INSTALLATION INSTRUCTIONS
Hydrosense Conventional Water Detection System
Document Part No. 3500012 REV03
Page | 5 of 27
System components:
Hydrowire (5 metre Length)
HYDW-05
Hydrowire (10 metre Length)
HYDW-10
End of Line Plug
HS-HWCI-EOL
Hydrowire Connection Box
HS-HWCI
Zone Extender (1 metre length)
HY-ZB01
Zone Extender (3 metre length)
HY-ZB03
Zone Extender (10 metre length)
HY-ZB10
Leader Cable (100m lengths)
HYLCB
Hydrowire / Leader Cable Fixing Clips
HY-FXSA
Batteries
Y7-12
System Options
Floor Mounted Probe
HS-WLDP
Probe Junction Box
HS-WLJB
Remote Indicator Unit
HY-WLRI-F
Remote Indicator with Surface Box
HY-WLRI-S
Voice Sounder
HSVS
White Sounder (Multi Tone)
892A4A0
Banshee Excel Lite - Combined
white sounder and blue strobe
8581800
Design & Planning
Design Notes
!
Water finds its own level so careful consideration must be given to slopes and dips in the
area to be protected.
!
Can the cable be installed to avoid doorways and traffic.
!
Floor probes can be used to protect wells, cavities or hollows.
!
Is the site occupied? If so, will the site require just visible alarms or will there be a need
for conventional or voice enhanced sounders?
!
Is a remote signalling device required?
!
How is the cable to be fixed to the floor? Are other services going to interfere with it?
!
Check with the building owner or manager for future plans or designs that may alter the
requirements or siting of the equipment.
!
Will the system require expansion? Give consideration to the possible addition of extra
zones.