INSTALLATION INSTRUCTIONS
Hydrosense Conventional Water Detection System
Document Part No. 3500012 REV03
Page | 4 of 27
Point Detection Floor Probe
Where a requirement exists for more localised
detection, such as HVAC plant, drip trays, elevator
shafts and storage areas a floor probe (HS-WLDP) can
be installed.
As with the cable the detection of moisture triggers an
alarm and is also monitored by the line fault circuit of
the control panel. Additionally the probe has an LED
indicator on top to identify exactly which probe has
been activated. Up to 20 detectors can be used in each
zone. The probe is simply plugged into the system
using the Junction Box.
Probe is fitted with a 1m cable.
If the distance from the junction box to where the probe needs to be mounted is more than 1m
then additional Extension leads are available in 1m (HY-ZB01), 3m (HY-ZB03) and 10m (HY-
ZB10) lengths.
Control and Indicating Equipment
of a Hydrosense
System
Control Panel (2 to 8 Zones)
HSCP Series
– This panel is available in 2, 4 and 8 zone
configurations. These are fully programmable and allow the
addition of Ancillary PCBs, repeater panels and a Mimic
Display.
Ancillary PCBs provide a means to extend Alarm, Fault,
coincidence and Zonal alarm volt free contacts to locations
remote from the control panel via a 2-core data bus
(RS485).
Hydrosense Mimic Panels
The Hydrosense Mimic Display uses flexible fibre optic guides to illuminate areas on a floor
plan. This provides a clear, geographical indication of the alarm activation enabling a speedy
identification of the source and location of the alarm.
This unique system dispenses completely with wiring and
enables indicators to be moved, removed or added without the
need for any wiring.
It can only be used with the HSCP range of panels.