INSTALLATION INSTRUCTIONS 
Hydrosense Conventional Water Detection System 

  

 

 

Document Part No. 3500012 REV03 

Page | 16 of 27 

 

C94 

ZONE 4 NON- SOUNDER MODE

 

C95 

ZONE 5 NON- SOUNDER MODE

 

C96 

ZONE 6 NON- SOUNDER MODE

 

C97 

ZONE 7 NON- SOUNDER MODE

 

C98 

ZONE 8 NON- SOUNDER MODE

 

 

 

 

A1 

ZONE 1 30 SECOND INPUT DELAY 

Zone needs to be triggered for 30 seconds 
continuously before an alarm is generated, 
programmable for each zone. 
(Prevents spurious alarms) 

A2 

ZONE 2 30 SECOND INPUT DELAY 

A3 

ZONE 3 30 SECOND INPUT DELAY 

A4 

ZONE 4 30 SECOND INPUT DELAY 

A5 

ZONE 5 30 SECOND INPUT DELAY 

A6 

ZONE 6 30 SECOND INPUT DELAY 

A7 

ZONE 7 30 SECOND INPUT DELAY 

A8 

ZONE 8 30 SECOND INPUT DELAY 

 

 

 

AD 

ACTIVATE ALARM DELAY 

 

DO NOT set option codes that are not listed in the above table, setting of unlisted options 
may have unintended and serious consequences. 
 
Once the required configuration options have been set, the Access level 3 switch 

must

 be 

returned to its normal position. The General fault indicator will remain lit if the Access level 3 
switch is not turned off. 

 
Internal Switches 
Watchdog Reset switch (W/Dog Reset) 

If for any reason the microprocessor in the control panel fails to carry out its operation 
correctly it will attempt to restart itself. This process is called a “watchdog” and the control 
panel must record and indicate these events. 
If a watchdog event occurs, the control panel will show the FAULT and SYSTEM FAULT 
LEDs on the front panel, the CPU fault LED inside the panel and the buzzer will sound. This 
fault can only be cleared by pressing the 

Watchdog Reset

 button on the PCB inside the 

control panel. This is a serious failure and the control panel buzzer will continue to sound 
until the watchdog activation is reset. 

 
Processor Reset  

Once started, the microprocessor controlling the panel should continue to run the panel 
continuously without interruption. If the microprocessor fails to run, it can be reset by 
operating the 

Processor Reset

 button on the PCB. 

This should not normally be necessary but should be done as a matter of course if the 
system is behaving abnormally. The system should resume normal operation within a couple 
of seconds of pressing the 

Processor Reset

 button. 

 
Write Enable 

Changes to the configuration as listed in table above require that the changes be stored in 
the control panel memory. To enable the memory to be written to it is necessary to operate 
the Write Enable slide switch. 

 

 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for hydrosense HSFPI-100

Page 1: ...Delivering a New Standard in Water Leak Detection Installation Instructions 3500012 Rev 03 June 2020 By www acornfiresecurity com www acornfiresecurity com...

Page 2: ...rowire Cable 6 System Installation Notes 6 Panel Installation 7 Safety 7 Panel Mounting 7 Removing the front facia 8 Control relays 12 Access level 2 configuration options 13 Access level 3 configurat...

Page 3: ...t will continuously monitor the potential hazards 24 hours a day and has the facility for 24 hours battery standby in the event of power failures Any water penetration detected will be signalled to a...

Page 4: ...d to the panel through the Connection Interface As soon as the cable detects moisture this will trigger an alarm For the cable to measure water on the surface then it is recommended that the cable is...

Page 5: ...eads are available in 1m HY ZB01 3m HY ZB03 and 10m HY ZB10 lengths Control and Indicating Equipment of a Hydrosense System Control Panel 2 to 8 Zones HSCP Series This panel is available in 2 4 and 8...

Page 6: ...0 Banshee Excel Lite Combined white sounder and blue strobe 8581800 Design Planning Design Notes Water finds its own level so careful consideration must be given to slopes and dips in the area to be p...

Page 7: ...tres Recommended pitch between cable for area protection 2 metres Minimum bend radius 150mm Note Do not mix probes and Hydrowire on the same zone System Installation Notes 1 Check design with the kit...

Page 8: ...from either 110V or 230V 50Hz mains supplies depending upon model and is of class 1 construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installatio...

Page 9: ...ional cable entry points are required all swarf and debris caused by drilling of additional cable entries must be cleared before power is applied to the panel Figure 1 G P E4 E4 5mm DIAMETER SCREWS FI...

Page 10: ...e must not exceed 25 ohms Wiring should enter the enclosure at the top of the panel using the knockouts provided and be formed tidily to the appropriate terminals leaving enough wire to ensure that th...

Page 11: ...nnect the RS485 bus and power to each repeater panel Up to 7 repeater panels may be connected and each board has terminals for the incoming cables and outgoing cables All except the last RS485 device...

Page 12: ...n panel wait for a few seconds and the main panel will show the addresses of the ancillary boards that were found on the display for instance o1 indicates that an ancillary board at address 1 has been...

Page 13: ...be exceeded under any circumstances Typically the Aux 24V output of the control panel is switched through these relays and used to control other systems Fault relay The fault relay is normally energis...

Page 14: ...end upon panel d1 8 Disable Zone 1 8 total number of zones will depend upon panel db Disable Sounders Ad Activate Alarm Delays t1 8 Test zone Selecting t1 through to t8 puts respective zone into test...

Page 15: ...e 6 Figure 6 Configuration options are simple to enter using the codes in Table 1 below When the control panel is at Access Level 3 the sub text of the Mode and Select buttons is used to enter a numbe...

Page 16: ...FROM DETECTOR DELAYED C34 ZONE 4 ALARM FROM DETECTOR DELAYED C35 ZONE 5 ALARM FROM DETECTOR DELAYED C36 ZONE 6 ALARM FROM DETECTOR DELAYED C37 ZONE 7 ALARM FROM DETECTOR DELAYED C38 ZONE 8 ALARM FROM...

Page 17: ...e control panel fails to carry out its operation correctly it will attempt to restart itself This process is called a watchdog and the control panel must record and indicate these events If a watchdog...

Page 18: ...equipment This LED indicates that fuse protecting the R0V output has operated and the rating of this output has been exceeded The fuse is a self resetting type and the supply will resume when the fau...

Page 19: ...two Hydrowires is no more than 2 metres For localised protection of sources of potential water leakage such as air conditioning and water filled radiators the distance between Hydrowires may be greate...

Page 20: ...e discarded It is advisable to leave the lid off the control panel until all testing is complete NOTE The Connection Interfaces cannot be daisy chained together only one Connection Interface can be co...

Page 21: ...e forefinger and thumb into a cup of tap water shaking off the excess drips and then gripping the Hydrowire firmly whilst rolling it slowly This should produce an alarm condition at the control panel...

Page 22: ...etection cable Part Number Description Quantity HSCP S 4 230 4 Zone Control panel 1 HYDW 10 Hydrowire cable 10m 8 HS HWCI EOL End Of Line Device 2 HS HWCI Hydrowire Connection Interface 2 HS WLDP Hydr...

Page 23: ...d installed on the last Junction box 2 Unplug the Floor Probe s and check that a Fault is reported 3 Remove power from the Control Panel Disconnect the Floor Probe s and store ready for installation 4...

Page 24: ...5mm2 2 core cable HYLCB to the Z and Z terminals at the control panel Figure 10 Floor Probe Remote Lamp Connection In some installations particularly in floor voids it is desirable to identify the are...

Page 25: ...oor Probe Testing 1 This is best achieved by wetting both of the brass contacts simultaneously with fresh water 2 This should produce an immediate reaction at the control panel the LED mounted on top...

Page 26: ...25 of 27 Probe Layout Figure 11 Part Number Description Quantity HSCP S 2 230 2 Zone Control panel 1 HS WLDP Hydrosense Floor Probe 20 HS WLJB Hydrosense Junction Box 20 HSVS Voice Sounder 1 Y7 12 7A...

Reviews: