Initial start−up, inspection and maintenance
5
Implementation
To obtain the optimum combustion values, it is essential to adjust the burner
with the boiler heated to operating temperature.
Check the CO content, CO
2
content, flue gas temperature, room temperature
and chimney draught after 2minutes operation and at 60
º
C boiler water
temperature with fitted burner hood.
Remove the burner hood before commencing maintenance work.
1. System start−up
I
nitial start−up
Service instructions
Boiler control unit
Please note:
Vitoflame 200 oil burners have
excellent combustion values which
are achieved without the use of fuel
oil additives to improve combustion.
We do not therefore recommend the
use of such combustion improvers.
1.
Check whether the flame tube
attachment (for 15 to 33 kW
output) has been fitted.
2.
Check the heating system
pressure and the oil level in the
tank.
3.
Open the shut−off valves in the oil
supply lines on the oil tank and on
the filter.
4.
Fill the oil suction line and filter
with fuel oil using the manual oil
suction pump
before
switching on
the burner.
5.
Switch on the mains electrical
isolator (outside the boiler room).
6.
Switch on system On/Off
switch
B
on the control unit.
If fault indicator lamp
A
on the
control unit illuminates, press reset
button
C
on the burner.
Please note:
For Vitorond 222:
For balanced flue operation the air
supply duct should be fitted before
burner setup. Observe the following
values during this step:
H
Pressure loss in the air supply duct
max. 35 Pa,
H
Air inlet temperature in the inlet
adaptor min. 5°C/max. 30°C.
5692452 GB