background image

cause distortion, possible misalignment, and probable 

rapid wear of the pump. Do not use the pump to correct 

errors in piping layout or assembly.

12. 

All joints of the piping system should be tight; pipe 

sealer will help assure leak-free threaded joints. Leaks 

in the suction line permitting air to be drawn in may 

cause a noisy pump or a reduction in capacity. It is not 

recommended to use PTFE tape on NPT ports as a pipe 

sealer. This action can result in cracks in the pump.

13. ALIGNMENT

 - Check the alignment of the drive after the 

piping is hooked up. As a final check on pump alignment, 

remove the head of the pump and with a feeler gauge 

determine if there is clearance all the way around between 

the rotor and casing. Because of manufacturing tolerances, 

bushing clearances, etc., the rotor may not be centered 

in the casing, but it should not drag; dragging would 

indicate unit misalignment or casing distortion from piping 

strain. Making this check is most desirable on installations 

involving Q, M and N size general purpose pumps.

14. 

The auxiliary piping hooked to jackets, glands, etc. for 

heating, cooling, quenching, or for other purposes should 

receive the same attention as the piping handling the 

pumped liquid.

15. 

Provide a pressure relief device in any part of a pump and 

piping system that can be valved off and, thus, completely 

isolated. This is particularly important:

a. 

When handling a cold liquid such as refrigeration 

ammonia that can warm up to ambient temperatures 

when the pump is shut off.

b. 

When handling a liquid such as asphalt or molasses 

that has to be heated before it can be pumped.

The rise in temperature causes the liquid to expand; if there 

is no provision for pressure relief in the closed off section, 

there is a chance that the pump or piping will rupture.

FIGURE A13

Go around the 

obstruction on 

the horizontal

Obstruction

DO THIS

NOT THIS

Obstruction

FIGURE A14

Keep Long Horizontal 

Line Below Liquid Level

DO THIS

NOT THIS

START UP

Before starting the pump, check the following:

1. 

Are there vacuum and pressure gauges on or near the 

pump? These gauges are the quickest and most accurate 

way of finding out what is happening in the pump.

2. 

Check alignment - See suggestions in the Alignment 

section of this manual.

3. 

Check piping to be sure there is no strain on the 

pump casing.

4. 

Rotate the pump shaft by hand to be sure it turns freely. 

MAKE SURE THE PUMP DRIVER IS LOCKED OUT OR 

CANNOT BE ENERGIZED BEFORE DOING THIS.

5. 

Jog motor to be sure it is turning in the right direction; refer 

to discussion on pump rotation under item 4 in 

General 

Installation Notes

 section.

6. 

Check any relief valves to be sure they are installed 

correctly. Refer to discussion on relief valves in 

General 

Installation Notes

 section.

7. 

Check suction piping to be sure:

a. 

It is all connected and tight

b. 

Valves are open

c. 

End of pipe is below liquid level

8. 

Check discharge piping to be sure:

a. 

It is all connected and tight

b. 

Valves are open

c. 

There is a place for the liquid to go

9. 

Lubricate any grease fitting on the pump using a #2 NLGI 

grease. Check any gear reducer, motor, coupling, etc. 

for instructions and lubricate as recommended by the 

manufacturer. See 

Engineering Service Bulletin  

ESB-515

 at the end of the 

Appendix

 for Viking standard 

grease types to check compatibility.

10. 

For packed pumps, loosen packing gland nuts so gland 

can be moved slightly by hand. Adjust gland to reduce 

leakage only after pump has run long enough to reach 

constant temperature. Packing should weep a little to keep 

it cool and lubricated.

11. 

Do not use the Viking pump to flush, pressure test or 

prove the system with water. Either remove the pump or 

run piping around it while flushing or testing. Pumping 

water, dirty or otherwise, can do more damage in a few 

minutes than months of normal service.

12. 

Check to be sure all guards are in place.

13. 

Check the pump to be sure it is heated to operating 

temperature (if jacketed or heat traced).

If the pump begins to deliver liquid within 60 seconds, it 

can continue to be operated. If liquid is not leaving the 

discharge port, stop the pump. Running the pump longer than 

one minute without liquid inside it can damage the pump. 

Review the steps just outlined, consider what the suction 

and discharge gauges indicate, and see 

Troubleshooting

 

section. If everything appears to be in order, put some liquid 

in the pump. This will help it prime.

The pump can be restarted. If nothing is flowing within two 

minutes, stop the pump. The pump is not a compressor; it will 

not build up much air pressure. It may be necessary to vent 

the discharge line until liquid begins to flow.

TSM 1741  |  Issue B  |  Page 15 of 20

© 2019 Viking Pump, Inc. • Cedar Falls, IA  

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

© Viking Pump, Inc.

Summary of Contents for 4197 Series

Page 1: ... Maintenance 19 ESB 515 19 Lubrication of Viking Pumps 19 Lubrication of Viking Reducers 19 Lubrication of Viking Associative Equipment 19 FIGURE 2 AS AK AL SIZES FIGURE 1 GG HJ HL SIZES INTRODUCTION The illustrations used in this manual are for identification purposes only and cannot be used for ordering parts Obtain a parts list from your Viking Pump representative Always give a complete name of...

Page 2: ...ump rotation may be reversed during operation pressure protection must be provided on both sides of pump Relief valve adjusting screw caps must always point towards suction side of the pump If pump rotation is reversed position of the relief valve must be changed Pressure relief valves cannot be used to control pump flow or regulate discharge pressure For additional information refer to Appendix G...

Page 3: ...Bulletin ESB 31 MAINTENANCE These pumps are designed for long trouble free service life under a wide variety of application conditions with minimum maintenance The points listed below will help provide long service life CLEANING PUMP Keep pump as clean as possible This will facilitate inspection adjustment and repair work and help prevent overlooking a dirt covered grease fitting STORAGE If pump i...

Page 4: ...m Name Of Part Item Name Of Part 1 Locknut 9 Bearing Retainer Washer 17 Idler Bushing 2 Bearing Spacer Collar 10 Casing 18 Idler and Bushing Assembly 3 End Cap for Bearing Housing 11 O Rings for Relief Valve 19 Head O Ring 4 Lip Seal for Bearing Housing 12 Relief Valve 20 Idler Pin 5 Ball Bearing Outer 13 Pipe Plug 21 Head and Idler Pin Assembly 6 Bearing Housing 14 Capscrew for Valve 22 Capscrew ...

Page 5: ...tscrew Setscrew Endcap Shaft Locknut Outer Ball Bearing Bearing Housing Inner Snap Ring Outer Snap Ring Shaft Snap Ring Inner Ball Bearing Bearing Retainer Washer Setscrew Shaft Locknut DANGER Before opening any Viking pump liquid chamber pumping chamber reservoir relief valve adjusting cap fitting etc be sure 1 That any pressure in the chamber has been completely vented through the suction or dis...

Page 6: ... them slowly by hand Spinning the bearings will damage the race and balls Make sure the bearings are clean then lubricate with non detergent SAE 30 weight oil and check for roughness Roughness can be determined by turning the outer race by hand Replace the bearings if they have roughness Be sure the shaft is free from nicks burrs and foreign particles that might damage the mechanical seal Scratche...

Page 7: ...ce can be pressed upon rotor hub See Figure 10 on page 7 or Figure 13 on page 8 To disassemble the rotating portion of the seal compress the carbon face and rapidly depress the retaining ring through the notch at the end of the retainer cartridge as shown in Figure 14 on page 8 Press the retainer cartridge onto the rotor hub See Figure 11 on page 7 At the factory an installation tube is used to pr...

Page 8: ...ler pin which is offset in the pump head is positioned toward and equal distance between the port connections to allow for proper flow of liquid through the pump 4 Tighten the head capscrews evenly 5 If the pump was equipped with a relief valve and was removed during disassembly install on the head with new gaskets The relief valve adjusting screw cap must always point towards the suction port Ref...

Page 9: ...aring assembly Turn the thrust bearing assembly clockwise until it can no longer be turned by hand Back off counter clockwise until the rotor shaft can be turned by hand with a noticeable drag 2 Make a mark on the outside diameter of the bearing housing and a corresponding mark on the casing 3 For standard end clearance back off the thrust bearing assembly the required length measured on the outsi...

Page 10: ... discharge line for actual adjusting operation 3 Turn adjusting screw CW in to increase pressure and CCW out to decrease pressure For guidance dimensions contact your Viking Pump representative for Engineering Standard ES 37 4 Close the discharge line at a point beyond the pressure gauge Limit the amount of time the pump is being operated at this condition The temperature inside the pump will rise...

Page 11: ...tions including right hand and left hand 4 Suction Discharge shaft rotation will determine which port is suction and which is discharge A look at Figure A3 will show how rotation determines which port is which As the pumping elements gears come out of mesh point A on Figure A3 liquid is drawn into the suction port Then at point B the gears come into mesh and the liquid is forced out the discharge ...

Page 12: ... reached at which all of the liquid being pumped is going through the valve This pressure is the relief valve setting Viking pumps can be furnished with either an internal pressure relief valve one which directs the flow from the valve back to the suction side of the pump or a return to tank valve which directs the flow through piping back to the supply tank See Figure A5 A and Figure A5 B An inli...

Page 13: ...sult in personal injury and or damage to the unit FIGURE A9 EXAMPLE OF IMPROPER LIFTING METHOD NOTE NEVER lift the unit with slings connected to the component lifting features The lifting features are designed for the individual component and are not rated to lift the entire unit Improper lifts can result in personal injury and or damage to the unit FIGURE A10 A Check width between these surfaces ...

Page 14: ...on or discharge line go around the obstacle instead of over it Going over it creates an air pocket See Figure A13 5 Where practical slope the piping so no air or liquid pockets will be formed Air pockets in the suction line make it hard for the pump to prime 6 For a suction line with a long horizontal run keep the horizontal portion below the liquid level if possible This keeps the pipe full of li...

Page 15: ...s manual 3 Check piping to be sure there is no strain on the pump casing 4 Rotate the pump shaft by hand to be sure it turns freely MAKE SURE THE PUMP DRIVER IS LOCKED OUT OR CANNOT BE ENERGIZED BEFORE DOING THIS 5 Jog motor to be sure it is turning in the right direction refer to discussion on pump rotation under item 4 in General Installation Notes section 6 Check any relief valves to be sure th...

Page 16: ...ossibly an air leak insufficient liquid above the end of the suction pipe c Vibrating from cavitation misalignment or damaged parts PRESSURE GAUGE DISCHARGE PORT 1 High reading would indicate a High viscosity small diameter discharge line or long discharge line b Gate valve is partially closed c Filter is plugged d Vertical head did not consider a high specific gravity liquid e Line is partially p...

Page 17: ...tern on all parts Rapid wear occurring in a few minutes hours or days shows up as heavy grooving galling twisting breaking or similar severe signs of trouble See Rapid Wear Table RAPID WEAR RAPID WEAR TABLE CAUSE EVIDENCE POSSIBLE SOLUTION 1 ABRASIVES Gouges or marks made by large hard particles a rapid wearing away of bushings from very small abrasives or anything in between Flush the system with...

Page 18: ...d and a light coat of non detergent SAE 30 weight oil must be applied to all internal pump parts Lubricate fittings and apply grease to pump shaft extension Viking suggests rotating pump shaft by hand one complete revolution every 30 days to circulate the oil Retighten all gasketed joints before using the pump DO S DON TS Do s and Don ts for installation operation and maintenance of Viking pumps t...

Page 19: ...ose polyurea grease Grease used for bracket bushing when seal is behind rotor Petrolatum Chevron Petrolatum Snow White Grease used for O Pro Seal Edible Grease aluminum complex Chevron FM ALC EP 0 1 2 Lubricate each grease fitting every 500 hours of operation or every six months whichever occurs first If service is severe grease more often Be sure the grease is compatible with the grease used by V...

Page 20: ...S EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO ALL WARRANTIES OF MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE AND NON INFRINGMENT ALL OF WHICH OTHER WARRANTIES ARE EXPRESSLY EXCLUDED THE RIGHTS AND REMEDIES UNDER THIS WARRANTY ARE AND SHALL BE THE SOLE AND EXCLUSIVE RIGHTS AND REMEDIES AGAINST VIKING EXCEPT FOR THE SPECIFIC LIABILITIES AND OBLIGATIONS PROVIDED UNDER THIS WARRANTY VIKING SHA...

Reviews: