background image

 

LT0676 Issue 1.00 

         6 December 2017 

Page 6 of 8 

Figure 6 shows the 100V load that can be connected to the FP1137 BOWS with 1 and 2 T-Gen 120 units and varying 
strobe currents. 
 
Basically the FP1137 10A PSU will support: 

 

1 x T-Gen 120 @ 120W load with up to 2A strobe current 

 

2 x T-Gen 120 @ 100W load each with no strobe current, decreasing to a combined 120W load with a total 
strobe current of 4A. 
 

 

 

Figure 6 

– FP1137 T-Gen2 100V Load vs Strobe Current 

 

 

Battery Capacity 

 
For simplicity the required battery capacity has been calculated as follows.

 

 

# T-Gen2 Units 

FP1136 

FP1137 

12 AHr 

17 AHr 

17 AHr 

24 AHr 

 
This provides 24 hour standby operation with the T-Gen2 in the audio-enabled state, plus 30 minutes in alarm at the full 
load supported by that BOWS unit. There is reserve capacity to power one 100V Switching or 100V Splitter Module as 
well. 

Summary of Contents for T-Gen2

Page 1: ...s 100V output into 4 short circuit isolated outputs that can also be used to direct paging announcements to specific areas FP1118 100V Splitter Module This splits the T Gen2 s 100V output into 4 shor...

Page 2: ...urther details for configuring wiring the T Gen2 are contained in LT0667 and in the SmartConfig on line help file for preparing a custom configuration for the T Gen2 CONFIGURATION 1 T Gen2 Configurati...

Page 3: ...xternal Wiring 8U Cabinet Cable Entry There are four 20mm and two 50mm and knockouts provided in the top and bottom of the cabinet as well as a 20mm knockout provided in the top for mains wiring entry...

Page 4: ...12V 17Ah batteries the 18U cabinet has space for a pair of 12V 75Ah batteries The BOWS panels are supplied with a red battery lead for joining the neg terminal on the 1st battery to the pos on the 2n...

Page 5: ...ctions Re configure the master T Gen2 to include a Slave T Gen at address 1 using SmartConfig Paging The BOWS can be configured for area paging using FP1117 100V Switching Modules and the Paging butto...

Page 6: ...rent decreasing to a combined 120W load with a total strobe current of 4A Figure 6 FP1137 T Gen2 100V Load vs Strobe Current Battery Capacity For simplicity the required battery capacity has been calc...

Page 7: ...z 215Hz 8400Hz 100V Speaker Line Supervision ELD 1 Branch 56k 0 4W 56k 0 4W 2 Branches 100k 0 4W 100k 0 4W Strobe Output ELD 1 to 3 branches 1x10k 3 x 27k 0 4W 1x10k 3 x 27k 0 4W Current rating Max 2...

Page 8: ...19 rack mounting door complete with a Grade 3 user interface and PA microphone ready for connection to a T Gen60 or T Gen120 mounted inside the cabinet A 1 5m power loom and microphone extension loom...

Reviews: