LT0676 Issue 1.00 

         6 December 2017 

Page 4 of 8 

 

 

Figure 3 

– 18U Cabinet Cable Knockouts 

 

To prevent water entering the cabinets, seal unused knockouts and any top cable entries.  Where possible, use bottom 
cable entry with cables going down 100 mm below the cabinet before rising. 

 
 
Mains Wiring 

 

The BOWS needs to be supplied with a current-limited mains feed (e.g., via a circuit breaker) direct from a main 
switchboard (refer AS 3000). 
 
The General Purpose Outlet (GPO) must be wired by a suitably qualified electrician. 
 
IMPORTANT:  The factory-fitted earth loom under the GPO mounting block must be wired to the earth terminal of the 
GPO in order to correctly earth the BOWS cabinet. 
 
 

Battery Wiring 
 

The 8U cabinet has space for a pair of 12V 17Ah batteries, the 18U cabinet has space for a pair of 12V 75Ah batteries. 

The BOWS panels are supplied with a red battery lead for joining the neg(-) terminal on the 1st battery to the pos(+) on 
the 2

nd

 battery, and the screws, washers and nuts required for attaching the leads to the batteries. 

 

 
 
 
 
 
 
 
 
 
 
 
 

Figure 4 - Battery Wiring 

 
 

Factory Wiring 
 

The PSU 24V output is wired to the T-Gen2 +24V terminals and the PSU Charger Flt- signal is wired to the A/I/E- input.  
The default BOWS configuration for T-Gen2 sets the A/I/E- input as External PSU Fault, allowing a PSU fault to signal 
via the T-Gen2. 
 
The User Interface and microphone are connected to the T-Gen2 QBus connector J32 and PA MIC Connector J9 
respectively. 
 
 

T-Gen2 Field Wiring 
 

Refer to the T-Gen2 Installation and Operating Instructions (LT0667) included with the BOWS for details on connecting 
field wiring to the T-Gen2 and how to use the OLED display on the T-Gen2. 
 

Red 

Black 

Summary of Contents for T-Gen2

Page 1: ...s 100V output into 4 short circuit isolated outputs that can also be used to direct paging announcements to specific areas FP1118 100V Splitter Module This splits the T Gen2 s 100V output into 4 shor...

Page 2: ...urther details for configuring wiring the T Gen2 are contained in LT0667 and in the SmartConfig on line help file for preparing a custom configuration for the T Gen2 CONFIGURATION 1 T Gen2 Configurati...

Page 3: ...xternal Wiring 8U Cabinet Cable Entry There are four 20mm and two 50mm and knockouts provided in the top and bottom of the cabinet as well as a 20mm knockout provided in the top for mains wiring entry...

Page 4: ...12V 17Ah batteries the 18U cabinet has space for a pair of 12V 75Ah batteries The BOWS panels are supplied with a red battery lead for joining the neg terminal on the 1st battery to the pos on the 2n...

Page 5: ...ctions Re configure the master T Gen2 to include a Slave T Gen at address 1 using SmartConfig Paging The BOWS can be configured for area paging using FP1117 100V Switching Modules and the Paging butto...

Page 6: ...rent decreasing to a combined 120W load with a total strobe current of 4A Figure 6 FP1137 T Gen2 100V Load vs Strobe Current Battery Capacity For simplicity the required battery capacity has been calc...

Page 7: ...z 215Hz 8400Hz 100V Speaker Line Supervision ELD 1 Branch 56k 0 4W 56k 0 4W 2 Branches 100k 0 4W 100k 0 4W Strobe Output ELD 1 to 3 branches 1x10k 3 x 27k 0 4W 1x10k 3 x 27k 0 4W Current rating Max 2...

Page 8: ...19 rack mounting door complete with a Grade 3 user interface and PA microphone ready for connection to a T Gen60 or T Gen120 mounted inside the cabinet A 1 5m power loom and microphone extension loom...

Reviews: