SPECIFICATIONS 

 

FP1136 

FP1137 

Weight 

17kg 

42kg 

Size 

550 x 440 x 210mm 

575 x 885 x 388mm 

PSU Output Current (Peak) 

5A 

10A 

DC Supply Voltage 

19.2Vmin - 28.8Vmax 

19.2Vmin - 28.8Vmax 

Operating Temperature Range 

-5C to +45C 

-5C to +45C 

Relative Humidity 

0 to 95% non-condensing 

0 to 95% non-condensing 

Storage Temperature Range 

-20C to +70C 

-20C to +70C 

Quiescent Current 

 

 

  Power Save Mode (Audio turned off) 

65mA 

65mA 

  Audio enabled but idle (no audio) 

190mA 

190mA 

Active Current

 -  27Vdc (plus Strobe) 

3.0A @ 60W 

6.0A @ 120W 

Avg Alarm Current 

(plus Strobe)

 

 

 

AS4428.16 Evacuate Tone 

1A @ 60W 

2A @ 120W 

AS2220.1 Evacuate Tone 

2.4A @ 60W 

4.8A @ 120W 

100V Output 

 

 

Line Voltage  - AC (Tones) 

100V rms 

100V rms 

                     - DC (Supervision) 

2.5V (56k ELD 5.0V (O/C)) 

2.5V (56k ELD 5.0V (O/C)) 

Line Power   - Tones 

60W rms 

120W rms 

                     - Audio 

60W rms 

120W rms 

Maximum line capacitance 

200nF 

200nF 

Audio Frequency range 

 

 

+/- 1dB 

260Hz 

– 3800Hz 

260Hz 

– 3800Hz 

+/- 3dB 

215Hz 

– 8400Hz 

215Hz 

– 8400Hz 

100V Speaker Line Supervision   

 

 

ELD  

-  1 Branch 

56k 0.4W 

56k 0.4W 

              -  2 Branches 

100k 0.4W 

100k 0.4W 

Strobe Output 

 

 

ELD         - 1 to 3 branches 

1x10k - 3 x 27k 0.4W 

1x10k - 3 x 27k 0.4W 

Current rating 

Max 2.0A 

Max 2.0A 

Audio Inputs 

 

 

Audio 1 & Audio 2 

230mVrms (min) into 5k

 

isolated for full power 

230mVrms (min) into 5k

  

isolated for full power 

Microphone - Input Level 

3mVrms-100mVrms, PTT driven, supervised 

3mVrms-100mVrms, PTT driven, supervised 

Digital Inputs 

 

 

Alarm, AIE, GP1-4 

10k EOL, <3.5V Active 

10k EOL, <3.5V Active 

Open Collector O/Ps 

 

 

OC1 & OC2 

<1V @ 100mA, 30Vdc 

Optionally Load Supervised ( fault <12V) 

<1V @ 100mA, 30Vdc 

Optionally Load Supervised ( fault <12V) 

OC3 & OC4 

<1V @ 100mA, 30Vdc 

<1V @ 100mA, 30Vdc 

Interfaces 

 

 

OLED, 4 button menu structured 

 

 

QBus compliant 

Master / Slave operation, User Interface and 

100V Switching Module  

Master / Slave operation, User Interface and 

100V Switching Module  

Slave T-Gen2 

RJ45 cable within cabinet 

RJ45 cable within cabinet 

On-board Storage 

4MB (configuration and audio files) 

4MB (configuration and audio files) 

Micro-SD Card 

32GB FAT32 support 

32GB FAT32 support 

Headphone Output 

(internal

- Load 

impedance 

8

 min 6mW 

8

 min 6mW 

Summary of Contents for T-Gen2

Page 1: ...s 100V output into 4 short circuit isolated outputs that can also be used to direct paging announcements to specific areas FP1118 100V Splitter Module This splits the T Gen2 s 100V output into 4 shor...

Page 2: ...urther details for configuring wiring the T Gen2 are contained in LT0667 and in the SmartConfig on line help file for preparing a custom configuration for the T Gen2 CONFIGURATION 1 T Gen2 Configurati...

Page 3: ...xternal Wiring 8U Cabinet Cable Entry There are four 20mm and two 50mm and knockouts provided in the top and bottom of the cabinet as well as a 20mm knockout provided in the top for mains wiring entry...

Page 4: ...12V 17Ah batteries the 18U cabinet has space for a pair of 12V 75Ah batteries The BOWS panels are supplied with a red battery lead for joining the neg terminal on the 1st battery to the pos on the 2n...

Page 5: ...ctions Re configure the master T Gen2 to include a Slave T Gen at address 1 using SmartConfig Paging The BOWS can be configured for area paging using FP1117 100V Switching Modules and the Paging butto...

Page 6: ...rent decreasing to a combined 120W load with a total strobe current of 4A Figure 6 FP1137 T Gen2 100V Load vs Strobe Current Battery Capacity For simplicity the required battery capacity has been calc...

Page 7: ...z 215Hz 8400Hz 100V Speaker Line Supervision ELD 1 Branch 56k 0 4W 56k 0 4W 2 Branches 100k 0 4W 100k 0 4W Strobe Output ELD 1 to 3 branches 1x10k 3 x 27k 0 4W 1x10k 3 x 27k 0 4W Current rating Max 2...

Page 8: ...19 rack mounting door complete with a Grade 3 user interface and PA microphone ready for connection to a T Gen60 or T Gen120 mounted inside the cabinet A 1 5m power loom and microphone extension loom...

Reviews: