ESFR PENDENT SPRINKLER 

UL: SPECIFIC APPLICATION ESFR SPRINKLER 

FM: STORAGE SPRINKLER

NFPA: SPECIAL SPRINKLER  

VK514 (K28.0)

TECHNICAL BULLETIN

Page 2 of 6

Form No. F_102422      Rev 01     October 2022

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

5.  INSTALLATION

NOTICE

Viking sprinklers are manufactured and tested to meet rigid requirements of the approving agencies. The sprinklers are designed 

to be installed in accordance with recognized installation standards or FM Global Loss Prevention Data Sheets. System design 

must be based on guidelines described in the latest edition of the applicable FM Global Loss Prevention Data Sheets indicated for 

Storage sprinklers, the latest NFPA Standards indicated for ESFR sprinklers, the Authority Having Jurisdiction, and also with the 

provisions of government codes, ordinances, and standards whenever applicable. Deviation from the standards or any alteration 

to the sprinkler after it leaves the factory including, but not limited to: painting, plating, coating, or modification, may render the 

sprinkler inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation.

A.  Sprinklers must be handled with care. They must be stored in a cool, dry place in their original shipping container. Never install 

sprinklers that have been dropped or damaged in any way. Such sprinklers should be destroyed immediately. 

B.  The sprinklers must be installed after the piping is in place to prevent mechanical damage. Before installing, be sure to have the 

appropriate sprinkler model and style, with the correct orifice size, temperature rating, and response characteristics.

C.  With the sprinkler contained in the plastic protective cap, apply a small amount of pipe-joint compound or tape to the male threads 

only, while taking care not to allow a build-up of compound in the sprinkler orifice.

D.  Use ONLY sprinkler wrench 13635W/B (shown in Figure 1) for installing VK514. With the sprinkler contained in the 

protective cap, install the sprinkler onto the piping by applying the sprinkler wrench to the sprinkler wrench flats only, 

while taking care not to damage the sprinkler operating parts.

•  DO NOT use any other type of wrench, as this could damage the unit.

•  DO NOT use the sprinkler deflector or fusible element to start or thread the sprinkler into a fitting.

•  Hand tight plus 1 to 1-1/2 turns with wrench. Over tightening may distort the sprinkler inlet with consequent leakage or 

impairment of the sprinkler.

E.  After installation, the entire sprinkler system must be tested. The test must be conducted to comply with the Installation 

Standards. Make sure the sprinkler has been properly tightened. If a thread leak occurs, normally the unit must be removed, new 

pipe-joint compound or tape applied, and then reinstalled. This is due to the fact that when the joint seal is damaged, the sealing 

compound or tape is washed out of the joint. Immediately replace any damaged units, using the special sprinkler wrench only.

F.  After installation and testing and repairing of all leaks, remove the protective caps from the sprinklers. Do NOT use 

any type of tool to remove the cap. Remove the cap by hand: turn it slightly and pull it off the sprinkler. When remov-

ing caps, use care to prevent dislodging or damaging sprinkler fusible element. THE CAPS MUST BE REMOVED FROM 

SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE.

6.  OPERATION

During fire conditions, the heat-sensitive fusible element assembly disengages, releasing the seat and belleville spring assembly 

to open the waterway. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to 

suppress the fire.

7.  INSPECTIONS, TESTS AND MAINTENANCE

NOTICE

The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For 

minimum maintenance and inspection requirements, refer to the NFPA standard that describes care and maintenance of 

sprinkler systems. In addition, the Authorities Having Jurisdiction may have additional maintenance, testing, and inspec-

tion requirements that must be followed.

NOTE: 

Wet pipe systems must be provided with adequate heat.

A.  The sprinklers must be inspected on a regular basis for corrosion, mechanical damage, obstructions, paint, etc. The frequency 

of inspections may vary due to corrosive atmosphere, water supplies, and activity around the device.

B.  Sprinklers that have been painted or mechanically damaged must be replaced immediately. Sprinklers showing signs of corrosion 

shall be tested and/or replaced immediately as required. Installation standards require sprinklers to be tested and, if necessary, 

replaced after a specified term of service. For Viking ESFR Pendent Sprinklers, refer to the Installation Standards and the Authorities 

Having Jurisdiction for the specified period of time after which testing and/or replacement is required. Sprinklers that have operated 

cannot be reassembled or reused, but must be replaced. When replacing sprinklers, use only new sprinklers.

C.  The sprinkler discharge pattern is critical for proper fire protection. Therefore, nothing should be hung from, attached to, or other-

wise obstruct the discharge pattern. All obstructions must be immediately removed or, if necessary, additional sprinklers installed.

Summary of Contents for VK514

Page 1: ...torage materials including Encapsulated or unencapsulated Class I II III and IV commodities UL Listed for protection of cartoned nonexpanded Group A plastic commodities FM Approved for protection of cartoned unexpanded plastic commodities Refer the Approval Chart and Commodity Selection and Design Criteria Overview for Listing and Approval requirements that must be followed The terms nonexpanded a...

Page 2: ...sequent leakage or impairment of the sprinkler E After installation the entire sprinkler system must be tested The test must be conducted to comply with the Installation Standards Make sure the sprinkler has been properly tightened If a thread leak occurs normally the unit must be removed new pipe joint compound or tape applied and then reinstalled This is due to the fact that when the joint seal ...

Page 3: ... products of combustion but have not operated should be replaced Refer to the Authorities Having Jurisdiction for minimum replacement requirements 8 AVAILABILITY The Viking Model VK514 Sprinkler is available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 9 GUARANTEE For details of warran...

Page 4: ...PT 28 0 404 3 3 16 81 A1 22894 VK514 1 NPT 28 0 404 3 3 16 81 A1 A1 22958 VK514 25 mm BSPT 28 0 404 3 3 16 81 A1 A1 Approved Temperature Ratings A 165 F 74 C and 205 F 96 C Approved Finish 1 Brass Footnotes 1 Base part number shown For complete part number refer to the price list 2 Metric K Factor measurement shown is when pressure is measured in bar When pressure is measured in kPa divide the met...

Page 5: ...of 4 in 102 mm from walls but no more than 1 2 the allowable distance permitted between sprinklers Deflector distance measured from ceiling to sprinkler deflector Minimum of 36 in 914 mm Sprinkler installation from ceiling For all building heights 6 14 in 152 356 mm Maximum Ceiling Height 48 ft 14 6 m Maximum Storage Height 43 ft 13 1 m Storage Arrangement Single and double row rack storage no ope...

Page 6: ...g Sprinkler Installation Guidelines As per FM 2 0 DS 2 0 Installation Guidelines for Automatic Sprinklers with the following exception Vertical distance from underside of the ceiling to the centerline of the sprinkler s thermal element no more than 13 inches 325 mm As per FM 2 0 DS 2 0 Installation Guidelines for Automatic Sprinklers with the following exception Vertical distance from underside of...

Reviews: