background image

 

LT0676 Issue 1.00 

         6 December 2017 

Page 5 of 8 

100V Switching Module Field Wiring 
 

Refer to the 100V Switching Module Installation Instructions (LT0668) for details on fitting and wiring this optional 
module. 
 
 

100V Splitter Module Field Wiring 
 

Refer to the 100V Splitter Module Installation Instructions (LT0671) for details on fitting and wiring this optional module. 
 
 

Expansion T-Gen2 
 

Fit the expansion T-Gen2 as per the instructions in LT0667.  Connect 24V from the master T-Gen2 to the expansion  
T-Gen2 module, using red/black power wires. 
 
Using the supplied RJ45 cable, connect the master T-Gen2 QBus OUT connector (J28) to the expansion T-Gen2 QBus 
IN connector (J27). 
 
Configure the expansion T-Gen2 with the Slave configuration and address 1 (refer to LT0667 for instructions). 
Re-configure the master T-Gen2 to include a Slave T-Gen at address 1 using SmartConfig. 
 
 

Paging 
 

The BOWS can be configured for area paging using FP1117 100V Switching Modules and the Paging buttons on the 
User Interface, or an external paging console.  Refer to the T-Gen2 Installation & Wiring Instructions LT0667 for details. 
 
 

PSU Rating 
 

The BOWS is supplied with a 5A (FP1136) or 10A (FP1137) maximum current PSU. This limits the load that can be 
connected to the T-Gen2 units, as AS 1670.1:2015 requires the PSU to be able to supply the full alarm load without any 
batteries connected. 
 
Figure 5 shows the 100V load that can be connected to the FP1136 BOWS with 1 and 2 T-Gen 60 units and varying 
strobe currents. 
 
Basically the FP1136 PSU can support: 

 

1 x T-Gen 60 @ 60W load with up to 2A strobe load. 

 

2 x T-Gen 60 @ 50W load each with no strobe load, decreasing to a combined 20W load with a total of 4A 
strobe load. 

 

 

 

Figure 5 

– FP1136 T-Gen2 100V Load vs Strobe Current

 

Summary of Contents for T-Gen2

Page 1: ...s 100V output into 4 short circuit isolated outputs that can also be used to direct paging announcements to specific areas FP1118 100V Splitter Module This splits the T Gen2 s 100V output into 4 shor...

Page 2: ...urther details for configuring wiring the T Gen2 are contained in LT0667 and in the SmartConfig on line help file for preparing a custom configuration for the T Gen2 CONFIGURATION 1 T Gen2 Configurati...

Page 3: ...xternal Wiring 8U Cabinet Cable Entry There are four 20mm and two 50mm and knockouts provided in the top and bottom of the cabinet as well as a 20mm knockout provided in the top for mains wiring entry...

Page 4: ...12V 17Ah batteries the 18U cabinet has space for a pair of 12V 75Ah batteries The BOWS panels are supplied with a red battery lead for joining the neg terminal on the 1st battery to the pos on the 2n...

Page 5: ...ctions Re configure the master T Gen2 to include a Slave T Gen at address 1 using SmartConfig Paging The BOWS can be configured for area paging using FP1117 100V Switching Modules and the Paging butto...

Page 6: ...rent decreasing to a combined 120W load with a total strobe current of 4A Figure 6 FP1137 T Gen2 100V Load vs Strobe Current Battery Capacity For simplicity the required battery capacity has been calc...

Page 7: ...z 215Hz 8400Hz 100V Speaker Line Supervision ELD 1 Branch 56k 0 4W 56k 0 4W 2 Branches 100k 0 4W 100k 0 4W Strobe Output ELD 1 to 3 branches 1x10k 3 x 27k 0 4W 1x10k 3 x 27k 0 4W Current rating Max 2...

Page 8: ...19 rack mounting door complete with a Grade 3 user interface and PA microphone ready for connection to a T Gen60 or T Gen120 mounted inside the cabinet A 1 5m power loom and microphone extension loom...

Reviews: