Viking VK514 Technical Bulletin Download Page 4

ESFR PENDENT SPRINKLER 

UL: SPECIFIC APPLICATION ESFR SPRINKLER 

FM: STORAGE SPRINKLER

NFPA: SPECIAL SPRINKLER  

VK514 (K28.0)

TECHNICAL BULLETIN

Page 4 of 6

Form No. F_102422      Rev 01     October 2022

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

 

Approval Chart

ESFR Pendent Sprinkler VK514 

Maximum 175 PSI (12 bar) WWP

Base Part 

Number

1

SIN

Thread Size

Nominal K-Factor

Overall Length

Listings and Approvals

3,4 

(Refer also to Tables 3 and 4.)

U.S.

metric

2

Inches

mm

UL

5

FM

6

19591

VK514

1” NPT

28.0

404

3-3/16

81

A1

--

19592

VK514

25 mm BSPT

28.0

404

3-3/16

81

A1

--

22894

VK514

1” NPT

28.0

404

3-3/16

81

A1

A1

22958

VK514

25 mm BSPT

28.0

404

3-3/16

81

A1

A1

Approved Temperature Ratings

A - 165 °F (74 °C) and 205 °F (96 °C)

Approved Finish

1 - Brass

Footnotes

1. 

Base part number shown. For complete part number, refer to the price list.

2. 

Metric K-Factor measurement shown is when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-Factor shown by 10.0.

3. 

This chart shows listings and approvals available at the time of printing. Other approvals may be in process. 

4. 

Refer to the latest standards of NFPA 13.

5. 

Listed by Underwriters Laboratories Inc. for use in the U.S. as an ESFR Sprinkler (refer to the deflector position requirements).

6. 

FM Approved as a quick response pendent Storage sprinkler. Refer toTables 3 & 5.

Figure 2: Sprinkler Dimensions

1-3/4” 

(45mm)

Protective Sprinkler 

Cap

Wrench Flat

Use Side B Only

3-3/16” 

(81mm)

1-9/16” 

(40mm)

1-5/8” 

(41mm)

Figure 1: Sprinkler Wrench

Summary of Contents for VK514

Page 1: ...torage materials including Encapsulated or unencapsulated Class I II III and IV commodities UL Listed for protection of cartoned nonexpanded Group A plastic commodities FM Approved for protection of cartoned unexpanded plastic commodities Refer the Approval Chart and Commodity Selection and Design Criteria Overview for Listing and Approval requirements that must be followed The terms nonexpanded a...

Page 2: ...sequent leakage or impairment of the sprinkler E After installation the entire sprinkler system must be tested The test must be conducted to comply with the Installation Standards Make sure the sprinkler has been properly tightened If a thread leak occurs normally the unit must be removed new pipe joint compound or tape applied and then reinstalled This is due to the fact that when the joint seal ...

Page 3: ... products of combustion but have not operated should be replaced Refer to the Authorities Having Jurisdiction for minimum replacement requirements 8 AVAILABILITY The Viking Model VK514 Sprinkler is available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 9 GUARANTEE For details of warran...

Page 4: ...PT 28 0 404 3 3 16 81 A1 22894 VK514 1 NPT 28 0 404 3 3 16 81 A1 A1 22958 VK514 25 mm BSPT 28 0 404 3 3 16 81 A1 A1 Approved Temperature Ratings A 165 F 74 C and 205 F 96 C Approved Finish 1 Brass Footnotes 1 Base part number shown For complete part number refer to the price list 2 Metric K Factor measurement shown is when pressure is measured in bar When pressure is measured in kPa divide the met...

Page 5: ...of 4 in 102 mm from walls but no more than 1 2 the allowable distance permitted between sprinklers Deflector distance measured from ceiling to sprinkler deflector Minimum of 36 in 914 mm Sprinkler installation from ceiling For all building heights 6 14 in 152 356 mm Maximum Ceiling Height 48 ft 14 6 m Maximum Storage Height 43 ft 13 1 m Storage Arrangement Single and double row rack storage no ope...

Page 6: ...g Sprinkler Installation Guidelines As per FM 2 0 DS 2 0 Installation Guidelines for Automatic Sprinklers with the following exception Vertical distance from underside of the ceiling to the centerline of the sprinkler s thermal element no more than 13 inches 325 mm As per FM 2 0 DS 2 0 Installation Guidelines for Automatic Sprinklers with the following exception Vertical distance from underside of...

Reviews: