ESFR PENDENT SPRINKLER 

UL: SPECIFIC APPLICATION ESFR SPRINKLER 

FM: STORAGE SPRINKLER

NFPA: SPECIAL SPRINKLER  

VK514 (K28.0)

TECHNICAL BULLETIN

Page 6 of 6

Form No. F_102422      Rev 01     October 2022

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

TABLE 6:

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW FOR 

NFPA 13 SPECIAL SPRINKLER VK514

Description

            50 Ft. (15,2 m) Ceilings

            55 Ft. (16,76 m) Ceilings

Sprinkler Type

QR Storage**

QR Storage**

Temperature Rating

165 ºF (74 ºC) and 205 ºF (96 ºC)

165 ºF (74 ºC) and 205 ºF (96 ºC)

Response Type

QR

QR

Sprinkler Position

Pendent, frame arms aligned with pipe, deflectors 

parallel to floor.

Pendent, frame arms aligned with pipe, deflectors 

parallel to floor.

System Type

Wet Pipe System only

Wet Pipe System only

Maximum Area of Coverage*

100 ft

2

 (9,29m

2

)

Refer to FM 2-0, Table 17

100 ft

2

 (9,29m

2

Refer to FM 2-0, Table 17

Minimum Area of Coverage

64 ft

2

 (5,9 m

2

Refer to FM 2-0, Table 17

64 ft

2

 (5,9 m

2

Refer to FM 2-0, Table 17

Maximum Ceiling Slope

Up to 10° 

Refer to FM 2-0, Section 2.2.1.6

Up to 10° 

Refer to FM 2-0, Section 2.2.1.6

Maximum Spacing

10 ft. (3,0 m)

10 ft. (3,0 m)

Minimum Spacing

8 ft. (2,4 m)

8 ft. (2,4 m)

Deflector Distance from Walls

Refer to FM 2-0, Section 2.2.3.3

Refer to FM 2-0, Section 2.2.3.3

Deflector to Top of Storage

Minimum of 36 inches (914 mm) 

Refer to FM 2-0 Section 2.2.2.1 

and FM 8-9, Section 2.2.6

Minimum of 36 inches (914 mm) 

Refer to FM 2-0 Section 2.2.2.1 

and FM 8-9, Section 2.2.6

Ceiling Sprinkler Installation 

Guidelines

As per FM 2-0 (DS 2-0), Installation Guidelines for 

Automatic Sprinklers with the following exception:

Vertical distance from underside of the ceiling to the 

centerline of the sprinkler’s thermal element - no more 

than 13 inches (325 mm)

As per FM 2-0 (DS 2-0), Installation Guidelines for 

Automatic Sprinklers with the following exception:

Vertical distance from underside of the ceiling to the 

centerline of the sprinkler’s thermal element - no more 

than 13 inches (325 mm)

Maximum Ceiling Height

50 ft. (15,2 m)

55 ft. (16,76 m)

Maximum Storage Height

45 ft. (13,5 m)

50 ft. (15,2 m)

Storage Arrangement

Solid-piled, palletized, shelf, bin-box, as well as single, 

double, and multi row racks that qualify as open-frame

Solid-piled, palletized, shelf, bin-box, as well as single-

row and double-row racks that qualify as open-frame

Storage Aisles Between Racks

Minimum 6 ft (1,8 m) wide

Minimum 8 ft (2,4 m) wide

Commodity

Class 1-4 Cartoned unexpanded plastics

Class 1-4 Cartoned unexpanded plastics

Sprinkler System Design

QR Storage Sprinkler based upon 10 @ 40 psi (2.8 

bar) design pressure @177 gpm (670 Lpm) with 9 

sprinkler remote area (3x3) on 3 branchlines and 1 

sprinkler on 1 branchline. 

Exception: a sprinkler design of 9 (3x3) @ 40 psi (2.8 

bar) design pressure @177 gpm (670 Lpm) when the 

water supply can also provide a design of 4 (2x2) @ 80 

psi (5.5 bar) design pressure @250 gpm (950 Lpm)

QR Storage Sprinkler based upon 9 @ 80 psi (5.5 

bar) design pressure with 250 gpm (950 Lpm) with 9 

sprinkler remote area (3x3) on 3 branchlines.

Obstruction Criteria

Refer to FM 2-0 Section 2.2

Refer to FM 2-0 Section 2.2

Hose  Stream  Allowance  and                                      

Water Supply Duration

250 gpm (950 Lpm) for 60 minutes

250 gpm (950 Lpm) for 60 minutes

* The maximum coverage area must not exceed 100 ft

2

 (9,29 m

2

).

** 

Approved storage sprinklers are also FM Approved for use as non-storage sprinklers.

Summary of Contents for VK514

Page 1: ...torage materials including Encapsulated or unencapsulated Class I II III and IV commodities UL Listed for protection of cartoned nonexpanded Group A plastic commodities FM Approved for protection of cartoned unexpanded plastic commodities Refer the Approval Chart and Commodity Selection and Design Criteria Overview for Listing and Approval requirements that must be followed The terms nonexpanded a...

Page 2: ...sequent leakage or impairment of the sprinkler E After installation the entire sprinkler system must be tested The test must be conducted to comply with the Installation Standards Make sure the sprinkler has been properly tightened If a thread leak occurs normally the unit must be removed new pipe joint compound or tape applied and then reinstalled This is due to the fact that when the joint seal ...

Page 3: ... products of combustion but have not operated should be replaced Refer to the Authorities Having Jurisdiction for minimum replacement requirements 8 AVAILABILITY The Viking Model VK514 Sprinkler is available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 9 GUARANTEE For details of warran...

Page 4: ...PT 28 0 404 3 3 16 81 A1 22894 VK514 1 NPT 28 0 404 3 3 16 81 A1 A1 22958 VK514 25 mm BSPT 28 0 404 3 3 16 81 A1 A1 Approved Temperature Ratings A 165 F 74 C and 205 F 96 C Approved Finish 1 Brass Footnotes 1 Base part number shown For complete part number refer to the price list 2 Metric K Factor measurement shown is when pressure is measured in bar When pressure is measured in kPa divide the met...

Page 5: ...of 4 in 102 mm from walls but no more than 1 2 the allowable distance permitted between sprinklers Deflector distance measured from ceiling to sprinkler deflector Minimum of 36 in 914 mm Sprinkler installation from ceiling For all building heights 6 14 in 152 356 mm Maximum Ceiling Height 48 ft 14 6 m Maximum Storage Height 43 ft 13 1 m Storage Arrangement Single and double row rack storage no ope...

Page 6: ...g Sprinkler Installation Guidelines As per FM 2 0 DS 2 0 Installation Guidelines for Automatic Sprinklers with the following exception Vertical distance from underside of the ceiling to the centerline of the sprinkler s thermal element no more than 13 inches 325 mm As per FM 2 0 DS 2 0 Installation Guidelines for Automatic Sprinklers with the following exception Vertical distance from underside of...

Reviews: