22
6. Web Front-end
The web front-end can be used to read out 01548´s actual device parameters (HTTP port, IP address, MAC address, …), to update its firmware and set (additional) Individual
Addresses for Tunneling . For identifying a certain 01548 in a KNX network, the Programming LED/Programming Mode can be remotely switched on and off without pressing
the on-device Programming Button .
To switch back from boot mode to normal operation it is necessary to run the firmware update procedure, then press abort, or wait for the 10 min timeout .
6.1 Protection of the 01548 Web Front-end
The web front-end can be used for remotely carrying out firmware updates, control functions and readout device settings . To guarantee full protection of an installation
the web front-end must be set to “not available” during normal runtime operation .
To use the remote functions of the web front-end when Security is activated, it must be set to “available having full functionality” .
Figure 18: ETS Parameter for Web Front-End Availability
When the web front-end is set to “only status info display”, remote control functions (Program Mode activation, Set Tunneling) and the update function are off . Only the
informational readout is available .
To ensure full protection of a secured installation the web front-end availability must be set to “web front-end not available” (default value) .
For reasons of efficient protection, it is strictly recommended not to use the “available having full functionality” option on a permanent basis .
6.2 Accessing the 01548 Web Front-end
There are three ways to access the 01548 web front-end . It can be accessed via Windows explorer directly, or by a web browser . For access via web browser either
the IP address or the MAC address, together with the HTTP port, have to be known . How to use IP address and MAC address with the browser´s URL bar is described
in the following .
For access via web browser the correct HTTP port must be used .
Factory default HTTP port is 8080 .
6.2.1 via Windows Explorer
Due to UPnP discovery, 01548 appears in the local network window . A double click on the 01548 device opens the web front-end in the standard web browser .
Figure 19: Windows Explorer showing 01548 (“KNX IP Secure Meda Coupler”)
Web Front-end