped.

Will the Wine Cooler reach 

5

℃? (

after continuously running for 3hrs at ambient 32

℃)

 

Check Cooling System   

No 

YES 

Cooling System works 
well. 

 

Visually inspect Fans, PCB, Temp. Senor and PTC Heater, is all OK? 

No 

Disassemble and Replace 

faulty part as below mentioned. 

Is Compressor running with unusual noise or 
vibration? 

Is Start Relay and Overload Protector OK? 

No 

Disassemble and 

Replace faulty part as 

below mentioned. 

YES

YES 

No 

Replace faulty 
part. 

3. Anti-dew 

Tube leaks

 

 

Re-solder tube or 
replace faulty part. 

Restart Compressor, 

Does it work well? 

Re-charge 
Refrigerant  

No 

YES 

Yes 

Check Rubber Foot, Mounting 

Screw and Capillary Tube. 

YES 

No 

Disassemble and Replace 

faulty part as below mentioned. 

 

 

 

■ 

How to re-charge Refrigerant (R600a): 

Step 1 Extract vacuum from Suction Tube (Low-pressure Tube) and Discharge Tube (Hi-pressure Tube) at the same 

time, pls.refer to Figure 10,11,12.for location of tubes and solder joints. 

Step 2. Vacuum extraction will take 20min with pressure less than 

100Pa

Step3 . Re-solder Service Tube of Dry Filter under vacuum extracting condition; 
Step 4 Re-charge Refrigerant into Service Tube of Suction, Refrigerant weight should be same as the data marked 

on Rated Label. 

Step 5. Re-solder Service Tube of Suction Tube. 

■ 

Test After Repairing: 

After repairing and run the unit for 3 hours at ambient temp. 32

, if   

1.actual temp. of inner cabinet is same as temp. set, and 
2.the compressor will stop after unplugged with actual temp.of inner cabinet 2.5

  less than temp.set, and 

3.the compressor will restart after plugged with actual temp.of inner cabinet 2.5

  more than temp.set. 

then the cooling system can be confirmed in normal working condition. 

Remark: if necessary, pls. record actual term. of inner cabinet by a temp. meter.

 

■ 

Baffle Board and Control Box Disassembly

                 

1.For BU-22   

Step 1: Open door fully (180

O

), Lift up Chrome Shelf and pull it outwards one by one 

(Figure 1)

;

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for BU-22

Page 1: ...Machine 3 Gas Meter 4 Temp Meter CONTENTS Cooling System Fault Troubleshooting P1 How to re charge Refrigerant P2 Test After Repairing P2 Baffle Board and Control Box Disassembly P3 Solder Joints Pos...

Page 2: ...rge Refrigerant No YES Yes Check Rubber Foot Mounting Screw and Capillary Tube YES No Disassemble and Replace faulty part as below mentioned How to re charge Refrigerant R600a Step 1 Extract vacuum fr...

Page 3: ...Screw Screw Screw Screw A A B B D C D C AScrew C Screw B Screw Step 4 Pull Control Box out about 70mm away in Horizontal direction and unplug terminals of Power PCB carefully Take Control Box out Fig...

Page 4: ...ssure Solder Joint Evaporator Stopper Shelf Step 2 Unscrew the 5 screws No 1 5 on Separator Board Cover one by one Figure 8 Step 3 Pull Baffle Board out Caution Unplug Fan Connector carefully before p...

Page 5: ...as following figure and loose the 2 screws No 3 4 a little about 2mm away Figure 10 1 B A Screw at back of PCB Box D C Screw Phillips Screw Driver Step 5 Pull Control Box put Figure 10 2 Caution Unplu...

Page 6: ...ndenser Solder Joint I Suction Tube Low Pressure Tube Solder Joint J Discharge Tube High Pressure Tube Solder Joint K Connection Tube 3 Solder Joint 2 For BU 58 Figure 13 A Evaporator Solder Joint B C...

Page 7: ...appened caused by following reasons a Fan Shaft is broken b Fan running unstable due to part abased badly over time Solutions Replace faulty Fan as following steps Evaporator Cooling Fan replace Figur...

Page 8: ...Evaporator too far 1 Re Insert Capillary Tube into Evaporator with depth less than 15mm Re solder it and wrap it with Shock absorbing Clay 2 Re do vacuum extraction and re charge Refrigerant Page 2 2...

Page 9: ...ared Fig 18 2 Fan will be blocked even broken if Ice too much Ice too much inside Replace Fan with new one Fig 13 Fig 14 Temperature Unstable Problem Possible Cause Solutions Temperature Unstable Cool...

Page 10: ...es Figure 1 Figure 7 Step 2 Remove Baffle Board and Control Box Figure 5 Figure 9 Step3 Unplug all Terminal of Fan and Temp Senor Figure 5 Figure 9 Step 3 Unscrew Screws of Temp Senor Remove Temp Seno...

Page 11: ...ep 4 Remove Control PCB and Replace it with new one Figure 21 Terminals Screws 2pcs Control PCB Bracket Control PCB Phillips Screwdriver Terminals Control PCB Bracket Control PCB Snaps Control PCB Pow...

Page 12: ...minals For 7 Bottles Screws 2pcs Washer Hex Nut Transformer Terminals For 19 Bottles Screws 2pcs Washer Hex Nut Transformer Connector Position Control PCB Figure 24 Connector Position Power PCB Figure...

Page 13: ...k Absorbing Rubber Foot Bushing Hex Nut Spring Washer Flat Washer Compressor Bracket Clip Spring Terminal Cover Start Relay Overload Protector Compressor For 7 Bottles LED Light Replace Warning Unplug...

Reviews: