4. Operational Description

In KNX network installations, 01548 is used as KNX IP line/area coupler to couple KNX IP and KNX TP (see also chapter 2 .2 IP (Secure) Routing) . It can be used in the com-
mon way without activation of Security and in ETS projects where Security is set to active . After connecting to KNX TP, 01548 operates with its default settings . Setting a 
correct Individual Address is necessary . Only Individual Addresses x .y .0 are allowed .

4.1 IP Secure Router Application

When 01548 receives telegrams (for example during commissioning) that use Individual Addresses as destination addresses, it compares the Individual Addresses of 
the receiver with its own Individual Address and decides on that whether it has to route the telegrams or not .

When 01548 receives telegrams that use group addresses as destination addresses, it reacts in accordance with the parameter settings . During normal operation (with 
Group Telegram routing set to filter), 01548 only routes the telegrams whose group addresses are entered in the group filter table .

If a telegram is routed by 01548 without receiving the corresponding acknowledgement, i .e . due to a missing receiver or to a transmission error, the telegram will be 
repeated up to three times (depending on the ETS setting) . With the parameters „Repetitions if errors  . . .“, this function can be configured separately for each line and 
both kinds of telegrams . It is recommended to use the default parameter setting .

IP Router is designed for use in 10/100 BaseT networks compliant to IEEE802 .3 . The AutoSensing function sets the baud rate (10 Mbit or 100 Mbit) automatically . IP 
address can be received from a DHCP server . For this, the automatic assignment setting of the IP address can be set by ETS (“obtain an IP address automatically”) . If 
set so and no DHCP server is found, 01548 starts an AutoIP procedure and autonomously assigns the IP address . If 01548 is supposed to have a fixed IP address (as 
well as subnet mask and standard gateway) it can be set by ETS .

4.2 IP Network

01548 sends telegrams from/to the TP network to/from the IP network in accordance with the KNXnet/IP protocol specification . According to the default setting, IP 
telegrams are sent as IP Multicast to the IP address 224 .0 .23 .12 port 3671 . The Multicast IP address 224 .0 .23 .12 is the defined address for KNXnet/IP by KNX Associa-
tion in conjunction with the IANA . It is recommended to change this address only when it becomes necessary due to the existing network .

Important notes:
• All KNX IP devices that are intended to communicate with each other via IP must have the same IP multicast address .
• Multicast IP address 224 .0 .23 .12 may need to be changed in respect of the network type and of the network components´ settings .
• IGMP (Internet Group Management Protocol) is used for IP Routing and Discovery .
• If problems occur for IP address assignment, please ask your network administrator .
• According to the topology, Individual Addresses that are used for Tunneling channels always have to be assigned in the range of subline addresses . Detailed informa-

tion about additional Individual Addresses for (Secure) Tunneling can be found in chapter 5 .4 IP (Secure) Tunneling Address Assignment .

Operational Description

Summary of Contents for 0072031B45CB

Page 1: ...BUILDING AUTOMATION WELL CONTACT PLUS Installer manual 01548 KNX IP media coupler...

Page 2: ...2...

Page 3: ...11 4 3 KNX Network Installation 12 4 4 Adding Device Certificate 13 4 5 Programming 14 4 5 1 Programming of Individual Address and Application 14 4 5 2 IP Configuration 15 4 6 Special Functions 16 4...

Page 4: ...or troubleshooting The device is for KNXnet IP Secure Routing and Tunnelling and it is equipped with a dedicated QR code to be used with ETS version 5 5 and later during configuration The Secure Tunn...

Page 5: ...No telegram traffic 4 Telegram Traffic KNX TP Subline blinking green Telegram traffic extent indicated by blinking blinking red Transmission error BUSY NACK missing IACK off No telegram traffic 5 Grou...

Page 6: ...outing Table 4 LED Status Display for Factory Reset after first Function Button Press Number LED Color Comment 1 State IP orange Lights red if not connected 01548 Traffic Function IP TP ROUTER IP KNX...

Page 7: ...1548 X Serial number 0044270 MAC address 0072031B45CB D0 76 50 00 57 EC Art 01548 0072031B45CB Device certificate ABZAGG 2BZKDF 54SHGN OIPIXZ RRPF6Z A5GESR 01548 State Traffic Function IP TP GA PA ROU...

Page 8: ...the necessary knowledge and skills also required for troubleshooting by practical exercises Please read this chapter carefully before first use and installation 1 6 1 Installation and Commissioning I...

Page 9: ...KNX Data Secure format Activation of IP Backbone Security for protection of IP routing When additional protection becomes necessary for example the subline is located outside the building configuring...

Page 10: ...extra security to a KNX installation during commissioning as well as for KNX installations at runtime Difference between normal KNX devices and KNX Secure devices is KNX Secure devices have the abili...

Page 11: ...s compliant to IEEE802 3 The AutoSensing function sets the baud rate 10 Mbit or 100 Mbit automatically IP address can be received from a DHCP server For this the automatic assignment setting of the IP...

Page 12: ...2 Bus State Traffic Function LINE COUPLER Main Sub GA PA Sub Main 1 1 0 01504 2 Bus State Traffic Function LINE COUPLER Main Sub GA PA Sub Main 1 2 0 01548 State Traffic Function IP TP GA PA ROUTER I...

Page 13: ...ate can be found printed on a side label on the housing Device Certificates can be entered manually and by taking a QR code webcam picture After opening the project the Device Certificate list can be...

Page 14: ...For downloading an interface connection to the KNX bus system is required To program devices of a line different to which the device used as ETS Current Interface is connected a correct topology is ma...

Page 15: ...work administrator Figure 9 Automatic IP Address Assignment When the Use a static IP address option is chosen IP address Subnet Mask and Default Gateway can be set manually Figure 10 Manual IP Address...

Page 16: ...utton has to be pressed The status of an active special function is indicated by the LED display see chapter 1 3 LED Indication of Special Functions 4 6 1 Manual Function During normal operation a rat...

Page 17: ...on display again Table 7 Activation of Factory Reset Step Factory Reset 1 Hold Function button for 15 seconds 2 LEDs 1 2 now are orange 3 Hold Function button for 3 seconds 4 Device restarts 4 6 3 IP...

Page 18: ...ion setting for telegram routing when the Manual Fun ction is active Switch off time for Manual Function 10 min 1 hour 4 hours 8 hours 1 hour After expiry of this time period the Manual Function is sw...

Page 19: ...legrams are transmitted To set parameters different as available here use configure Group telegrams Main group 0 13 transmit all not recommended block filter filter Filtering of Group telegrams with m...

Page 20: ...31 transmit all not recommended block filter filter Filtering of Group telegrams with main groups 14 31 can be configured to route all telegrams no telegrams or only telegrams entered in the filter t...

Page 21: ...Tunneling Cannels To use IP Secure Tunneling both Secure Commissioning and Secure Tunneling must be activated in the Properties window of 01548 Then also the password protec tion option for each Tunn...

Page 22: ...en the web front end is set to only status info display remote control functions Program Mode activation Set Tunneling and the update function are off Only the informational readout is available To en...

Page 23: ...s factory default setting This means HTTP port is 8080 and DHCP is active The DHCP server assigned the IP address 192 168 1 201 Then in the browser s URL bar has to be entered http 192 168 1 201 8080...

Page 24: ...age busload on TP Figure 22 KNX Tab For showing the busload diagram the web browser must support SVG graphics For IP Tunneling four Individual Addresses can be set Setting a different Individual Addre...

Page 25: ...he boot mode it is necessary to enter the Update tab of the web front end Then either the firmware update has to be completed like shown by steps 1 to 5 or the firmware update process has to be stoppe...

Page 26: ...ile and enter boot mode Figure 26 Request Update Step 5 The update file can be selected and uploaded After that the device exits boot mode and restarts Clicking on the Abort button cancels the firmwar...

Page 27: ...r short an Object Group Telegram Group oriented telegrams are named Group Telegrams Filtering of Group Telegrams is accomplished according to the built in filter tables for group communication IACK se...

Page 28: ...oup 0 13 DHCP AutoIP Group telegrams main group 14 31 224 0 23 12 Physical telegrams filter KNX TP KNX TP Subline to IP Main line Group telegrams main group 0 13 filter filter table is empty Group tel...

Page 29: ...to IEC60529 Pollution degree 2 according to IEC60664 1 Protection class III according to IEC61140 Overvoltage category II according to IEC60664 1 Approbation KNX certified according to ISO IEC14543 3...

Page 30: ...successful What can I do Make sure the web front end is not deactivated and the URL bar entry matches the correct IP address together with the right HTTP port or use the MAC address in exactly the way...

Page 31: ...31...

Page 32: ...Viale Vicenza 14 36063 Marostica VI Italy www vimar com 01548 EN 01 2010...

Reviews: