PULL DOWN MENUS
4-5
October 1999
Part No. 001-2009-201
ALARM DESCRIPTION
This is a text string (up to 15 characters) to
describe the alarm. This test string is sent via Morse
code if the alarm input is programmed with a Tx ID
and an output is selected in the cross reference menu
(see Figure 4-10
).
TRANSMIT ID
Each of the 4-alarm outputs can be assigned a
Group ID from 1-225 (default setting is 0 (zero) for
disabled). This Group ID and the Repeater number
identify an active alarm. This ID is programmed into
a transceiver so that when the alarm is active, the
alarm description is received in Morse code.
ALARM TRANSMIT RATE
This sets the time interval for transmitting the
alarm message (1-255 min, 0=disabled). If more than
one alarm is active, this is the inter-alarm time.
CROSS REFERENCE
The cross reference screen selects the output
alarm that is activated by each input alarm. There are
up to 48 alarms (0-47), 4 external input alarms and 40
internal alarms (see Table 1-2). There are four output
alarms. An alarm condition on any input can cause an
output alarm. This screen configures which input
alarm activates an output alarm.
NOTE: More than one alarm condition can have the
same output alarm (see Figure 4-10).
Figure 4-10 ALARM CROSS REFERENCE
4.3.4 REPEATER TYPE
This screen (see Figure 4-11
) selects the repeater
type (LTR signaling protocol and features):
Frequency Band
800 MHz
800 MHz [-
12.5 kHz]
900 MHz
Power Level
75W
160W
IAC Type
4 I/O IAC
8 I/O IAC
Figure 4-11 REPEATER TYPE
4.3.5 DELETE REPEATER
Figure 4-12 DELETE REPEATER
4.3.6 TELEPHONE PARAMETERS
Refer to the Telephone Interface Card manual,
Part No. 004-2000-370, for information on the Tele-
phone Access Parameters, Telephone Interface and
TIC Calibration Data.
4.4 TRANSFER
Figure 4-13 TRANSFER MENU
Select which Output Alarm is activated by each Input Alarm.
8. None
24. None
32. None
40. None
5. None
6. None
7. None
9. None
10. None
11. None
12. None
13. None
14. None
15. None
17. None
18. None
19. None
20. None
21. None
22. None
23. None
25. None
26. None
27. None
28. None
29. None
30. None
31. None
34. None
35. None
36. None
37. None
38. None
39. None
41. None
42. None
43. None
44. None
45. None
46. None
47. None
Alarm Cross Reference Selection
Press F2 to Accept
0. None
1. 1
2. 1
3. 2
4. 3
16. None
33. 4
Press F2 to Accept
LTR
Select the Repeater Type
Repeater Type Selection
Select Signaling Method (Spacebar)
IAC Type: 4 I/O IAC
Power Level: 160W
Freq Band: 900 MHz
Select Rptr To Delete
Rptr 1
File Edit Transfer Hardware Test Utilities
Read Setup Parms F5
Write Setup Parms F6
Edit Option Keys
Read TIC Calibration Data
Write TIC Calibration Data
Summary of Contents for VX 900 MHz LTR
Page 2: ...1 2 October 1995 Part No 001 2008 202...
Page 4: ...1 4 October 1995 Part No 001 2008 202...
Page 24: ...INTRODUCTION AND OPERATION 1 10 October 1999 Part No 001 2009 201...
Page 26: ...INTRODUCTION AND OPERATION 1 12 October 1999 Part No 001 2009 201...
Page 40: ...INSTALLATION 2 14 October 1999 Part No 001 2009 201...
Page 56: ...PULL DOWN MENUS 4 12 October 1999 Part No 001 2009 201...
Page 60: ...REPEATER PROGRAMMING 5 4 October 1999 Part No 001 2009 201...
Page 142: ...SERVICING 8 8 October 1999 Part No 001 2009 201...