INSTALLATION INSTRUCTIONS
Hydrosense Conventional Water Detection System
Document Part No. 3500012 REV03
Page | 13 of 27
Access level 2 configuration options
Turn enable keyswitch to get to access level 2.
OPERATION
Press Mode button until the required function as detailed below appears in the 7 segment
displays.
For Zonal tests or Disablements, press the Select button to scroll to the required zone
number then press enter. The “select” dot at the bottom of the display will flash to indicate a
test or disablement is active.
For sounder disablements and other functions, press the Select button until the required
function is displayed then press enter to activate that function. The “select” dot will flash to
confirm the setting as above.
[ t1 - 8]
Test Zone 1 – 8 (total number of zones will depend upon panel)
[ d1 - 8]
Disable Zone 1 – 8 (total number of zones will depend upon panel)
[ db]
Disable Sounders
[ Ad]
Activate Alarm Delays
[t1 - 8] Test zone
Selecting [t1] through to [t8] puts respective zone into test mode. Zones that are in test
mode shall automatically reset 3 seconds after they have operated. The Test Mode On and
zonal fault/test disablement indicators shall illuminate while any zone is in test mode.
[d1 – 8] Disable zone
Selecting [t1] through to [t8] disables the respective zone. Disabled zones shall not report
alarm or fault conditions. The General Disablement and zonal fault/test disablement
indicators shall illuminate while any zone is disabled.
[db] Disable Sounders
Selecting [db] will disable sounder outputs. The General Disablement and Sounder fault/
Disablement indicators shall illuminate whilst the sounders are disabled.
[Ad] Activate delays
Selecting [Ad] shall make delays configured by access level 3 options C00 to C09 active.