INSTALLATION
2-2
October 1999
Part No. 001-2009-201
repeater or 6A for each 160W repeater and should be
protected by a circuit breaker. It is recommended that
all of the repeaters in a rack should not be on the same
breaker in order to provide one operational repeater in
the event a breaker trips. An AC surge protector is
recommended for all equipment.
Each Repeater requires an outlet and the Receiver
multicoupler and OCXO drawer require one each, so
for a 5-channel system a minimum of 7 outlets is
required. An additional three should be added for test
equipment. The outlets must be within 3 feet of each
Repeater cabinet. Future system expansion should be
considered when electrical work is being planned for
the initial system.
The VIKING VX Repeater power supply can be
equipped with an optional 24V DC back-up in the
event of AC power failure. Since the transmitter will
remain on full power, if desired, the DC power source
must have a current capability of about 15A per 75W
repeater (25A per 160W repeater) or 75A for 5-75W
repeaters (125A for 5-160W repeaters). The multicou-
pler requires another 1A for a total system requirement
at 24V DC of 76.5A for 75W repeaters (126.5A for
160W repeaters).
Figure 2-1 2000 SERIES POWER SUPPLY
2.5 BATTERY BACKUP
If the power supply is equipped with battery
backup, screw lugs are provided on the front of the
power supply for battery connections (see Figure 2-2).
A switch is provided for charging the battery or can be
off if a separate battery charger is used. A battery tem-
perature sensor connection is also provided. The tem-
perature sensor cable is shown in Figure 2-2. LED
indicators are provided to show Reverse Battery con-
nection, Charger On/Off and Battery Fault.
Figure 2-2 TEMPERATURE SENSOR CABLE
2.6 800W POWER SUPPLY
The power supply has four voltage output levels
(see Table 2-1). Each voltage is set to ±1% at +25°C
(+77°F). The output of this supply is capable or run-
ning any 2000 series repeater.
Each output is overload protected such that the
power supply current limits and automatically resets
when the overload is removed (see Table 2-1).
Each output is over voltage protected such that
the power supply shuts down when an over voltage
condition exists, usually when a component in the sup-
ply has failed (see Table 2-2). The power supply must
be manually reset by toggling the Enable Line or
removing AC power for more than 10 seconds.
B-
B+ TEMP
ACTIVE
CHARGER
ON
CHARGER
FAULT
BATTERY
BATTERY
REVERSE
GROUND
EARTH
NEUTRAL
LINE
SWITCH
Table 2-1 OUTPUT VOLTAGES
Voltage
Current
Wattage
+26.5V
22A
583W
+15V
5A
75W
+5.2V
5A
26W
-5V
1A
5W
Table 2-2 OVER VOLTAGE
Voltage
Range
+26.5V
+32V to +33V
+15V
+16V to +18V
+5.2V
+6V to +7V
-5V
-6V to -7V
BATTERY
TEMP
TERMINAL
NEGATIVE
GND
BLK
WHT
Summary of Contents for VX 900 MHz LTR
Page 2: ...1 2 October 1995 Part No 001 2008 202...
Page 4: ...1 4 October 1995 Part No 001 2008 202...
Page 24: ...INTRODUCTION AND OPERATION 1 10 October 1999 Part No 001 2009 201...
Page 26: ...INTRODUCTION AND OPERATION 1 12 October 1999 Part No 001 2009 201...
Page 40: ...INSTALLATION 2 14 October 1999 Part No 001 2009 201...
Page 56: ...PULL DOWN MENUS 4 12 October 1999 Part No 001 2009 201...
Page 60: ...REPEATER PROGRAMMING 5 4 October 1999 Part No 001 2009 201...
Page 142: ...SERVICING 8 8 October 1999 Part No 001 2009 201...